Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.4 LAccepted-AOC | L1 | Accepted-AOC First Lowest quoted bidder and negotiation | |
| 2 | L2₹9.6 L+₹73,647 (8.30%)Rejected-Finance 1763 JOSHI VAS OPP RAMJI MANDIR B H NAVRANGPURA POLICE STATION NAVRANGPURA AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | L2 | Rejected-Finance Not First lowest quoted bidder |
Tender Value
₹7.8 L
EMD Value
₹15,666
Closing Date
9 Jun 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer
The Executive Engineer, Indian Institute of Technology Gandhinagar, Academic Block No. 03-112A, IIT Gandhinagar, Palaj, Gandhinagar, Gujarat 382355
Providing and fixing of Kitchen Exhaust system for Shop of Hostel-H at IIT Gandhinagar
2022_IITGN_689604_1
03/IITGN/IWD/2022-23
Open Tender
Electrical Works
Item Rate
60 days
IIT Gandhinagar
As per tender Document
2 documents required · 2 mandatory
₹500
Payable To IIT Gandhinagar
₹15,666
IIT Gandhinagar
21 Jul 2022
18 May 2022
10 Jun 2022
19 May 2022
9 Jun 2022
19 May 2022
19 May 2022 - 24 May 2022
24 May 2022
Amount
Supplying, installation, testing and commissioning of factory built floor mounted double skin horzontal wet scrubber units made of 45 mm thick panel, consisting of pre plasticized G.l. casing of thickness 0.6mm outside layer and 0.6 mm inside layer with 40 Kg/m³ density polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with forward / backward curved AMCA certified blower (Efficiency>75%) suitable for static pressure as required, TEFC weather proof motor of IP55 protection having efficiency class IE3 at 415±10% volts, 3 phase, 50 cycles power , Plug Type Fan with metallistik vibration isolators. Fan capacity shall be based on outlet velocity not exceeding 600 M/minute. The unit shall consist of double bank spray chamber having 90 % saturation efficeincy with water tank made up of 18 G SS, brass Nozzle , GI spray header , GI intake louver, 4/6 bend PVC eliminator, strainer with brass jaali, gate valve, NRV and sump strainer, GI piping from strainer, gauges and fittings including all the necessary valves and its arrangement. 2 No. (1W+1SB) pumps (of suitable rating) of factory mounted on GI channel base with electric motor for circulation of water. Pumps shall be aligned and suitable for415±10% volts, 50 cycles’s, 3 phase power supply. One No. 3 phase isolator switch in weather proof enclosure shall be provided near motor.The unit shall be compatible with BMS System.Unit shall be complete in all respect
6000 CFM, Total Static pressure of 65 mm WG
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration.
Damper
Actuator
Supplying and installation of rigid ISI marked UPVC drain piping of 10 Kg/sq.cm of pressure rating of following sizes for the unit as per specification including all accessories like bends, tees, clamps and supports etc. complete etc. as requried.
32 mm dia
Supplying , fixing, testing and commissioning of following nominal sizes Class "B" GI drain water piping complete with fittings, supports, U trap arrangement, drain plug and accessories for Wet SCRUBBER as per specifications etc. complete etc. as requried.
32 mm dia
Supplying ,laying and fixing on wall / terrace of one number XLPE insulated and PVC sheathed armoured power cable of 1.1 KV grade ISI marked confirming to IS 7098 ( Pt.-1) following size etc. as required
4C X 6 Sqmm Copper conductor cable .
4X 2.5 sq. mm copper conductor( Between remote push button and panel on terrace)
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Providing and fixing Pump on/off push button type remote switches on surface or recess complete with connection, testing and commissioning etc as required.
Supply, installation, testing and commissioning of Kitchen exhaust hood [Size of 1500mm X600mmX500mm] Fabricated with 18 SWG, 304 Grade SS Sheet complete with Grase extraction Baffles (Filter) 304 SS, Socket for hanging, Grease collection side out tray, cutout for exhaust dut connection, 3 nos. Bulk LED fitting duly wired with fire rated cable, suspenders etc as required.
M. K. Aircon Systems Pvt. Ltd.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .