| 1 | Supply, installation, testing and commissioning of Servo controlled voltage stabilizer (confirming to BIS 9815 (Part-l) :1994, reaffirmation 2019 latest version). Three phase, four wire (RYBN), 50 Hz, Naturally Oil cooled, indoor, unbalanced type, cooper wound, metallic body duly power coated with lifting Hooks two nos, digital display type, relay free smooth and silent operation with 1st filling of Transformer oil up to level having following specification:-
(a) Capacity - .150... KVA
(b) Type - Suitable for unbalanced load and unbalanced input.
(c) Input voltage 360V-480V, Input frequency 50 Hz
(d) Output voltage - stabilized at any deigned/ desired voltage 415/ +- 1%
(e) Rated frequency - 50 Hz
(f)Wave form distortion - Nil
(g)Response time - not to exceed 20 mili seconds
(h) Sensitivity - (+/) 1%
(j) Rate of correction- Not less than 6 Volt second between phase and neutral
(k) Efficiency - more than 95%
(l) Type of load - three phase, unbalanced type
(m) Metering - Digital display Voltmeter/ Ammeter with multi- functional meter
(n) Operating temperature - For indoor use upto max ambient temp + 55°C
(o) Dimmer rating- as per OEM
(p) Dimension of tanks - As per OEM(width x depth xf height) in inches | 1 | Each | - | - |
| 1.01 | (q) Oil capacity- As per OEM
(r) Class of insulation - Class F
(s) Mode of operation Automatic manual
(t) Winding Temperature rise Max 55°C (10°C above operating temp)
(u) Transformer oil -S 335 marked
(v) Core - CRGO M4 Grade/CRNO (Cold Roll Grain Oriented)/ (Cold Rolled Non- Oriented)
(w) Auto transformer (Variac) -100 percent Copper wound Electrolytic Grade
(x) Losses - As per IS Norms
(y) Power Factor- Not less than 0.95
(z) Protection –
(i) Over load protections
(ii) Short Circuit protections
(iii) High/Low voltage cut off
(iv) By pass arrangement in case of Emergency
(v) Single phase sequence change Iphase fal protection
(vi) Earth fault protection
(aa) Standard Fitting & Accessories e.g Marking plate, lifting lugs, Cl Rollers, Earthing Terminals etc cable box. | - | - | - | - |
| 2 | Supply, installation, testing and commissioning of Servo controlled voltage stabilizer (confirming to BIS 9815 (Part-l) :1994, reaffirmation 2019 latest version). Three phase, four wire (RYBN), 50 Hz, Naturally Oil cooled, indoor, unbalanced type, cooper wound, metallic body duly power coated with lifting Hooks two nos, digital display type, relay free smooth and silent operation with 1st filling of Transformer oil up to level having following specification:-
(a) Capacity - 200 KVA
(b) Type - Suitable for unbalanced load and unbalanced input.
(c) Input voltage 360V-480V, Input frequency 50 Hz
(d) Output voltage - stabilized at any deigned/ desired voltage 415/ +- 1%
(e) Rated frequency - 50 Hz
(f)Wave form distortion - Nil
(g)Response time - not to exceed 20 mili seconds
(h) Sensitivity - (+/) 1%
(j) Rate of correction- Not less than 6 Volt second between phase and neutral
(k) Efficiency - more than 95%
(l) Type of load - three phase, unbalanced type
(m) Metering - Digital display Voltmeter/ Ammeter with multi- functional meter
(n) Operating temperature - For indoor use upto max ambient temp + 55°C
(o) Dimmer rating- as per OEM
(p) Dimension of tanks - As per OEM(width x depth xf height) in inches | 1 | Each | - | - |
| 2.01 | (q) Oil capacity- As per OEM
(r) Class of insulation - Class F
(s) Mode of operation Automatic manual
(t) Winding Temperature rise Max 55°C (10°C above operating temp)
(u) Transformer oil -S 335 marked
(v) Core - CRGO M4 Grade/CRNO (Cold Roll Grain Oriented)/ (Cold Rolled Non- Oriented)
(w) Auto transformer (Variac) -100 percent Copper wound Electrolytic Grade
(x) Losses - As per IS Norms
(y) Power Factor- Not less than 0.95
(z) Protection –
(i) Over load protections
(ii) Short Circuit protections
(iii) High/Low voltage cut off
(iv) By pass arrangement in case of Emergency
(v) Single phase sequence change Iphase fal protection
(vi) Earth fault protection
(aa) Standard Fitting & Accessories e.g Marking plate, lifting lugs, Cl Rollers, Earthing Terminals etc cable box. | - | - | - | - |
| 3 | Material and labour for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.50 Mtr below ground level. The earth plate to be connetced with GI earthing strip of size 32mmx6mm thick by means of brazing between GI strip and earth plate min 45 cm in vertical length and GI strip also to be joined by brazing only. The GI earthing strip to be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness ) , 3rd layer with tibba sand up to the ground level. Earthing shall also be include for providing concrete earth pit in PCC (1:2:4) type B-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work and testing, complete all as specified and directed.
Note :- GI Strip upto 7.5 metre is deemed to be included in quoted rate of this item. | 4 | Each | - | - |
| 4 | Supply and Laying XLPE Cable 120 Sqmm 3.5 core in trenches/fixed on walls/poles of passing through pipe, PVC insulated armoured heavy duty LT U/G electric cable with aluminium conductor 1100 volts grade with suitable cable glands and lugs etc, complete all as specified and directed. | 10 | RM | - | - |
| 5 | All as per item No 4 above but size 95 Sqmm 3.5 core. | 10 | RM | - | - |
| 6 | Excavation in trenches not exc 1.5m wide and not exc 1.5m depth for laying of cables etc getting out including forming bottom surface to required level and gradient in soft / loose soil, complete all as specified and directed. | 5.4 | Cum | 100 | ₹540 |
| 7 | M&L removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point, complete all as specified and directed. | 1.9 | Cum | - | - |
| 8 | Returning filling in, and including spreading and leveling in layers not exceeding 25 cm thick, complete all as specified and directed. | 3.5 | Cum | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
TD.pdf
Tender Documents • 1.13 MB
BOQ_884620.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .