Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.2 LAccepted-AOC | ₹49.2 L Quoted ₹49.3 L | L1 | Accepted-AOC L1 Accepted |
| 2 | L2₹49.4 LRejected-AOC | ₹49.4 L | L2 | Rejected-AOC L2 Rejected |
| Sl No | Description | Qty | Unit | PIONEER COOLTECH L1 | seasoncontrol L2 |
|---|---|---|---|---|---|
| 1.00Installation of AC | |||||
| 1.00 | OD18114/2025-2026:AIR HANDLING UNITS Supply Installation Testing and Commissioning of Floor/Ceiling mounted DX ODU compatible Double skin Air handling unit with thermal break profile with panel thickness of 40 mm, with 40 kg density complete with DX coil ,Plug fan with VFD, Fan motor shall be of efficiency grade IE2 , outer skin of 0.6 mm pre-coated GSS and inner skin of 0.6 mm plain GSS, The Air Handling Unit shall consist of Mixing Box with fresh air intakes with dampers, filter section with 10 micron Pre filter (MERV 7), 5 micron fine filter(MERV 14) ,0.3 Micron HEPA filters, Twin circuit Coil section with4 Row DX cooling coil, access door, marine light, outlet flange, & vibration isolators. Units shall be Eurovent certified, VFD drive motor suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply drain connections, stainless steel drain pan/tray with SS 304 with nitrile rubber insulation, 22 TR, 8800 CFM with minimum 125mm TSP. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including replacing of defective components of the unit etc: as required. | 1 | each | 9,46,485 ₹9.5 L | 9,46,490 ₹9.5 L |
| 1.00 | OD18122/2025-2026:AIR HANDLING UNITS- Supply Installation Testing and Commissioning of Floor/Ceiling mounted DX ODU compatible Double skin Air handling unit with thermal break profile with panel thickness of 40 mm, with 40 kg density complete with DX coil ,Plug fan with VFD, Fan motor shall be of efficiency grade IE2 , outer skin of 0.6 mm pre-coated GSS and inner skin of 0.6 mm plain GSS, The Air Handling Unit shall consist of Mixing Box with fresh air intakes with dampers, filter section with 10 micron Pre filter (MERV 7), 5 micron fine filter(MERV 14) ,0.3 Micron HEPA filters, Twin circuit Coil section with4 Row DX cooling coil, access door, marine light, outlet flange, & vibration isolators. Units shall be Eurovent certified, VFD drive motor suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply drain connections, stainless steel drain pan/tray with SS 304 with nitrile rubber insulation, 11 TR, 4400 CFM with minimum 125mm TSP. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including replacing of defective components of the unit etc: as required. | 1 | each | 5,60,980 ₹5.6 L | 5,60,992 ₹5.6 L |
| 1.00 | OD18125/2025-2026:OUTDOOR UNITS - Supply Installation Testing and Commissioning of following 13HP air-cooled Inverter Type DX Condensing Unit consisting of Hermetically Sealed, High effieincy Inverter Scroll Compressor, Copper refrigerant coil, fan motor assembled in, powder coated metal enclosure with HP/LP safety switch microprocessor-based control unit protection relays contactors etc, suitable for operation on R 410A gas complete Air-cooled compresssor with accessories, connection wire, antivibration pad, necessary AHU kit, etc. suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including gas topup and replacing of defective components of the unit etc: as require. | 2 | each | 2,59,980 ₹5.2 L | 2,59,998 ₹5.2 L |
| 1.00 | OD18124/2025-2026:OUTDOOR UNITS - Supply Installation Testing and Commissioning of following 7.5HP air-cooled Inverter Type DX Condensing Unit consisting of Hermetically Sealed, High effieincy Inverter Scroll Compressor, Copper refrigerant coil, fan motor assembled in, powder coated metal enclosure with HP/LP safety switch microprocessor-based control unit protection relays contactors etc, suitable for operation on R 410A gas complete Air-cooled compresssor with accessories, connection wire, antivibration pad, necessary AHU kit, etc. suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including gas topup and replacing of defective components of the unit etc: as required. | 2 | each | 1,61,980 ₹3.2 L | 1,62,000 ₹3.2 L |
| 1.00 | OD18118/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 12.77 mm. | 40 | metre | 1,149.6 ₹45,984 | 1,149.8 ₹45,992 |
| 1.01 | OD18130/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 15.88 mm. | 30 | metre | 1,353.5 ₹40,605 | 1,354 ₹40,620 |
| 1.01 | OD18123/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 22.23 mm. | 40 | metre | 1,676.2 ₹67,048 | 1,676.55 ₹67,062 |
| 1.01 | OD18113/2025-2026:REFRIGERANT PIPE - Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 28.58 mm. | 30 | metre | 1,954.5 ₹58,635 | 1,955 ₹58,650 |
| 1.01 | 16.16:Supplying & fixing of powder coated extruded aluminum Return Air Grills with louvers but without volume control dampers complete as required. | 5 | sqm | 6,804 ₹34,020 | 6,805 ₹34,025 |
Tender Value
₹49.4 L
EMD Value
₹50,000
Closing Date
26 Feb 2026, 6:00 pmClosed
Chief Electrical Engineer
Office of the Chief Electrical Engineer PWD Electrical Wing Public Office Thiruvananthapuram
GENERAL Health Department Annual Plan 2023 24 Implementation of Plan scheme Developing Super Specialty Facilities Various electrical works in Super Specialty Block 4th floor AA Rahim Memorial District Hospital Kollam Electrical AC Work
2026_PWD_837348_1
PWD/BLDG/TR/3148/2023_13_1_1
Open Tender
Electrical Works
240 days
AA Rahim Memorial District Hospital Kollam
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
Yes
21 Mar 2026
18 Feb 2026
28 Feb 2026
18 Feb 2026
26 Feb 2026
18 Feb 2026
18 Feb 2026 - 26 Feb 2026
Installation of AC
OD18114/2025-2026:AIR HANDLING UNITS Supply Installation Testing and Commissioning of Floor/Ceiling mounted DX ODU compatible Double skin Air handling unit with thermal break profile with panel thickness of 40 mm, with 40 kg density complete with DX coil ,Plug fan with VFD, Fan motor shall be of efficiency grade IE2 , outer skin of 0.6 mm pre-coated GSS and inner skin of 0.6 mm plain GSS, The Air Handling Unit shall consist of Mixing Box with fresh air intakes with dampers, filter section with 10 micron Pre filter (MERV 7), 5 micron fine filter(MERV 14) ,0.3 Micron HEPA filters, Twin circuit Coil section with4 Row DX cooling coil, access door, marine light, outlet flange, & vibration isolators. Units shall be Eurovent certified, VFD drive motor suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply drain connections, stainless steel drain pan/tray with SS 304 with nitrile rubber insulation, 22 TR, 8800 CFM with minimum 125mm TSP. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including replacing of defective components of the unit etc: as required.
OD18122/2025-2026:AIR HANDLING UNITS- Supply Installation Testing and Commissioning of Floor/Ceiling mounted DX ODU compatible Double skin Air handling unit with thermal break profile with panel thickness of 40 mm, with 40 kg density complete with DX coil ,Plug fan with VFD, Fan motor shall be of efficiency grade IE2 , outer skin of 0.6 mm pre-coated GSS and inner skin of 0.6 mm plain GSS, The Air Handling Unit shall consist of Mixing Box with fresh air intakes with dampers, filter section with 10 micron Pre filter (MERV 7), 5 micron fine filter(MERV 14) ,0.3 Micron HEPA filters, Twin circuit Coil section with4 Row DX cooling coil, access door, marine light, outlet flange, & vibration isolators. Units shall be Eurovent certified, VFD drive motor suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply drain connections, stainless steel drain pan/tray with SS 304 with nitrile rubber insulation, 11 TR, 4400 CFM with minimum 125mm TSP. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including replacing of defective components of the unit etc: as required.
OD18125/2025-2026:OUTDOOR UNITS - Supply Installation Testing and Commissioning of following 13HP air-cooled Inverter Type DX Condensing Unit consisting of Hermetically Sealed, High effieincy Inverter Scroll Compressor, Copper refrigerant coil, fan motor assembled in, powder coated metal enclosure with HP/LP safety switch microprocessor-based control unit protection relays contactors etc, suitable for operation on R 410A gas complete Air-cooled compresssor with accessories, connection wire, antivibration pad, necessary AHU kit, etc. suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including gas topup and replacing of defective components of the unit etc: as require.
OD18124/2025-2026:OUTDOOR UNITS - Supply Installation Testing and Commissioning of following 7.5HP air-cooled Inverter Type DX Condensing Unit consisting of Hermetically Sealed, High effieincy Inverter Scroll Compressor, Copper refrigerant coil, fan motor assembled in, powder coated metal enclosure with HP/LP safety switch microprocessor-based control unit protection relays contactors etc, suitable for operation on R 410A gas complete Air-cooled compresssor with accessories, connection wire, antivibration pad, necessary AHU kit, etc. suitable for 415+-10% volts, 50 Hz, 3 Phase AC supply. Periodical maintenance and servising shall be done up to the end of 36 months from date of commissioning including gas topup and replacing of defective components of the unit etc: as required.
OD18118/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 12.77 mm.
OD18130/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 15.88 mm.
OD18123/2025-2026:REFRIGERANT PIPE -Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 22.23 mm.
OD18113/2025-2026:REFRIGERANT PIPE - Supply, Installation, Testing and Commissioning of Hard drawn Refrigerant Copper Piping , insulated with 13mm thick nitrile rubber tubing approved make, with necessary proper supports. Size: 28.58 mm.
16.16:Supplying & fixing of powder coated extruded aluminum Return Air Grills with louvers but without volume control dampers complete as required.
OD18131/2025-2026:Supply, Installation, Testing and Balancing of Extruded Aluminum Volume Control Dampers complete with flanges, channels and control levers suitable for duct mounting.
OD18127/2025-2026:DIFFUSERS & DAMPERS - Supply, installation, testing and balancing of Aluminium powder coated Square Diffusers without aluminum volume control damper.
OD18120/2025-2026:DIFFUSERS & DAMPERS - Supply, installation, testing and balancing of Aluminium powder coated Square Diffusers with aluminum volume control damper.
OD18116/2025-2026:Supply, Installation, Testing and commissioning of Electrical control panel for AHU VFD BYPASS control and DX ODU with High/Low Voltage protection, overload protector, single phase preventer and suitable MCCB's etc.
OD192795/2025-2026:SITC of duct mounted finned tubular heater of 6 KW with air flow switch, humidistat, safety thermostat and all other safety accessories, heater shall be placed in the plenum box.
16.12.1.1:Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.63 mm sheet
16.12.1.2:Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.80 mm sheet
16.12.1.3:Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006 Thickness 1.00 mm sheet
OD192453/2025-2026:DUCT INSULATION - Supply and fixing of External Thermal insulation on ducts using 13 mm thick closed cell Nitrile rubber class O insulation with aluminum foil face after applying cold setting adhesive as per recommendation of the manufacturer. --
OD18129/2025-2026:DUCT INSULATION - Supply and fixing of External Acoustic insulation on ducts using 10mm thick open cell Nitrile rubber after applying cold setting adhesive as per recommendation of the manufacturer. --
OD93796/2025-2026:DRAIN PIPING - Supply, installation, testing and commissioning of Drain piping insulated with 9mm thick nitrile rubber insulation of closed cell with protection fibre glass cloth with a layer of protective coating. Size: 32 mm dia. --
OD93797/2025-2026:DRAIN PIPING - Supply, installation, testing and commissioning of Drain piping insulated with 9mm thick nitrile rubber insulation of closed cell with protection fibre glass cloth with a layer of protective coating. Size: 25 mm dia. --
OD18133/2025-2026:Supply, fabrication, installation, testing of flexible connections made out of fire resistant flexible double canvas sleeve. --
OD18119/2025-2026: Supply and Installation of isowall Pannelling(PUF Pannel) for covering indoor unit ductable split AC and return air box with 40 mm thick puff insulation 16kg density expanded polystymer side covered with 6mm thick pre-painted GI sheet with inspection and service opening for cleaning air filter with provision for canvas connection, Supported with GI channel and providing Silicon sealand, Fishers, screws, revet, doom nut etc. complete.
OD18112/2025-2026:Charges for filling sufficient quantity of freon R-410A gas for existing air conditioner unit including leak testing .
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.6.4.54:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run
90.6.5.18:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 1.50 sq mm
90.6.5.19:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 2.50 sq mm
90.6.5.20:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 4.00 sq mm
90.6.5.21:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 6.00 sq mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD18132/2025-2026:Engaging labour for demolition of wall for Providing Ducting and cleaning properly.
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD311269/2025-2026:Supply , Installation, Testing and Commissioning of 2TR,5 star rated Air Cooled Hi Wall Invertor split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), Copper evoporator coil and condensing coil , surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celcius. Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature) with comprehensive maintenance contract up to the end of DLP period including periodical services, gas topping etc. complete.(Including stand)
OD272811/2025-2026:Supply and providing the following size soft drawn copper pipe for connecting Indoor and Out Door unit using rubberized foam sleeve 10 mm thick, brazing, leak testing etc. 9 mm (3/8 inch) , 16 mm (5/8 inch) dia, 22g
OD311260/2025-2026:Supply and installation of automatic stabilizer suitable for 2.0 TR AC unit with working voltage range of 170 V - 270 V AC, current capacity of 15A, indicators, suitable for wall mounting etc. as required. (V-Guard VG 500 or equivalent)
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1410088.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1410088.xls
BOQ • 0.33 MB
SBD.pdf
Tender Documents • 1.64 MB
MOM.pdf
Tender Documents • 0.28 MB
Download all tender documents and submit your bid