Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.0 CrAccepted-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | ₹1.0 Cr | L1 | Accepted-AOC L1 Accepted |
| 2 | L2₹1.2 CrRejected-AOC | ₹1.2 Cr | L2 | Rejected-AOC L2 Rejected |
| Sl No | Description | Qty | Unit | ELCON ELECTRICALS L1 | Biju E.M L2 |
|---|---|---|---|---|---|
| 1.00750KVA Transformer and MSB | |||||
| 1.00 | OD107764/2025-2026:Supply, conveyance, installation, testing, and commissioning of 750kVA outdoor type Unitized Substation (USS) comprising HT multi panel , dry-type cast resin transformer, with necessary HT/LT termination system as a compact integrated assembly suitable for 11kV/433V, 3-phase, 50Hz power supply as incomer. The HT panel includes HT ,TOD metering facility , 3 Nos. ---/5A, 15VA, Class 0.2S CTs, 1 No. 3-phase 3-limb 11kV/110V, 15VA, Class 0.2 PT and test terminal block with sealing arrangement as per KSEBL standards.HT multipanel consist of 1No 11kV, 630A, 3-phase, 350MVA Vacuum Circuit Breaker (VCB) motorised as incomer with Emergency Push button, 50/51 over current, 50N/51N earth fault, 86 lockout relay, shunt trip coil, including all other related components for VCB operation and protection systems and 2Nos 630A, 3-phase, 350MVA Air Break Switch Fuse Units (HT AB SFU) with 40A HRC fuses as outgoings with suitable size 11KV copper busbar . (1No for connecting the existing transformer and other for 750KVA newly proposed transformer). The transformer shall be 750kVA, 11kV/433V, 50Hz, Delta/Star connected, cast resin insulated copper wound with Class F insulation and Off-Load Tap Changer (OLTC) of 2.5% x 5 steps, built with laser scribed core conforming to ECBC norms. The LT section shall include one 1250A, 4P ACB with 50kA breaking capacity, 3 O/C + 1 E/F releases, and under-voltage trip coil set at 80% (1000A), along with a 200/5A Class 5P10, 10VA Neutral CT connected to a 51G relay for sensitive earth fault protection, MF meter showing voltage and current.All interconnections shall be made using electrolytic grade copper busbars, tinned at contacts and insulated with heat-shrinkable sleeves. Internal earthing, phase barriers, and shrouding shall be provided as per IS standards. The entire structure shall be fabricated from CRCA sheets conforming to IP 54 , seven-tank treated and powder-coated, and the installation shall be carried out at site under the supervision of the Engineer-in-Charge | 1 | each | 30,50,000 ₹30,50,000 | 34,32,500 ₹34,32,500 |
| 1.00 | OD114659/2025-2026:Supply, installation, and fixing of 11kV Load Break Switch (LBS) panel outdoor type, comprising 630A, 3-phase, 350MVA Air Break Switch Fuse Units (HT AB SFU) with 40A HRC fuses. The panel shall be provided with a 230V AC trip coil, mechanical trip mechanism, manual operating handle, ON/OFF push buttons, ON/OFF indicator lamps, and integrated earth switch with mechanical interlock to ensure safety during maintenance. The assembly shall include HRC fuse links for protection, space heater with thermostat for moisture control, and shall be housed in a weatherproof, powder-coated CRCA sheet steel enclosure suitable for outdoor installation. The panel shall be complete with high-conductivity copper busbars, necessary internal wiring, interlocks, and mounting arrangements, ready for energization and compliant with relevant IS/IEC standards. | 1 | each | 1,30,000 ₹1,30,000 | 1,47,300 ₹1,47,300 |
| 1.00 | OD107182/2025-2026:Supply and installation of 3-phase, 4-wire 110 V (L-L), -/1 A CT or -/5A CT, accuracy class 0.2S, TOD meter as per the KSEB Norms including arranging the testing from KSEB TMR unit, and arranging the inspection and necessary arrangement for charging the HT system as required | 1 | each | 40,000 ₹40,000 | 500 ₹500 |
| 1.00 | OD124742/2025-2026:Supply, laying of 1no power cable,11KV grade of the following sizes in the existing masonry open duct as required. 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated , insulation screened with extruded semi conducting compound in combination with copper tape(0.3 KA for 1 sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS:7098 part II 1985 with latest amendments | 100 | metre | 2,170 ₹2,17,000 | 4,400 ₹4,40,000 |
| 1.00 | OD124743/2025-2026:Supply and laying of 1no aluminum power cable,11KV grade of the following sizes in the existing RCC/HUME/STONE WARE/GI/DWC pipe as required. 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated , insulation screened with extruded semi conducting compound in combination with copper tape(0.3 KA for 1 sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS:7098 part II 1985 with latest amendments | 25 | metre | 2,200 ₹55,000 | 4,400 ₹1,10,000 |
| 1.01 | 10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm | 5 | each | 10,000 ₹50,000 | 16,800 ₹84,000 |
| 1.01 | 10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete
with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor
cable of 11 KV grade as required :300 sq. mm | 1 | each | 15,000 ₹15,000 | 15,000 ₹15,000 |
| 1.01 | OD280460/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminum armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5x400 sqmm | 20 | metre | 2,100 ₹42,000 | 4,200 ₹84,000 |
| 1.01 | OD280458/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE Aluminum conductor armoured power cable of 1.1 KV grade conforming to IS1554/(part I)/1988 for PVC & IS7098 (part I)/1988 for XLPE of following size in the existing masonry open duct as required. 3.5x400 sq. mm | 240 | metre | 2,100 ₹5,04,000 | 4,200 ₹10,08,000 |
Tender Value
₹1.0 Cr
EMD Value
₹50,000
Closing Date
7 Feb 2026, 6:00 pmClosed
Chief Electrical Engineer
Office of the Chief Electrical Engineer PWD Electrical Wing Public Office Thiruvananthapuram
DEPOSIT Providing additional Transformer and connected Electrical works in Govt. Medical College, Manjeri Malappuram District Health Family Welfare Department Implementation of the Plan Scheme Government Medical College Manjeri Minor Works
2026_PWD_832450_1
PWD/BLDG/TR/11169/2025_6_1_1/1
Open Tender
Electrical Works
270 days
MCH MANJERI MALAPPURAM
Please refer Tender documents.
7 documents required · 7 mandatory
₹6,508
₹50,000
Yes
11 Mar 2026
31 Jan 2026
10 Feb 2026
31 Jan 2026
7 Feb 2026
31 Jan 2026
31 Jan 2026 - 7 Feb 2026
750KVA Transformer and MSB
OD107764/2025-2026:Supply, conveyance, installation, testing, and commissioning of 750kVA outdoor type Unitized Substation (USS) comprising HT multi panel , dry-type cast resin transformer, with necessary HT/LT termination system as a compact integrated assembly suitable for 11kV/433V, 3-phase, 50Hz power supply as incomer. The HT panel includes HT ,TOD metering facility , 3 Nos. ---/5A, 15VA, Class 0.2S CTs, 1 No. 3-phase 3-limb 11kV/110V, 15VA, Class 0.2 PT and test terminal block with sealing arrangement as per KSEBL standards.HT multipanel consist of 1No 11kV, 630A, 3-phase, 350MVA Vacuum Circuit Breaker (VCB) motorised as incomer with Emergency Push button, 50/51 over current, 50N/51N earth fault, 86 lockout relay, shunt trip coil, including all other related components for VCB operation and protection systems and 2Nos 630A, 3-phase, 350MVA Air Break Switch Fuse Units (HT AB SFU) with 40A HRC fuses as outgoings with suitable size 11KV copper busbar . (1No for connecting the existing transformer and other for 750KVA newly proposed transformer). The transformer shall be 750kVA, 11kV/433V, 50Hz, Delta/Star connected, cast resin insulated copper wound with Class F insulation and Off-Load Tap Changer (OLTC) of 2.5% x 5 steps, built with laser scribed core conforming to ECBC norms. The LT section shall include one 1250A, 4P ACB with 50kA breaking capacity, 3 O/C + 1 E/F releases, and under-voltage trip coil set at 80% (1000A), along with a 200/5A Class 5P10, 10VA Neutral CT connected to a 51G relay for sensitive earth fault protection, MF meter showing voltage and current.All interconnections shall be made using electrolytic grade copper busbars, tinned at contacts and insulated with heat-shrinkable sleeves. Internal earthing, phase barriers, and shrouding shall be provided as per IS standards. The entire structure shall be fabricated from CRCA sheets conforming to IP 54 , seven-tank treated and powder-coated, and the installation shall be carried out at site under the supervision of the Engineer-in-Charge
OD114659/2025-2026:Supply, installation, and fixing of 11kV Load Break Switch (LBS) panel outdoor type, comprising 630A, 3-phase, 350MVA Air Break Switch Fuse Units (HT AB SFU) with 40A HRC fuses. The panel shall be provided with a 230V AC trip coil, mechanical trip mechanism, manual operating handle, ON/OFF push buttons, ON/OFF indicator lamps, and integrated earth switch with mechanical interlock to ensure safety during maintenance. The assembly shall include HRC fuse links for protection, space heater with thermostat for moisture control, and shall be housed in a weatherproof, powder-coated CRCA sheet steel enclosure suitable for outdoor installation. The panel shall be complete with high-conductivity copper busbars, necessary internal wiring, interlocks, and mounting arrangements, ready for energization and compliant with relevant IS/IEC standards.
OD107182/2025-2026:Supply and installation of 3-phase, 4-wire 110 V (L-L), -/1 A CT or -/5A CT, accuracy class 0.2S, TOD meter as per the KSEB Norms including arranging the testing from KSEB TMR unit, and arranging the inspection and necessary arrangement for charging the HT system as required
OD124742/2025-2026:Supply, laying of 1no power cable,11KV grade of the following sizes in the existing masonry open duct as required. 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated , insulation screened with extruded semi conducting compound in combination with copper tape(0.3 KA for 1 sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS:7098 part II 1985 with latest amendments
OD124743/2025-2026:Supply and laying of 1no aluminum power cable,11KV grade of the following sizes in the existing RCC/HUME/STONE WARE/GI/DWC pipe as required. 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated , insulation screened with extruded semi conducting compound in combination with copper tape(0.3 KA for 1 sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS:7098 part II 1985 with latest amendments
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
OD280460/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminum armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5x400 sqmm
OD280458/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE Aluminum conductor armoured power cable of 1.1 KV grade conforming to IS1554/(part I)/1988 for PVC & IS7098 (part I)/1988 for XLPE of following size in the existing masonry open duct as required. 3.5x400 sq. mm
OD280461/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x400 sqmm (clamped with 40x3mm MS flat clamp)
OD280463/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5x240 sqmm
OD280464/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x240 sqmm (clamped with 40x3mm MS flat clamp)
OD280465/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x185 sqmm (clamped with 25/40x3mm MS flat clamp)
OD280466/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 KV grade conforming to IS1554/(part I)/1988 for PVC & IS7098 (part I)/1988 for XLPE of following size in the existing masonry open duct as required 2x10 sq. mm
OD280467/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I )/1988 for XLPE of following size on wall surface as required 2x10 sqmm (clamped with 1mm thick saddle)
9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
OD288952/2025-2026:Supplying and providing earth clamps for siemens/ tropodor type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required. 1.5 sq mm to 16 sqmm size cable with 12 mm wide x 1 mm thick clip
OD288953/2025-2026:Supplying and providing earth clamps made out of copper strips of the following sizes including cutting and bending the flat exactly to the shape of the gland, drilling necessary holes for nut & bolt, tinning the points of contacts and giving connections to the main earthling system as required. 20 x 3 mm for earthing glands of size 120 sq mm to 185 sq mm
OD288954/2025-2026:Supplying and providing earth clamps made out of copper strips of the following sizes including cutting and bending the flat exactly to the shape of the gland, drilling necessary holes for nut & bolt, tinning the points of contacts and giving connections to the main earthling system as required. 25 x 3 mm for earthing glands of size 240 sq mm to 300 sq mm
OD288955/2025-2026:Supplying and providing earth clamps made out of copper strips of the following sizes including cutting and bending the flat exactly to the shape of the gland, drilling necessary holes for nut & bolt, tinning the points of contacts and giving connections to the main earthling system as required. 25 x 6 mm for earthing glands of size 400 sq mm to 630 sq mm
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.9.5:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench90/75 mm or nearest size
3.5.3:Supplying, installation, including suspension, testing and commissioning of following capacity bus trunking with aluminium bus bars in 1.6mm thick sheet steel enclosure in convenient sections for use on, 3 phase, 4 wire, 415 volts, 50 Hz, A.C. supply including jointing of sections, flexible joints, expansion joints, bends and earthing with 2 runs of galvanised iron strips, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.1250 amps
OD276526/2025-2026:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & shall conform to relevant IS .Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD281002/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 10.00sq mm wire single run
OD281001/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 6.00sq mm wire single run
OD280996/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 4.00sq mm wire single run
OD280995/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 2.50sq mm wire single run
OD124754/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipment's including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run
OD115025/2025-2026:Supplying and fixing 2 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing panel board complete with connections, testing and commissioning etc. as required. Single pole
90.14.10.21:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.400A, 70 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.2:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.8.18:1250 A, 4 pole, electrical draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA
90.14.8.16:800 A, 4 pole, electrical draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA
OD118844/2025-2026:Supply and fixing of Shunt Release coil suitable for Air Circuit Breakers (ACBs)
OD118845/2025-2026:Supply and fixing of Under Voltage Release (UVR) module with adjustable time delay ranging from 0.2 seconds to 3.2 seconds, suitable for Air Circuit Breakers (ACBs).
OD118435/2025-2026:Supply, installation, programming, testing, and commissioning of a complete PLC-based automation system using SMART PLC for the control and automation of electrical loads and power sources in existing MSB panels. The scope of work includes complete wiring with all control components (wires, relays, connector, numbering ferules etc) and interfacing of the PLC with multifunction energy meters, plug-in relays, SMPS units, and other protective devices. All components shall be properly installed, labeled, and integrated within the panel infrastructure. The system shall communicate using the MODBUS protocol over RS-485, enabling real-time data exchange between the PLC and connected field devices. The PLC shall be programmed to monitor real-time parameters such as grid (KSEB) availability, generator readiness, and load thresholds. Based on these conditions, the system will perform logical decision-making for source switching and load sharing, including the use of interlocks and priority-based control logic. Setpoints and operational parameters shall be configured to ensure automatic failover and safe recovery during power outages or equipment faults. Upon completion of installation, the system will undergo comprehensive testing, including load simulation and sequence verification. The commissioning process will include validation of both automatic and manual operating modes, as well as training for the operator or maintenance team. Make of PLC: Siemens S7-200 SMART or equivalent approved make. Scope Includes: All required control wiring, programming, testing tools, software loading, system documentation, and final commissioning reports in compliance with applicable IS standards and submit all control wiring diagram with PLC programming manual etc as required
OD118396/2025-2026:Supply, installation, testing, and commissioning of 12-point microprocessor-based alarm annunciator unit, Model: 2 0B 12S P0 of MBAS 0600 series, suitable for indoor panel mounting. The annunciator shall support 12 individual alarm inputs (potential-free contacts), with 12 small LED windows for alarm indication, and inbuilt audio buzzer. It shall include push buttons for Reset, Acknowledge, Test, and Mute operations, and shall operate on 230V AC or 24V DC supply (as specified). The unit shall be panel door flush mountable in 2D box size and compatible for integration with automation systems. Communication feature RS-485 MODBUS shall be available optionally, if required. Alarm status should be clearly visible even in bright ambient lighting, and all components should comply with industrial standards. Make: Rishabh, Prok Devices, Micon, Selec, Minilec, L&T or equivalent approved make
OD112245/2025-2026:Supply and Fixing 1200/5A , 15VA Accuracy class 1 , Resin cast metering CT
OD112244/2025-2026:Supply and Fixing 800/5 A, 15 VA, accuracy class 1, Resin Cast Metering CT
OD113212/2025-2026:Supply and fixing 250/5 A, 10 VA, accuracy class 1, Resin Cast Metering CT including connection in existing Panel board.
OD113213/2025-2026:Supply and fixing 100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT including connection in existing Panel board.
OD124756/2025-2026:Supply and fixing LED indication lamp for all voltage ranges- Red, Green, Blue, Yellow, colour in existing panel and giving connection etc as required
OD177342/2025-2026:Supply and fixing Blue colour LED indicator, AC/DC, 22.5 mm cut out dia
OD289822/2025-2026:Supply, installation, testing, and commissioning of numerical protection relay, Make: L&K, Model: MC12, Catalog No: MC12AB50X00, suitable for earth fault protection with protection functions 50N and 51N. The relay shall operate on an auxiliary supply voltage range of 88-264V AC/DC and support CT secondary input of 5A. It shall be microprocessor-based, capable of high-speed and reliable tripping, and equipped with LED indications, test/reset button, and front panel programmability. The unit shall be housed in a compact enclosure suitable for panel mounting. All necessary accessories, wiring, mounting hardware, and tools for installation and commissioning shall be included to ensure full functionality and integration into HT/LT protection panels.
90.14.24.68:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
90.14.24.71:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
90.14.24.73:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
90.14.24.74:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
OD113231/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks 4-7 kVAR with AC Coil, including suitable no NO/NC auxiliary contractor in existing panel board and giving connection etc as required.
OD113230/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks 7.5-10 kVAR with AC Coil, including suitable no NO/NC auxiliary contractor in existing panel board and giving connection etc as required.
OD113229/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks 11-15 kVAR with AC Coil, including suitable no NO/NC auxiliary contractor in existing panel board and giving connection etc as required.
OD113460/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks 20 kVAR with AC Coil, including suitable no NO/NC auxiliary contractor in existing panel board and giving connection etc as required.
OD113475/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 5 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection.
OD113474/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 10 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection.
OD113473/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 15 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection.
OD113472/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 20 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection.
OD113225/2025-2026:Supply and providing 8 stage 440/110V 5/1A Intelligent power factor controller in the existing panel board and giving connection.
OD113220/2025-2026:Supplying and fixing 24Hr Analog Timer switch with NO/NC operating voltage 230V in the existing APFC Panel complete with connections, testing and commissioning etc. as required
OD113221/2025-2026:Supply and providing 150 mm panel mounting cooling fan with fresh air grill working on 230 V A/C in the existing APFC Panel using bolt and nuts including giving connections etc. as required
OD113222/2025-2026:Supply and fixing push button with NO/NC Auxilary contacts in the existing panel board and giving connection etc. as required.
OD113223/2025-2026:Supplying and fixing following rating 40A, four pole, 415 volts, MCX 04 type Power Contactor in the existing Panel board complete with connections, testing and commissioning etc. as required.
OD83654/2025-2026:Supply and fixing following multi function meter to read V,A,F, 3phase accuracy class1 in existing panel and giving connection complete.
OD124757/2025-2026:Supply and providing plate earthing with 1200x1200x12mm GI earth plate,50 mm GI(medium class) watering pipe,GI funnel with weld mesh,25x5 mm GI clamps,CI/MS cover plate with locking arrangements,charcoal/coke and salt etc including providing brick work masonry enclosure at the top (450x450x450mm inside)etc as required.
OD124760/2025-2026:Supply and providing and fixing 32 mm X 6 mm G.I. strip earth lead from the test joint to the earth plate
OD124761/2025-2026:Supply and providing and fixing 2 X 32 mm X 6 mm G.I. strip test joint for earthing system
90.16.3.5:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 6 mm GI strip
90.16.4.5:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).32 x 6 mm GI strip
OD124759/2025-2026:Supply and providing the following sizes of strips in ordinary soil below ground level including excavation. as required .32 x 6 mm GI strip
OD97285/2025-2026:Supply and providing 25x6mm brass bolt
OD111979/2025-2026:Charges for dismantling the existing aluminium cable complete ,good the damages of wall and conveying the dismantled materials to the section store
OD124762/2025-2026:Cleaning and painting the existing MSB panel attending minor repairs, including control wiring, with replacing indication lamps, auto/manual operation switches, meters etc, including test running etc as required
OD124785/2025-2026:SITC of 5Kg ABC Fire Extinguisher cap filled with mono ammonium phosphate powder 50% confirms to IS 1409, stored pressure type, with pressure gauge, the discharge time 24 sec, controllable discharge mechanism, jet range 5 meters, average discharge is 90%, applicable on A,B & C and electrically started fire, A rating-3A, B rating 21B, construction: deep drawn & co2 mig welded, EPDM rubber hose with both end aluminium clamped, internal coating-epoxy powder coating, external coating-pure polyster powder coating(UV resistant),brass forged valves with safety pin is of ss material, sheet metal thickness ISI approve
OD124786/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD124791/2025-2026:Supply and providing Class B (2.5 mm thick) Elastomeric insulating mat conforming to IS 15652/2006 with maximum use voltage is 11KV.
OD124792/2025-2026:Supply and providing 9 litre capacity Galvanized mild steel Fire bucket conforming to IS 2546-1974. The bucket shall be galvanized and painted with two coats of white paint on the inside and two coats of red paint on the outside. The handles and ears shall be painted with two coats of black paint. The word 'FIRE" shall be painted in black centrally on the outside,its letters shall be 75 mm high and approximately 12 mm thick.The bucket shall be water tight.The bucket shall be fixed on MS angle frame work/ wall bracket filled with fine sand .
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD178437/2025-2026::Supply and providing Bus bar chamber, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required
OD178438/2025-2026::Supply and providing Cable alley, 100 x 40 mm aluminum anodized legend plates in the existing panel board as required
OD178439/2025-2026:Supply and providing Earth, 40 x 20 mm with 8 mm hole aluminum anodized legend plates in the existing panel board as required
OD124790/2025-2026:Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required
OD112160/2025-2026:Charges for preparation of Electrical Drawing per A3 sheet first copy - (Prepare all LT additional in the exiting installation and regularize the all installation in hospital campus building)
OD112161/2025-2026:Copying charges of Electrical/fire Drawing per A3 sheet additional copies
OD162975/2025-2026:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level: 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)(CIVIL WORKS Specification code No: 4.1.8)
OD163023/2025-2026:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level: 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size derived from natural sources)(CIVIL WORKS Specification code 5.1.3)
OD163162/2025-2026:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo - Mechanically Treated bars of grade Fe-500D or more(CIVIL WORKS specification code no:5.22.6)
OD163190/2025-2026:Centering and shuttering including strutting, etc. and removal of form for: Lintels, beams, plinth beams, girders bressumers and cantilevers(CIVIL WORKS specification code no:5.9.5)
OD163269/2025-2026:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil(CIVIL WOKS specification code no:2.8.1)
OD163268/2025-2026:Solid block masonry using pre cast solid blocks ( factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part 1 of 1979 for foundation and plinth with thickness 20 cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete(CIVIL WORKS specification no:50.6.1.1)
OD163267/2025-2026:12 mm cement plaster of mix: 1:4 ( 1 cement : 4 fine sand)(CIVIL WORKS specification code no:13.1.1)
OD163266/2025-2026:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface: Water thinnable cement primer (CIVIL WORKS Specification code: 13.43.1)
OD163265/2025-2026:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work( CIVIL WORKS specification code :13.60.1)
OD163264/2025-2026:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete(CIVIL WORKS specification code no :50.10.1)
OD163263/2025-2026:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete (CIVIL WORKS specification code no:50.10.2)
OD163384/2025-2026:Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.(CIVIL WORKS specification no: 10.2)
OD163383/2025-2026:Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide P A 6 grade sleeve, including drilling of hole in frame, concrete/masonry, etc. as per direction of Engineer-in-charge. 10x120 mm(CIVIL WORKS specification no:10.27.3)
OD163382/2025-2026:Providing valleys of 90 cm wide overall in plain G.S. sheet fixed with polymer coated J or L hooks, bolts and nuts 8 mm dia G.I. limper and bitumen washers complete:1.60 mm thick with zinc coating not less than 350 gm/ m2(CIVIL WORKS specification no:12.5.1)
OD163381/2025-2026:Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screwscomplete : Ridges plain (500-600 mm)( CIVIL WORKS specification no 12.51.1)
OD163380/2025-2026:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work(CIVIL WORKS specification no:13.61.1)
OD163415/2025-2026:Dry rubble masonry with hard stone in foundation and plinth including cost of through stone and bond stone.
OD163379/2025-2026:Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar (CIVIL WORKS specification code no:15.7.4)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1399310.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
SBD.pdf
Tender Documents • 4.05 MB
MOM.pdf
Tender Documents • 0.42 MB
BOQ_1399310.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid