Loading…
Loading…
Tender Value
₹12.6 L
EMD Value
₹12,600
Closing Date
5 Feb 2026, 6:00 pmClosed
Similar tender results from the same govt authority in the past 3 years.
Chief Officer, VAGHODIYA NAGARPALIKA
Providing, Supplying & Erecting Street Light Pole with LED Lights From Tavara Main Road To Taluka Seva Sadan at Vaghodiya. ( Second Attempt)
265406
1 of 2025-26
Open
Civil - All
Vadodara
1 document required · 1 mandatory
₹1,062
CHIEF OFFICER, VAGHODIYA NAGARPALIKA, VAGHODIYA
₹12,600
16 Jan 2026
16 Jan 2026
16 Jan 2026
5 Feb 2026
16 Jan 2026
Name Of Work :- Providing, Supplying & Erecting Street Light Pole with LED Lights From Tavara Main Road To Taluka
Seva Sadan at Vaghodiya.
No Description Quantity Total Rate Per Amount
1 Supplying & erecting Steel tubular pole (Swaged) confirming
to IS - 2713 (Part-II) 1980. Manufacturing process of steel
tubular pole should be as per IS specification. Basic steel tube
should be ISI Marked. Pole should be painted by one coat of
Zinc comet Primer and two coat of Aluminium /approved
paint to be erected on / in existing Foundation. The length of
poles are as below.
(B) 8.5 mtr. Long Swaged Steel tubular pole
(i) Pole as per IS code 410-SP-16 with 300 X 300 X 4 mm base
plate with necessary G.I. J Bolts (Approximate weight 75 Kg)
For burial erection 30.00 8148.68 NO.
(ii) Add Extra for M.S. Base plate 300 X 300 X 16 mm for pole,
mounting on surface of foundation on GI foundation bolt.
with required stiffeners. 30.00 982.73 NO.
(iii) Add Extra for PU base primer and PU Paint on pole. 30.00 443.39 NO.
2 Supplying and erecting street light pole bracket comprising
main B Class GI pipe of 4.2 cm/require outside dia. complete
with suitable B Class GI sleeve tubing of approx. 45cms.length
and suitable for 76.5mm/80mm or require size pole top
having sufficient fastners for fixing the brackets and having
suitable rise as per site condition as directed and spread of
mtr.with suitable welded stiffener reducer and with lock nut
complete painted with one coat of Red oxide / PU base
primer and two coats of Aluminium / PU paint. Suitable for
side entry fitting brackets of following nos of arms.
[a] Single Arm bracket 2 Mtr 30.00 795.88 NO.
Supplying & erecting approved make SMC press moulded
composite FRP. loop-in, loop-out approx. 2mm thick box
complete with Bakelite connector strip 5way(3P+N+E),DIN rail
for mounting mob & hinged doors as per requirement having
locking arrangements with mounting clamp with nuts, bolts &
washers suitable for erection on pole with cable clamps&
earth bolt of following size of box.
(B) 250mm x 200mm x 100mm [deep] 30.00 515.10 Nos.
4 Supplying and erecting LED street light / Flood light fittings
with High power White LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more than 130 lm/w
and corrosion free High pressure die cast aluminum housing
with smooth finish powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate optics/ lenses,
with toughened glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more than 0.95, THD <
10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire
efficacy> 100 lumens/watt . LED driver efficiency > 85 %.(
fittings required LM-79 & LM-80 certificates)(NOTE: Below
description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage
capacity between the ranges shown.)
(A) Street Light (IP-65), Surge protection -4KV integral and
,Light must have 440VAC line supply with over-voltage
(iii) above 60 to 90 Watts Cat III 30.00 5976.17 NO.
5 Supplying and erecting Flexible PVC insulated multistrand
multicore 1.1 kv grade ISI marked copper wires of following
size to be erected as directed.
e) 1.50 Sq.mm 3 core round PVC sheathed 660.00 31.31 Rmt.
6 Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV. to be laid on
wall with necessary clamps or in existing trench / pipe of
following size of cables
(A) 4 core 16 Sq. mm 1380.00 153.52 Rmt.
7 Supplying and erecting B class Galvanized iron pipe having
smooth finished bore of the pipe on both ends erected nuts
and bolts along the pole / wall shaping the pipe as per site
requirement. Pipe dia as following.
8 Providing and erecting Pipe type earthing having
cms.long and 2.5 cms. dia. galvanised iron pipe with coupling
and buch buried in specially prepared earth pit complete with
necessary 8 SWG earth wire. 30.00 368.65 Nos.
9 For using salt and charcoal / coke as required for pipe type
earthing. 30.00 171.70 Nos.
10 Supplying & erecting earth pit of minimum bore dia.150mm
size approved make Earthing Electrode consisting Pipe-in-
Pipe Technology as per IS 3043-1987 made of corrosion free
hot dipped G.I.Pipes having Outer pipe dia of 50mm having
80-200 Micron galvanising, Inner pipe dia of 25 mm having
200-250 Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded by highly
conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy
duty cover. (A)(approved make OEM has to submit test
certificate including value of earth resistance of installation
duly stamped and signed by agency and officer Incharge has
to ensure the value of earthing resistane mentioned in test
Certificate) & having back filling compound of (B) Inner
chemical (CCM Compound)- Resistivity:- 0.2 ohm / meter
testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no
load & dry form, Sulphar content:- <2%(C) Back fill Compound
:- Earthing compound should be capable to retain moisture
for long time Necessary test report must be submitted by
(a) For Electrical Installation up to 440V in normal soil Length
of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg. 2.00 4591.46 Nos.
11 Making trench in Hard Murrum / Tar Road of suitable width
of 90 cms or required depth for laying any size of cable or
locating the fault all over the run and back filling the same
and making the surface as normal ground.
12 Making trench in Hard Murrum / Tar Road of suitable width
of 90 cm or required depth for laying any size of cable or
locating the fault all over the run and back filling the same
and making the surface as normal ground. (B) If additional
machinery like hammer driller or JCB use [Add]
13 Providing & laying approved make Double walled corrugated
pipes (DWC) of polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same material at
required depth for laying of cable. below ground / road
surface for enclosing cable and back filling the same to make
ground as per original.
14 Providing and fixing Terminal board of size 5.0 x 127 x
mm.bakelite sheet with suitable brass studs with nuts,
washers and clamps of size 25mm x 3mm suitable for pole
painted with one coat of red lead paint. 30.00 146.45 Nos.
15 Providing 1:2:4 cement concrete foundation & 70 % PCC from
bottom including excavation for the pole of size 60 x 60 x
cm. Deep in below ground level with plinth of 45 cm x
cm(or 45 cm dia x 45 cm) high upper ground level with
necessary curing and finishing in approved manner. ( for
16 Providing and, fixing heavy duty flange type brass cable gland
with rubber ring for PVC insulated armoured cable complete
with out going tails, insulating tape etc for following size of
(B) 2 to 4 core 6 Sq. mm 120.00 38.38 Nos.
(D) 2 to 4 core 16 Sq. mm 60.00 47.47 Nos.
Solderless crimping type Aluminium lugs conforming to IS
suitable for cable of following size evenly crimped with high
pressure tool & connected to switchgear terminals with
brass/cadmium plated nut bolts in an approved manner.
Supplying & erecting IP 55 grade following size section pillar
fabricated from joint less M.S. Sheet with angle iron legs
made from jointless M.S. Angle with cable clamps to be
buried in ground to have appropriate erection to work
uniform until erected with cement concrete foundation and
45 cm high bricks work finishing with plaster etc. hinged
double door internally supported on both side, with internal
and outside looking arrangement with look and keys in
duplicate 35 x 35 x 5 mm M.S. Angle of Two Nos. one is
welded and other with nut and bolt for erecting Bakelite
sheet. Painting the Section Pillar inside and out side with
three tank powder coated paint. section pillar roof should be
without joint with water leakage proof & tested as per IP
test & followed by IS 2147 of 1962 1.00 1884.66 Nos.
(C) 60 X 30 X 45 cm section pillar fabricated from 16 Gauge
MS Sheet with angle iron legs 45 cm long made from 35 X
X 5 mm thick MS angle.
19 Supplying and erecting HYLAM sheet on existing angle iron
frame.for following thickness (F) 12mm 1.00 2311.89 Smt.
20 Supplying & erecting approved make Digital time switch
having lithium cell 6 years operative and operate battery
backup 1 channel day clock with 14 memory programme,
suitable to operate on 240V + 5%, 16A with, floating contacts
Minimum switching setup time 1 minimum & LCD display.
Also comprised permanent ON/OFF switching. Programming
switches & housed in fire proof thermoplastic enclosure &
transparent cover erected as required with necessary
connection erected as directed. 1.00 3168.37 Nos.
21 Supplying and erecting Ammeter / Voltmeter selector switch
for 3 phase AC Supply 500 V on existing panel board with
necessary connections. 1.00 317.14 Nos.
22 Supplying and erecting approved make panel mounting type
Digital Ammeter having 3 digits LED display, external CT
operated, calibrated for 0 to 1000 Amps suitable to operate
on 500 Volt AC , erected on existing panel board with all
connection, wiring etc .with manufacturers calibration
certificate. 1.00 1558.43 Nos.
23 Supplying and erecting approved make panel mounting type
Digital Voltmeter having 3 digits LED display, 0 to 750 AC
Volts range erected on existing panel board with all
connection, wiring etc .with manufacturers calibration
certificate. 1.00 1275.63 Nos.
24 Supplying and erecting approved make suitable panel
indicator LED type lamp, lens cover, complete erected with
necessary connections. 1.00 43.43 Nos.
25 Providing & erecting L.T. Current Transformer with bar
primary 50/5 to 1000/5 ratio 15 VA burden erected in existing
CRCA box duly secured with insulating materials connected to
the meter 1.00 274.72 Nos.
Providing and erecting Approved make Four pole moulded
case circuit breaker having breaking capacity ICU of 25 KA. at
415 V,having normal current rating up to 25 A to 100A. with
Fixed thermal & magnetic release suitable to work on A.C.
supply 50 c/s. with all internal connections, spreader tinned
copper & complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III 1.00 6173.12 Nos.
27 providing and erecting Miniature circuit breaker single pole
0.5A to 2A system and having breaking capacity 10 KA to be
erected in existing box. confirming to IS 8828/1996 with ISI
Mark Cat.III 30.00 270.68 Nos.
Providing & erecting 415V MCB Four Pole Switch for Lighting
Load (B curve) having 10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
(A) 6 to 32 Amp. Cat.III
Add 3 % Cont. & Superv. :
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
02. SBD.pdf
Invitation.pdf
Schedule-B.pdf
Terms and Conditions.pdf
Volume 1.pdf
Download all tender documents and submit your bid