Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.9 LAccepted-Finance OPPOSITE VIPUL GAS AGENCY HOSPITAL ROAD SOLAN H P | SOLAN | SOLAN | HIMACHAL PRADESH | L1 | Accepted-Finance L1 | |
| 2 | L2₹10.5 L+₹55,112 (5.54%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹10.8 L+₹82,612 (8.30%)Rejected-Finance | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | Thakur Traders L2 | M/S Swastika Enterprises L3 | ROYAL ENGINEERING WORKS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, erection, testing & commissioning of submersible/ mono submersible pumping set of reputed make such as KSB/BS/ Johnston/Kirloshker/Worthington/Oswal/Sabar Brand conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characterstics as mentioned in item 5(A) greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton/Havels make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The Pump set shuold include water level guard , errection clamps, tubler pie fited with outlet of tank with suitable arrangement welding/connecting to GI pipe (GI pipe for pump will be issued by the department free of cost) cable clips. & depth guage etc & suitable for operation of data given below. | 1 | Set | 10,50,000 ₹10,50,000 | 10,77,500 ₹10,77,500 | 9,94,888 ₹9,94,888 Lowest |
| 1.01Note:- Out of the 2 Nos. Pumps, 1 No. pump set will run and other will act as stanfd by:- | ||||||
| 1.02Total Head 420 Mtr | ||||||
| 1.03Capacity of each pump set 5 LPS | ||||||
| 1.04Dia of Rising Main 100 MM dia | ||||||
| 1.05Length of R/Main (in meter) 2280 Mtrs | ||||||
| 1.06 | Providing and Fixing double flanged cast steel sluice valve of leader/KSB/ Kirlosker make of 50 mm capable of with standing the normal seat presure as per IS 5312-1884P-1 with upto date ammedement for class ASA-300 as per direction as per direction of Engineer-in-Charge including entire carriage of matrial up to all leads and lifts. | 1 | Each | - | - | - |
| 1.07 | Providing and Fixing double flanged swing type cast steel refluxe valve of Bir/leader/KSB/Kirlosker/Kartar/Behl/Kirlosker//Kilbum/Gled/Kartar valve/ Fouress make 50 mm for rising main and capable of with standing the normal seat presure as per IS (API-6D) with upto date ammedement for class ASA-300 as per direction as per direction of Engineer-in-Charge including entire carriage of matrial up to all leads and lifts. | 1 | Each | - | - | - |
| 1.08 | Providing and fixing of suitable direct on line/oil immersed star delta starter/ATS/stator rotor stator of standard make such as MEI/Kilburn/Jyoti/Larson & Turbo/Havell/L& T standard confirming to BIS 8544-1979 latest with up to date amendment for squirrel cage slip ring motor (make to be specified by the tendrer) mounted on p[anel board with magnetic type over load release & dashpot, time lag under voltage release with initial oil filling. | 2 | Job | - | - | - |
| 2.00 | Supplying, errection, testing commisioning of 60 HP AC induction motor make Marathon/Kirlosker/Bhel/Cropton/Jyoti/(STP type 2900 RPM 60HP) suitable to operation on 415 volts(+) (-) 10% 50 cycle/second 3 phase AC electric supply , the motor should be suitable to coupled with existing pump set complete with suitable coupling on common base plate including cost of nuts & bolts etc. as required complete in all respect. | 1 | Each | - | - | - |
Tender Value
₹10.0 L
EMD Value
₹19,950
Closing Date
28 Oct 2025, 11:00 amClosed
EE
Jal Shakti Division Rajgah
Supply and errection of 60 HP induction motor, cables and electrical items
2025_HPIPH_118502_1
5324-5423 dated 17-10-2025
Open Tender
Pumps/Motors
Item Rate
90 days
Rajgarh
Please refer Tender documents.
12 documents required · 12 mandatory
₹500
EE Rajgarh
₹19,950
Yes
6 Dec 2025
22 Oct 2025
28 Oct 2025
22 Oct 2025
28 Oct 2025
22 Oct 2025
Amount
Supply, erection, testing & commissioning of submersible/ mono submersible pumping set of reputed make such as KSB/BS/ Johnston/Kirloshker/Worthington/Oswal/Sabar Brand conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characterstics as mentioned in item 5(A) greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton/Havels make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The Pump set shuold include water level guard , errection clamps, tubler pie fited with outlet of tank with suitable arrangement welding/connecting to GI pipe (GI pipe for pump will be issued by the department free of cost) cable clips. & depth guage etc & suitable for operation of data given below.
Note:- Out of the 2 Nos. Pumps, 1 No. pump set will run and other will act as stanfd by:-
Total Head 420 Mtr
Capacity of each pump set 5 LPS
Dia of Rising Main 100 MM dia
Length of R/Main (in meter) 2280 Mtrs
Providing and Fixing double flanged cast steel sluice valve of leader/KSB/ Kirlosker make of 50 mm capable of with standing the normal seat presure as per IS 5312-1884P-1 with upto date ammedement for class ASA-300 as per direction as per direction of Engineer-in-Charge including entire carriage of matrial up to all leads and lifts.
Providing and Fixing double flanged swing type cast steel refluxe valve of Bir/leader/KSB/Kirlosker/Kartar/Behl/Kirlosker//Kilbum/Gled/Kartar valve/ Fouress make 50 mm for rising main and capable of with standing the normal seat presure as per IS (API-6D) with upto date ammedement for class ASA-300 as per direction as per direction of Engineer-in-Charge including entire carriage of matrial up to all leads and lifts.
Providing and fixing of suitable direct on line/oil immersed star delta starter/ATS/stator rotor stator of standard make such as MEI/Kilburn/Jyoti/Larson & Turbo/Havell/L& T standard confirming to BIS 8544-1979 latest with up to date amendment for squirrel cage slip ring motor (make to be specified by the tendrer) mounted on p[anel board with magnetic type over load release & dashpot, time lag under voltage release with initial oil filling.
Supplying, errection, testing commisioning of 60 HP AC induction motor make Marathon/Kirlosker/Bhel/Cropton/Jyoti/(STP type 2900 RPM 60HP) suitable to operation on 415 volts(+) (-) 10% 50 cycle/second 3 phase AC electric supply , the motor should be suitable to coupled with existing pump set complete with suitable coupling on common base plate including cost of nuts & bolts etc. as required complete in all respect.
Providing & fixing MS sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angle iron post suitable height and size ISA 40x40x6mm duly painted comparising and capable of mounting the following accessories with all internal electric connections. The drawing of panel board should be subject approval of Engineer in charge.
ICTP switches with HRC fuse of Kilburn/Larsen & Turbo Satbdard/Siemen Havells make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with up to date amendments immidiately after the poer meter of HPSEB.
Busbar chamber having three copper bars of suitable rating for full length equal to width of board of three live phases and one copper bar of half rating of full length for netural confirming to BIS 8084-1976 and 1353-1985 read with 5578-1985 all latest with up to date amendments.
ACB/MCB oil circuit breaker of suitable capacity of kilburn/L&T/MEI/GEC standard make on incoming feeder for motor offered by the tendrer conforming to BIS 250-1985 latest with up to date amendments with initial oil filling whenever required & neutral linked under voltage release.
Three phse indiacating lamps complete with toggle switches for indivdual motors conforming to BIS 3452 pari 1 & II latest with upto date amendments.
Hour run meter of reputed make of four digit capacity confirming to BIS-722 (latest eddition)/ recommendations.
Providing and fixing of 95mm2 single core copper of L&T/Havels/Alcon/Eon/make including carriage of material up to all leads & lifts.
Thakur Traders (BID ID -575614)
M/S Swastika Enterprises (BID ID -575644)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
Form6.pdf
Tender Documents • 0.76 MB
BOQ_173404.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .