Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.5 LAccepted-AOC | ₹48.5 L Quoted ₹54.0 L | L1 | Accepted-AOC Accepted as L1 bidder |
| 2 | L2₹54.5 L+₹55,803.55 (1.03%)Rejected-Finance | ₹54.5 L+₹55,803.55 (1.03%) | L2 | Rejected-Finance Quoted rate higher than L1 bidder |
Tender Value
₹42.9 L
EMD Value
₹85,852
Closing Date
30 May 2026, 3:00 pmClosed
xecutive Engineer IE Division Agartala
Office of the Executive Engineer IE Division Agartala
Supplying installation testing commissioning of 250 KVA DG set with AMF panel and relocation of old 125 KVA DG set including necessary accessories College of Fisheries Tripura
2026_CEPWD_73133_1
ACE_PU_PWD Bldgs_Elect_DNIT_05_2026_27
Open Tender
Electrical Works
Percentage
90 days
College of Fisheries Tripura
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,000
₹85,852
12 Aug 2026
20 May 2026
30 May 2026
20 May 2026
30 May 2026
20 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply installation, testing and commissioning of Silent Type -Floor Mounted Diesel Generator set CPCB IV+ Compliance model of 250KVA ,1500 RPM,0.8 Lagging power factor,3 phase Alternator at 415 volt suitable for 50Hz, 3 phase system & for 0.85 load factor and consisting of the following i/c DG Change over panel / AMF panel & supply with minimum 300 litres of fuel during the time of installation along with : DEF Tank Capable of 10-12 Hrs of Operation. a) Diesel Engine:-4 stroke, liquid cooled, Six cylinder in Line, electric start, exhaust mainfold with SS exhaust flexible, flywheel and flywheel housing, fule and lube oil filters, HDAC/Dry type air cleaner, starter motor, battery charger, capable of taking 10% over loading for one hour in 12 hours of continuos operation.Fuel consumption at 75% load should not be more than 40 litres(Considering 0.845 specific gravity of diesel,+1% tolerance),change of lubricrant oil should be at minimum 500 hrs or 1 year & lube oil consumption at 100% load should be <0.1% of FC. The engine to be fitted complete with all the required accessories. (With 5 years warranty from the date of installation or 5000 hours of running whichever is earlier). | 1 | set | 30,89,533 | ₹30,89,533 |
| 1.01 | b) Engine mounted Instrumental panel fitted with and having digital display for following:-Start-stop switch with key,Engine Temperature indication,Lubrication oil temperature indication,Battery Charging indication,starting Battery Voltage indication,Over speed indication,Low lub Oil trip Indication,Engine running hours Indication.Oil pressure indication. c) Alternator:- synchronous alternator rated at minimum 250 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor, temperature rise at 125 Degree C.Brushless Single Bearing, (4 pole), rotating field, solid state voltage regulator, voltage regulation +- 1%, insulation class H, sealed type 1 bearing, flex disc coupling, 100% rating of one step load accaptance, 25% of rated amps of unbalanced load capability. The alternator shall be having silent acoustic enclosure of IP23.(minimum 2 years warranty from the date of installation) d) Fuel Tank:-Daily service fuel Tank suitable for minimum 6 hrs of operation on full load capacity fabricated out of 3 mm thick M.S sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ' c' pipes of suitable dia complete with valves, level indicators and accessories as required as per specifications.
e) Exhaust System :-Residential silence type with minimum 05 mtr Exhaust Pipe, max allowable back pressure 10.0 kPa ,exhaust temperature 515 °C. | - | - | - | - |
| 1.02 | f) Starting System:-12 V/ 24 V DC starting system comprising of starter motors voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180 Ah capacity lead acid type) as required as per specifications.
g) Enclosure:-Powder coated weather proof (IP23) canopy Engine and alternator mounted on AV mounts with, with silence-acoustic type and SS exhaust below optimised to meet stringent MOEF / CPCB norms for sound and emission-Baserail with drawout type fuel tank, drain plug, inlet and outlet connections, airvent, level gauge. h)AMF CONTROLLER:- The system shall operate on 24V DC power and include Automatic Mains Failure (AMF) and Automatic Transfer Switch (ATS) functions. It shall have CAN bus and serial communication facilities. The device shall provide protection as per ANSI codes: 27P (under voltage), 59 (over voltage), 81U (under frequency), 81O (over frequency), 50TD (time delay overcurrent), 32F (forward power), 32R (reverse power), 14 (under speed), 12 (over speed), and 51 (inverse time overcurrent) . BREAKER DETAILS:- Three (03) numbers of MCCB( one for incomer, one for DG and one for outgoing ) shall be provided, each rated at 400A, 4-pole, with a breaking capacity of 36kA (Icu = Ics = Icw for 1 second with adjustable settings). | - | - | - | - |
| 1.03 | METERING & INDICATIONS:- The metering and indication system shall include four multifunction meters capable of measuring voltage, current, frequency, power factor, kilowatt, kilovolt-ampere, energy in KWh (old), on and run hours, with site-selectable kWh/kVAh display, accuracy class 0.5, auxiliary supply of 80–300V AC/DC, LED display, One (01) DC analog voltmeter of range 0–30V DC (MI type) and one (01) DC analog ammeter of range 0–30A DC (MI type) shall be provided. Indication lamps shall be provided as follows: red, yellow, and blue lamps operating at 230V AC; white lamp operating at 24V DC. All indication lamps shall be of cluster LED type of 22.5mm dia. CT DETAILS:-Three (03 sets. of Current Transformers (CTs) shall be provided, each having a rating of 400A/5A. BATTERY CHARGER:- One(01) no. of battery charger shall be provided of CCCV type. CONTROL CIRCUIT ACCESSORIES:- The control circuit accessories shall consist of push button actuators (green, red, and emergency type), TNC switches, contact block modules (NO and NC), control relays with relay bases, selector switches,MCB as suitable for above installation | - | - | - | - |
| 2 | Supply and fixing of extra exhaust pipe beyond the exhaust pipe provided with DG set. (i)150 mm dia MS pipe including fabrication, painting etc as required:- | 6 | mtr | 2,787 | ₹16,722 |
| 3 | Earthing with 40 mm dia G.I. Earth pipe (medium gauge) 4.5 m. long complete with masonry enclosure on top CI cover plate size 12"x 12" having locking arrangement including CC work, holes on earth pipe etc. as required. | 6 | set | 3,829 | ₹22,974 |
| 4 | Extra for using salt (5 kg) and charcoal (46kg) for pipe earth electrode as required. | 6 | set | 780 | ₹4,680 |
| 5 | Proving and fixing / drawing of 4.06 mm dia (8 SWG) G.I. wire on surface or in existing G.I/ PVC/ Polythene pipe for loop earthing as required. | 120 | mtr | 24 | ₹2,880 |
| 6 | Providng and laying 15mm dia (medium gauge) G.I. pipe for drawing of 4.06mm (8SWG) dia G.I./ Copper wire for earth connection from earth electrodes etc as required. | 8 | mtr | 193 | ₹1,544 |
| 7 | Earthing with Copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12"x 12" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:- | 2 | set | 14,532 | ₹29,064 |
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_74427.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
DNIeT.pdf
Tender Documents • 2.80 MB
BOQ_74427.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .