Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹3.0 CrAccepted-AOC | ₹3.0 Cr Quoted ₹3.1 Cr | L-1 | Accepted-AOC Being Lowest Bidder |
| 2 | L-2₹3.2 Cr+₹15.3 L (4.99%)Rejected-AOC | ₹3.2 Cr+₹15.3 L (4.99%) | L-2 | Rejected-AOC Being not Lowest Bidder |
| 3 | L-3₹3.2 Cr+₹17.7 L (5.75%)Rejected-AOC | ₹3.2 Cr+₹17.7 L (5.75%) | L-3 | Rejected-AOC Being not Lowest Bidder |
| 4 | L-4₹3.3 Cr+₹19.3 L (6.28%)Rejected-AOC ATHWAJAN SRINAGAR 191101 J K | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 191101 | ₹3.3 Cr+₹19.3 L (6.28%) | L-4 | Rejected-AOC Being not Lowest Bidder |
| 5 | L-5₹3.5 Cr+₹40.1 L (13.1%)Rejected-AOC | ₹3.5 Cr+₹40.1 L (13.1%) | L-5 | Rejected-AOC Being not Lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹3.5 L
Closing Date
23 Jan 2021, 6:00 pmClosed
CE 31 Zone
HQ Chief Engineer 31 Zone C/o 56 APO
PROVN OF SIGNAL CENTRE FOR CERTAIN UNITS AT BARAMULLA
2020_MES_359477_4
PROVN OF SIGNAL CENTRE FOR CERT UNTS AT BARAMULLA
Open Tender
Civil Works
Lump-sum
900 days
Baramulla Garrison
As per NIT
10 documents required · 10 mandatory
₹2,000
GE 969 EWS
₹3.5 L
Yes
30 Jan 2021
2 Jan 2021
25 Jan 2021
2 Jan 2021
23 Jan 2021
6 Jan 2021
2 Jan 2021 - 9 Jan 2021
Amount
Note: (i) Please refer Schedule 'A' Notes given on serial page No. 23 to 30 of tender documents. (ii) Item from Srl No. 3 to 9 of this document shall be Part-XIII (Miscellaneous Items of Works) of BOQ (iii) Unless otherwise specified, earth work and excavation shall be measured and paid separately for Sch 'A' Part III to X and XIII of BOQ (iv) This schedule 'A' Part-XIII (Miscellaneous items of Works) is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS
Lump sum price worked out by the contractor for BUILDING WORKS as listed in Schedule 'A' Part-I brought forward from serial page No.31
Lump sum price worked out by the contractor for INTERNAL ELECTRIC SUPPLY WORKS as listed in Schedule 'A' Part-II brought forward from serial page No.32
Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-III brought forward from serial page No.34
Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS listed in Schedule 'A' Part-IV brought forward from serial page No.36
Lump sum price worked out by the contractor for ROAD, PATH, CULVERT AND HARD STANDING WORKS as listed in Schedule 'A' Part-V brought forward from serial page No.38
Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule 'A' Part-VI brought forward from serial page No. 39
Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS as listed in Schedule 'A' Part-VII brought forward from serial page No.41
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-VIII brought forward from serial page No.42
Lump sum price worked out by the contractor for SITE CLEARANCE & EARTHWORKS as listed in Schedule 'A' Part-IX brought forward from serial page No.44
Lump sum price worked out by the contractor for LIGHTENING PROTECTION WORKS as listed in Schedule 'A' Part-X brought forward from serial page No.45
Lump sum price worked out by the contractor for DEMOLITION/DISMANTLING WORKS as listed in Schedule 'A' Part-XI brought forward from serial page No.46
SCHEDULE A PART XIII ( MISC ITEMS OF WORKS) INTERNAL ELECTRIFICATION WORKS
Supply and fixing Lamp holder bracket type with LED lamp 7 watt suitable for B-22 type holder, PVC/Polycarbonate type with skirt cap suitable for batten fitting, complete all as specified and directed.
Supply and fixing ceiling fan AC single phase 230/240V 50 Hz of size 1400 mm sweep 290 RPM energy efficient 5 star rated and complete with connecting up ceiling rose to connector block of fan including making of holes and grouting of nuts and bolts complete all as specified and directed. Make :- Havells Model - Velocity or equivalent in Crompton Greaves/Bajaj.
Supply and fixing PVC ventilation fan AC single phase 230V/240V 50Hz of 200 mm sweep,1350 rpm with louvers, shutter and connecting up to celling rose complete all as specified and directed. Make :- Havells Model VENTILAIR DX or equivalent in Crompton Greaves/Usha.
Supply and fixing sheet metal enclosure SPN factory made, double door for DBs 230 Volts single pole and neutral 12 way complete all as specified and directed. Make :- Havells Cat part No. DHDPSHODRW12 or equivalent in Legrand/L&T.
Supply and fixing MCB SPN 240 Volt, 50Hz , 10 KA, 'C' series of rating 63 Amp complete all as specified. Make :- Havells Cat Part No. DHMGCSNF063 or equivalent in Legrand/L&T.
Supply and fixing MCB SP 240 Volt, 50Hz , 10 KA, 'C' series of rating 10 Amp complete all as specified. Make :- Havells Cat Part No. DHMGCSPF006-032 or equivalent in Legrand/L&T.
Supply and fixing MCB SP 240 Volt, 50Hz , 10 KA, 'C' series of rating 06 Amp complete all as specified. Make :- Havells Cat Part No. DHMGCSPF006-032 or equivalent in Legrand/L&T.
Supply and fixing LED fitting 4' long decorative slim round profile LED light fitting fixture with extruded polycrbonate enviromental friendly energy efficient Elite LED pride plus complete all as specified. Make :- Havells Cat part No. LHESEXB7PN1W018 or equivalent in Crompton Greaves/Philips.
Supply and fixing 24W LED Street light fitting for area illumination energy saving environment friendly long life LED street light fitting made up of pressure die cast aluminium housing with high power LED as lighting source and lence embedded PVC cover having top opening separate driver compartment with IP 65 protection and impact resistance of IK07 complete all as specified and testing on completion and including GI wall mounting bracket 40 mm dia 1.2 Mtr long including 120 degree bend with 02 Nos FI clamps 25 x 3mm size with necessary nut bolts etc complete all as specified. Make :- Havells Cat part No. LHETBXU7PA6S024 or equivalent in or equivalent in Crompton Greaves/Philips.
Supply and fixing LED fitting 9 watt decorative slim round profile LED light fitting fixture with extruded polycarbonate environmental friendly Energy efficient complete is all specified. Make :- Havells model Elite LED pride plus Cat part No. LHExBL71W009 or equivalent in Crompton Greaves/Philips.
Supply and fixing LED recessed mounted luminaire 18 watt ultra slim modem designed VENUS NEO HE 2 x 2 which provided soft lit and glare free symmterical illumination all as specified and directed. Make :- Havells Cat Part No. VENUSNEOHE 2x2PLR 18-42 WLED830MOD or equivalent in Crompton Greaves/Philips.
Supply and fixing TPN vertical load line DB fitted with Bus bar, neutral link, blanking plate including 100 Amp MCCB double door suitable for TP/FP G Frame MCCB all as specified and directed. Make :- Havells Cat Part No. DHDLVSWGOF004, 4 way, DBLL 4 Way SD VERT of equivalent in Legrand/L&T.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x6 mm thick burried directly in gound (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanised iron earth lead 4mm dia by means of bolt, nuts check nuts and washers of galvanised iron and 4 mm dia GI earth wire protected by provn of GI medium grade pipe 15mm bore upto 7.5mtr including provision of concrete pit in PCC (1:2:4) type B-1 ( using 20 mm graded crushed stone aggregate) with 40mm thick cover of RCC (1:2:4) reinforced with XPM (Weight not less than 4kg/Sqm) and frame of angle iron 25x 25x3mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 of SSR -2010 Part -I and connecting to earth test point all as specified or indicated including testing on completion, complete all as specified and directed. Note : The quoted rate of earthing shall be deemed to include cost of 7.5 m long galvanised wire 4 mm dia and protection pipe 15 mm bore medium grade GI light grade 20 mm bore watering pipe. Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted rates.
SEWAGE DISPOSAL WORKS
S&F for united polyethylene septic tanks type-4, 3400 litres, 25-30 users made of polyethylene in a single moulding. The unique size and 3 chamber design of United polyethelene septic tanks play a very important role in processing waste. There are manholes provided for convenience. The high wall thickness withstands load and pressure of the earth to a great extent. Being light in weight, it is easy to transport and install. These septic tanks are made in salt resistant, nondegradable plastic, hence they are more suitable in saline areas. All that has to be done for fitting the tank is to fill the tank with water, connect the drain line to the inlet and outlet to the soak pit. Cover the manholes with the lids provided and the tank is ready to use including PCC 1:4:8 type D-2 ( using 40mm graded crushed stone aggregates) below foundation, and vent shaft connection etc. complete all as including necessary earth work and excavation in any type of soil complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY WORKS
M & L for sand cushioning with a layer of fine sand 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. Note: (i) Measurement shall be taken only after punning down sand cushioning.
Supply, installation, testing and commissioning indoor type, step down transformer, 11 KV/415 volts (at full load) AC 3 phase 50 HZ, 160 KVA capacity, core type, double copper wound , Oil immersed, naturally cooled, oil Natural Air Natural (ON AN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having tapping at ±2.5% & ±5% on HV side to be charged by means of hands operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temperature of 40 degree celsius. The transformer shall be IS:1180 BEE star rated capacity and shall comprises of the following:- (a) Three number porcelain bushing suitable for 11 KV on HV side ( Primary side ) , complete with copper rods nuts and washers. (b) One cable box on LT side (Secondary side) consisting of four number porcelain bushing with copper rods, complete with nuts and washers with cable glands suitable for reception/ taking out 3.5 core 120 LT 1100 Volts grade, PVC/ XLPE insulated and PVC sheathed heavy duty armoured cable including jointing material complete. (c) De-hydration breather with first filling of dehydrating agent (silica gel) Make :- BHEL/Schneider/ABB
(d) Explosive vent, Thermometer pocket on tank cover, oil level gauge, Oil drain filter valve, lifting lugs, oil filling hole with cap/ plug with connection plate complete, air release valve plug and four Nos plain solid cast steel detachable rollers. (e) One No 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (f) Two earthing terminals on tank cover to facilitate fixing of 50 X 6 mm galvanised iron earth strip for earthing of body. '(g) Rating plate and terminal marking plate (j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral. (k) First fill of new and unused transformer oil, IS-335 filtered and testing upto 40 KV dielectric strength at 2.5 mm air gap between testing electrodes. (l) Providing adequate size and number of channel embedded in floor, for movement of transformer. (m) Lifting lugs-02 Nos (n) Oil filling hole with cover. (o) Roller-04 Nos. Note :- The transformer shall be minimum two star rated as per GRIHA requirements.
Steel tubular swaged poles complete with MS base plate continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 55 (11 metres long) including two coats of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface after errection in position including preparation of surface, complete all as specified and directed. (Note:- Necessary earth work, PCC coping will be measured and paid for separately under respective item.)
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connecting to galvanized iron strip of size 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of brass after welding of copper strip to earth electrode to the full length of earth plate, GI light grade pipe 40 protection pipe upto test point, 20 mm dia GI watering mm watering pipe with funnel plate and wire mesh, PCC pit using cement concrete1:2:4, type B-1 with pit cover of size 30 x 30 cm made of RCC 1:2:4, B-1 (using 20 mm graded crushed stone aggregate) with suitable handle, angle iron frame made of angle iron of size 40 x 40 x 4 mm, adequate quantity of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling all as required at site including test point made out of steel plate of size 75 x 75 x 6 mm fixed to wall all as specified in plate No 3 of SSR part-I and directed by Engineer-in-charge. Note:- Earthing required for External Electrification, Air Conditioning and Lightening Protection shall be measured under this item.
Supply and fixing cable jointing cable end gland for 1.1 KV grade cable with Jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, alumunium conductor cable of size 120 to 185 sqmm,Indoor/Outdoor type, complete all as specified.
Supply, installation , testing and commissioning of cubical housing cabinet type LT feeder piller box out door type, plinth mounted, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA sheet overall size to accomodate the following accesories and built from suitable size angle iron frame work, having front and rear hinged doors, lifting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts, spring and washers and applying spray paint with powder coated painting. The panel should be suitable for 415 volts, 50 HZ, 3 phase 4 wire system and shall be complete with solid aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate the following MCCBs, including necessary foundation work complete all as specified and as directed. (a) MCCB 4 pole 400 amps 36 KA (Incoming) - 01 No (b) MCCB 3 pole,125 Amps 25 KA (outgoing) - 02 Nos (c) MCCB 3 pole, 100 Amps 16 KA (outgoing) - 02 Nos (d) MCCB 3 pole, 63 Amps 16 KA (outgoing) - 02 Nos (e) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 315 Amps. - 01 No
Supply, installation, commissioning and testing Servo Control voltage Stabilizer fully automatic micro processor based control card of capacity 160 KVA, three phase oil cooled with Single phase prevention system, indoor type and designed for input variation between 300 V to 480 V with output voltage stabilized at 415 volt with accuracy of + 2.5% and speed of correction 8 Volts per Sec per phase with out under/over shooting, no load loss less than 0.5%, operating temp (-) 15C to 45C above ambient and unbalanced load complete with first filling of oil complete, all as specified and as directed.
M & L chemical earthing system complete with copper earth plate 90cm x 60cm x 5mm & copper earth strip 32 x 6mm vertically to a depth not less than 3.50 Mtr deep below ground level with top edge of earth electrode at a depth not less than 500 mm below normal ground level and further connected to test point terminal block of size 120mmX120mmX25mm made of copper as directed, including 30 Kg (Minimum for each earth pit) NABL Lab Certified back fill chemical compound for filling bore holes with soil mixed, so as to achieve earth resistance below 1 Ohms. Excavation of PCC chamber in PCC (1:3:6) type C-1 complete with Pit cover of 300mm x 300mm made of cast Iron complete all as specified and directed.
M&L for Construction of Transformer shed complete all as specified and shown on drawings. ( refer Drg No CESZ/TD-1110/2011 Sheet 1/2 to 2/2) .
DG SET WORKS
Supply, installation, testing & commissioning of Silent Diesel Generating Set (CPCB NORMS COMPLIANCE) 160 KVA comprising Engine and Alternator mounted and aligned on a common base frame complete with all standard accessories like Fuel tank, Manual Electric Panel AVM Pads fitted on Base Frame, 12/24 Volts DC Battery, Leads & Sound Proof Acoustic Enclosure. 160 KVA DG Set .Manual control panel 3 Phase (Liquid - Cooled) with Engine G2 platform with floor mounted 4 stroke, 06 cylinder having fuel tank capacity of 360 litres, water cooled with centrifugal water pump, gear driven type all as directed by Engr -in -Charge. Make: As per Appendix 'E'
(A) ENGINE- ECO friendly for emisson and noise (CPCB NORM COMPLIANCE) 4 stroke diesel Engine confirming to BS standard developing 175 BHP @ 1500 RPM turbocharged air cooled/water cooled complete with a provision for 10% overload for one hour on 160 KVA and foundation etc.up to 160 KVA . (i) Fly wheel with starter ring for generating set. (ii) Dry type Air filter. (iii) Lub oil cooler assembly with accessories. (iv) Exhaust air manifold. (v) Exhaust silencer. (vi) Expansion bellow. (vii) Exhaust gas turbocharger. (viii) Fuel filter (pre micro).
( ix) Lubrication oil filter. (x) 12V electrical starting system with starting motor & battery charging alternator with self starter and other auto electric accessories as recommended by manufacturer. (xi) Centrifugal by-pass filter. (xii) In- line Monoblock fuel pump with mechanical governer and fuel pump. (xiii) Front & rear engine mounting supports. (xiv) Engine control panel consisting of OFF/ON/START keys lub oil pressure gauge, Ammeter, electronic Hour meter, speedometer. (xv) Safety against low lub oil pressure. (xvi) Engine operation/Maintenance, spare parts Manual. (xvii) Engine test certificate. (xviii) Cold starting Kit.
(B) ALTERNATOR- Sailent pole brushless type suitable for direct couple to engine self excited, self regulated with fast response thyristor type electronic automatic voltage withhold out put voltage with in desired limit(+1%) Dynamically balanced 400/415 volts AC 3 phase 50 HZ, 4 wire 0.8 PF lagging 160 KVA 1500 RPM star connected (4 wire) screen protected drip proof enclousers liquid coolant cooled with radial fan mounted on rotor with insullation class- F/H and with stand an over load of 10% for one hour in every 12 hours operation ambient temperature condition as per BS 2613 IS 4722 with following accessories (Must have flexible disc closed coupled having serving +/- 1% no load to full load with selh excited single bearing.) :- (i) One MS frame suitable for mounting of Engine & alternator. (ii) One fuel tank of suitable capacity for 6-8 hrs continuous running complete with fuel gauge inlet/outlet connections drain valve with plug etc. (iii) Battery of 180 AH capacity with copper leads and terminals of suitable size.(01 No battery will be as per 12 volts starting system)
(C) AMF CONTROL PANEL -The panel shall be made out of fabricated sheet steel suitable for indoor floor mounting installation hinged from panel door for easy accessibility and suitable rated bus bar internal wiring fuses with suitable provision for connection incoming/out going leads. It will include for following accessories. (i) Alternator and mains connector, 3 pole suitable size with overload relay for protection. (ii) Digital multifunctional programmable up to 200 Amps 500 Volts, three phase 4 wire LT net work to read power factor, frequency, Amps, and voltage - 01 No (iii) One set of mains supply voltage monitor to identify low voltage/complete failure and initiate necessory signal for. (iv) Push botton for start/stop/reset, acknowledge. (v) Master switch for auto/manual/test/off.
(vi) One set of lamp indicator. (vii) All control fuses will be so located as to be easily accessible for replacement. (viii) Relay section will comprise set of relays for following:- (a) Automatic starting of DG set in case of low voltage mains as pre-adjusted. '(b) Automatic transfer on mains dully monitored quality of supply for preset time period and shut down the DG set after present ideal running time. (c) In the event of faliure disel Engine to start on faliure of mains supply on one attempt to more starting impulse will be automatically given and of still the Engine does not start due to same defect with in 30 second of first starting impulse it will be disconnected and locked, automatically given audio and visual signals. (d) Automatically mains supply restoration without time delay in case of faliure of DG set due to faulty starting. (e) The circuit will make use of minimum number of relays and control wiring will be neatly provided with adequate size of copper conductor cable of suitable size and end tag numbered at either ends.
(D) Acoustic Enclosure- Supply & installation of Acoustic Enclosure suitable for 160 KVA DG set as under. (i) Fabricated out of CRCA sheet of suitable thickness as per manufacturer's design. Polyester based powder coated internally and externally with lockable type door handle. All nuts and handles shall be zinc coated. (ii) The doors are gasketed with EPDM gaskets. (iii) Sound proofing with high quality rock wool/mineral wool confirming to IS 8183 of 50mm thickness and density at 96 Kg /M3 coverd with fiber glass cloth and perforated powder coated sheet specially designed allenuators (Sound controller) at air entry and exit of the container noise level shall not to exceed 75 Db at 1 metre distance as per CPCB norms. (iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower. (v) Emergency stop push button out side the container. (vi) Provn of light inside the canopy providing of FTL fitting 1x20 watt with wiring and control switch.
EXTERNAL WATER SUPPLY WORKS
Cutting existing CI pipe of 200mm size and reducing to required length before laying in position for insertion of new tees, branches etc. complete all as directed.
MISC ELECTRICAL ITEMS OF WORKS
Intelligent Microprocessor based networkable Addressable type 99 Control Panel with capable of handling minimum 85 detectors per panel, located Reception / Control room. Panel should have alarm facilities, hooter, fire / fault indicators, audio signals also capable of giving visual signal (Optional) inbuilt rechargeable battery with battery charger, network integrator module, power supply, inbuilt clock for time monitoring, MCP actuated alarms and also for detector actuated alarms, etc., complete in all respects as per detailed specifications. Model No. QTN1-WP of Make:- QUTAK or equivalent in any other MES approved make
Intelligent Microprocessor based networkable Addressable type 999 Control Panel with capable of handling minimum 800 detectors per panel, located Reception / Control room. Panel should have alarm facilities, hooter, fire / fault indicators, audio signals also capable of giving visual signal (Optional) inbuilt rechargeable battery with battery charger, network integrator module, power supply, inbuilt clock for time monitoring, MCP actuated alarms and also for detector actuated alarms, etc., complete in all respects as per detailed specifications. Model No. QTN101-WP of Make:- QUTAK or equivalent in any other MES approved make
Wireless Intelligent Addressable Photoelectric Smoke Detector capable of emitting radio waves, also have addressable sensitivity & its testing button to test the complete system without generating any smoke all as specified. Model No. QT222WSD Make:- QUTAK or equivalent in any other MES approved make
Wireless Intelligent Addressable remote key fob with easy system testing features with fire / fault and inbuilt resettable button all as specified . Model No. QT03TF of Make:- QUTAK or equivalent in any other MES approved make
Supply and fixing Manual Call point box for remote key fob in ABS housing, complete all as specified.
Wireless Intelligent Addressable speaker cum hooter with emitter also with inbuilt charger, device should capable to read the zones of different detectors independently and able to transmit the signal to the panel complete all as specified and directed. Model No. QT 10TX Make:-QUTAK or equivalent in any other MES approved make
Material and labour for GI bracket type cable tray of size 300mm X 50 mm for fixing of cables of any type complete all as specified and directed. (Note:- Quoted rates inclusive of following items:- (i) Equal angle type supporting for cable tray in 2 Metre internal (ii) Fixing of Equal angles on walls/roof/floor (iii) Requirement nut & bolts alongwith washers for fixing of cable trays in series & as site position. (iv) Painting of cable tray with one coat of red-oxide and two coats of synthetic enamel paint complete all as specified and directed.
AIR CONDITIONING WORKS
Supply and installation of air cooled packaged AC indoor unit complete suitable to operate 3 Phase 415 V ± 10%, 50HƵ, using CFC free R-410A refrigrant along with provision of drain pipe of capacity 32mm. Complete unit must have COP not less than 4.0, capacity 11 TR having two compressors of size 5.5 TR each scroll compressor, with microprocessor controlled unit and starter, splash lubrication based evaporator unit with fan blower units of capacity not less than 4400 cfm complete of technically adequate capacity/size for proper efficiency for circulation and with outdoor unit air cooled condenser having 02 number propeller type fan of single phase, aluminium finned with copper tube condenser all as specified and directed. Makes :- Carrier/Daikin/Hitachi.
Installation of hard copper piping of 1/8" suction copper tubing and 5/8" delivery copper tubing required for item No.9.01 complete with necessary fittings and including insulation with nitrile rubber tubes complete all as specified and directed. Make :- Total Line/Mandev/Rajkot
Supply & Installation of GSS ducting work of 24 SWG complete with MS angle support, GI threaded hanger, Fastners, Rubber Gaskets, GI vanes complete as per standard norms complete all as specified and directed.
Supply & Installation of GSS ducting work of 22 SWG complete with MS angle support, GI threaded hanger, Fastners, Rubber Gaskets, GI vanes complete as per standard norms complete all as specified and directed.
Supply & Installation of GSS ducting work of 20 SWG complete with MS angle support, GI threaded hanger, Fastners, Rubber Gaskets, GI vanes complete as per standard norms complete all as specified and directed.
Supplying and fixing of duct insulation with closed cell 'O' class nitrile rubber density 25-32 Kg/m ³ . Applied by Adhesive, conforming to standard specification.13 mm thick closed cell nitrile rubber (indoor application).
Supplying and fixing of acoustic lining of duct with Open Cell Nitrile Rubber density 140-180 Kg/m³ . Applied by Adhesive, conforming to standard specification 9 mm thick open cell nitrile rubber complete all as specified and directed.
Supply, fabrication and erection of mild steel stand for installation of outdoor unit at suitable height and position as per site requirement including necessary welding, nuts, bolts, washers, grouting and fixing all specified items as per technical specifications and as ditrected by Engineer-in-Charge alongwith necessary civil works for provision of technically specified platform as per manufacturer's instructions.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications complete all as specified and directed.
Supplying & fixing of powder coated extruded aluminium Return Air Grills without volume control dampers complete all as specified and directed.
Supplying & fixing of fusible plug type fire damper in Supply air duct in AHU room complete all as specified and directed.
Supplying & fixing of Low leakage VCD for Indoor Package units and for return air opening in AHU room wall complete all as specified and directed.
Supply and installation of strip heaters of capacity 3 KW x 3 Nos complete with necessary controls viz heating thermostat, geyser stat, interconnected wiring etc complete all as specified and directed.
Supply, installation, testing and commissioning of LT panel board for AC plant (indoor type) cubical type made out of CRCA sheet 2 mm thick dust and vermin proof and angle iron of size 50 x 50 x 6 mm thick pedestal frame grouted in PCC (1:2:4). Panel should be covered from all the sides with front and back lockable doors complete with Copper Bus bar, Main Incomer SFU / MCCB and outgoing suitable for MCCB /SFU for 3 Nos Indoor units of capacity 11 TR each complete all as specified and directed.
Supply & fixing of size of 1.1 kV grade multicore copper conductor PVC sheathed armoured XLPE cable as per IS : 7098 of size 4 Core 10 Sqmm ( For Indoor Units) complete all as specified and directed.
Supply & fixing of size of 1.1 kV grade multicore copper conductor PVC sheathed armoured XLPE cable as per IS 7098. of size 3 Core 2.5 Sqmm (Control cable for Outdoor Units) complete all as specified and directed.
Supply & installation of following sizes of perforated MS cable trays including horizontal & vertical bends, reducers, tees, cross members and other accessories as required and duly supported from the ceiling/wall/floor with MS suspenders/supports and including painting etc. as required complete all as specified and directed.
Providing and fixing earth wire 6 SWG GI wire complete all as specified and directed.
Pressure testing, vaccumizing, refrigerant 407C charging and commissioning of entire system complete all as specified and directed.
M/s Muzaffar Ahmad Mir
M/S VALLEY ENTERPRISES CONSTRUCTION CO
ASM BUILDERS
M/s Mohammad Shafi Malik
M/s Hafizullah Beigh
MANZOOR AHMAD WANI
ZAHOOR ENGINEERING WORKS
M/S Himalayan Construction and Co.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .