Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.5 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹33.5 L+₹5.0 L (17.6%)Rejected-Finance | L2 | Rejected-Finance Rejected as stood L2 | |
| 3 | L3₹35.4 L+₹6.9 L (24.1%)Rejected-Finance | L3 | Rejected-Finance Rejected as stood L3 |
| Sl No | Description | Qty | Unit | GLYPTIC L1 | Greentech Solution L3 | Integrated Engineering Solutions L2 |
|---|---|---|---|---|---|---|
| 1.00Day to day preventive & corrective maintenance of the entire Fire Detection system installed at different buildings of IPGME&R-SSKM Hospital and it's Annex Hospitals by engaging manpower round the clock in each shift having adequate knowledge & skill in fire detection system as per terms & condition. | ||||||
| 1.10 | Semi-skilled labour - 3 nos staff | 12 | per month | 70,000 ₹8,40,000 Lowest | 85,000 ₹10,20,000 | 79,500 ₹9,54,000 |
| 1.20 | Un-Skilled labour - 4 nos staff | 12 | per month | 66,500 ₹7,98,000 Lowest | 80,000 ₹9,60,000 | 89,900 ₹10,78,800 |
| 2.00Replacement cost for following supply & installation of spare parts (Consumable spares & Emergency spares) as and when required for annual preventive and corrective maintenance of Fire Detection System. (As per attached Annexure I&II) | ||||||
| 2.01 | Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 4 loop control panel ( VDS / EN approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. (Make:Siemens) | 1 | No. | 3,75,000 ₹3,75,000 Lowest | 4,85,000 ₹4,85,000 | 3,95,000 ₹3,95,000 |
| 2.02 | Supply, Installation, Testing & Commissioning Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 2 loop control panel ( VDS / EN approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. (Make: Esser) | 1 | No. | 2,50,000 ₹2,50,000 Lowest | 3,75,000 ₹3,75,000 | 2,85,000 ₹2,85,000 |
| 2.03 | Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/EN aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard (Make: Siemens) | 50 | Nos. | 4,700 ₹2,35,000 Lowest | 5,200 ₹2,60,000 | 4,885 ₹2,44,250 |
| 2.04 | Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/EN aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard (Make: Esser) | 4 | Nos. | 4,700 ₹18,800 Lowest | 5,700 ₹22,800 | 4,860 ₹19,440 |
| 2.05 | Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / EN approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Make: Siemens) | 9 | Nos. | 4,100 ₹36,900 Lowest | 4,900 ₹44,100 | 4,250 ₹38,250 |
| 2.06 | Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / EN approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Make: Esser) | 5 | Nos. | 3,500 ₹17,500 Lowest | 4,600 ₹23,000 | 3,600 ₹18,000 |
Tender Value
₹29.0 L
EMD Value
₹57,935
Closing Date
19 Feb 2025, 12:00 pmClosed
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
75 Diamond Harbour Road Kolkata 23
Upkeepment and maintenance Round the clock yearly basis for FIRE DETECTION SYSTEM and allied accessories etc at all buildings within the campus of IPGMER SSKM Hospital.
2025_WBPWD_804549_1
WBPWD/EE-I/KSHED/Q107/24-25
Open Tender
Support/Maintenance Service
Item Rate
365 days
SSKM Hospital Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹57,935
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
24 Nov 2025
21 Jan 2025
21 Feb 2025
21 Jan 2025
19 Feb 2025
27 Jan 2025
27 Jan 2025
Amount
Day to day preventive & corrective maintenance of the entire Fire Detection system installed at different buildings of IPGME&R-SSKM Hospital and it's Annex Hospitals by engaging manpower round the clock in each shift having adequate knowledge & skill in fire detection system as per terms & condition.
Semi-skilled labour - 3 nos staff
Un-Skilled labour - 4 nos staff
Replacement cost for following supply & installation of spare parts (Consumable spares & Emergency spares) as and when required for annual preventive and corrective maintenance of Fire Detection System. (As per attached Annexure I&II)
Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 4 loop control panel ( VDS / EN approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. (Make:Siemens)
Supply, Installation, Testing & Commissioning Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 2 loop control panel ( VDS / EN approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. (Make: Esser)
Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/EN aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard (Make: Siemens)
Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/EN aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard (Make: Esser)
Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / EN approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Make: Siemens)
Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / EN approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Make: Esser)
Supply, Installation, Testing & Commissioning Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / EN approved) approved. (Make: Siemens)
Supply, Installation, Testing & Commissioning Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / EN approved) approved. (Make: Esser)
Supply, Installation, Testing & Commissioning Addressable Manual Call Point (VDS / EN approved) soft addressable type within built fault isolator as per NFPA style 7 wiring complete as required. (Make: Siemens)
Supply, Installation, Testing & Commissioning Addressable Manual Call Point (VDS / EN approved) soft addressable type within built fault isolator as per NFPA style 7 wiring complete as required (Make: Esser)
Supplying, installation, testing and commissioning of LED type Response Indicator (VDS / EN approved) having 2 Nos. red coloured LED lamps including connections etc. (Make: Siemens)
Supply, Installation, Testing & Commissioning of LED type Response Indicator (VDS / EN approved) having 2 Nos. red coloured LED lamps including connections etc. (Make: Esser)
Supply, Installation, Testing & Commissioning of LED type relay Modules (VDS / EN approved)
S&F of MCP Glass in place of damaged one.
S&F UPS Battery FR Type Make: Exide / Amaron
12Volt,12AH SMF, Make - Exide/Amaron
12Volt,7AH SMF, Make - Exide/Amaron
Supply & Laying of 2 core 1.5 sq.mm FRLS shielded copper cable (for loop)(make: Finolex/Gloster/Polycab)
Supply & Laying of 2 core 1.5 sq.mm FRLS shielded copper cable (for loop)(make: Finolex/Gloster/Polycab)
Supply & Laying of rigid PVC pipe (make - Precision/Polycab) incl. all accessories type medium/heavy as per direction of EIC.
Rate should be quotated inclusive of LWC and all other related related taxes & duties
Integrated Engineering Solutions (BID ID -6111612)
Greentech Solution (BID ID -6132362)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .