Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.1 LAccepted-AOC KSEB COLONY PANGBA IPAMBA | THIRUVANANTHAPURAM | KERALA | 695001 | L1 | Accepted-AOC lowest | |
| 2 | L2₹5.2 L+₹11,727 (2.31%)Rejected-AOC ALAPPUZHA | ALAPPUZHA | KERALA | 686534 | L2 | Rejected-AOC second lowest |
| Sl No | Description | Qty | Unit | RAMESH KARUNAKARAN L1 | Angel electricals L2 |
|---|---|---|---|---|---|
| 1.00ELECTRIFICATION | |||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 55 | point | 1,433 ₹78,815 | 1,116 ₹61,380 Lowest |
| 1.00 | 1.55.2:Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B | 7 | point | 736 ₹5,152 Lowest | 800 ₹5,600 |
| 1.00 | 1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). | 8 | each | 466 ₹3,728 Lowest | 510 ₹4,080 |
| 1.00 | OD118653/2025-2026:Supplying and fixing Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directely on wall or ceiling and its accessories neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, . Philips make model no. BN308C LED20S-6500 L120 PSU WH or it's equivalent. make) | 4 | each | 1,643 ₹6,572 | 1,600 ₹6,400 Lowest |
| 1.00 | OD118651/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. ceiling with with GI string and its accessories neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, (Philips Endura Next, model No. BN 308 C LED 20 S L 120 or its equivalent make ) | 16 | each | 1,840 ₹29,440 Lowest | 2,000 ₹32,000 |
| 1.01 | OD118652/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types commercial LED integrated batten made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on ceiling with GI string and accessories and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required. 1x34 w LED fitting with electronic driver, Aluminum heat sink,50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, etc.. Philips make model no. Endura BN308C LED40S-or it's equivalent. | 4 | each | 2,726 ₹10,904 Lowest | 3,000 ₹12,000 |
| 1.01 | OD114636/2025-2026:Supply conveyance, installation, testing and commissioning of 3600 lumen round/ square(1X1)
surface mount fitting made of diecast aluminium, having efficacy not less than 110l/w, 4000 to
6000K, pf greater than 0.95, THD less than or equal to 10%, (Chip make
Cree/Osram/lumilled/Nichea) and giving connections with 16/0.20 mm 3 core PVC insulated
and sheathed round copper conductor flex wire or extending the original wiring and giving
connections as required. Make: Philips/Osram/Havells or its equivalent. | 4 | each | 4,390 ₹17,560 Lowest | 5,000 ₹20,000 |
| 1.01 | OD118647/2025-2026:Supply and fixing Conveyance, installation, testing and commissioning of 1200 lumen round/ square surface mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/NicheaS directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required | 10 | each | 1,552 ₹15,520 Lowest | 1,800 ₹18,000 |
| 1.01 | OD118648/2025-2026:Supply Conveyance, installation, testing and commissioning of 7W LED bulk head fittings suitable for surface and wall mounting output greater than 100lumen/W 6500 K with IP 65 protection and IK08 protection poly carbonate diffuser cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. including fixing as required Philips vistaglow or its equivalent | 4 | each | 814 ₹3,256 Lowest | 900 ₹3,600 |
Tender Value
Refer Docs
EMD Value
₹15,148
Closing Date
13 Aug 2025, 5:00 pmClosed
ASSISTANT EXECUTIVE ENGINEER,
O/o the Assistant Executive Engineer PWD Electrical Sub Division Idukki Painavu
GENERAL-Veterinary Polyclinic - Kumily-Construction of Veterinary Polyclinic at Kumily-Electrification works-General Electrical Work
2025_PWD_782686_1
PWD/BLDG/TR/8024/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
180 days
kumily
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,340
₹15,148
13 Oct 2025
5 Aug 2025
16 Aug 2025
5 Aug 2025
13 Aug 2025
5 Aug 2025
Amount
ELECTRIFICATION
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.55.2:Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B
1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
OD118653/2025-2026:Supplying and fixing Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directely on wall or ceiling and its accessories neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, . Philips make model no. BN308C LED20S-6500 L120 PSU WH or it's equivalent. make)
OD118651/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. ceiling with with GI string and its accessories neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, (Philips Endura Next, model No. BN 308 C LED 20 S L 120 or its equivalent make )
OD118652/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types commercial LED integrated batten made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on ceiling with GI string and accessories and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required. 1x34 w LED fitting with electronic driver, Aluminum heat sink,50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, etc.. Philips make model no. Endura BN308C LED40S-or it's equivalent.
OD114636/2025-2026:Supply conveyance, installation, testing and commissioning of 3600 lumen round/ square(1X1) surface mount fitting made of diecast aluminium, having efficacy not less than 110l/w, 4000 to 6000K, pf greater than 0.95, THD less than or equal to 10%, (Chip make Cree/Osram/lumilled/Nichea) and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required. Make: Philips/Osram/Havells or its equivalent.
OD118647/2025-2026:Supply and fixing Conveyance, installation, testing and commissioning of 1200 lumen round/ square surface mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/NicheaS directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required
OD118648/2025-2026:Supply Conveyance, installation, testing and commissioning of 7W LED bulk head fittings suitable for surface and wall mounting output greater than 100lumen/W 6500 K with IP 65 protection and IK08 protection poly carbonate diffuser cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. including fixing as required Philips vistaglow or its equivalent
OD50811/2025-2026:S u p p l y , c o n v e y a n c e , installation, testing and commissioning of 10W LED mirror lamp complete with all accessories and lamps etc. and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.(K Lite 1597 or equivalent make )
90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
OD114938/2025-2026:Supply, conveyance, installation, testing and commissioning of 300/305 mm, single phase, light duty exhaust fan in metal frame in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS.
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
OD118943/2025-2026:Supply, conveyance, installation, testing and commissioning of BLDC ceiling fans sizes using standard accessories, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep -BLDC rated ceiling fan complete with 300mm down rod , canopies, shackeles and blades working on 140V/285V single phase AC 230 m3/min 350 rpm Pf 0.9 25 watt Attomberg EFFICIO make 1200 or its equivalent make of orient /crompron/Havels
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
OD118874/2025-2026:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. 1 x 2.5 sq. mm
OD118875/2025-2026:Supply and fixing of 3 mm thick Hylem sheet on the existing metal/PVC box using suitable size steel screws
OD118876/2025-2026:Supply and fixing circular PVC lid with screw suitable for 20/25 mm PVC junction boxes.
OD118877/2025-2026:Supply and fixing circular PVC lid with screw suitable for deep fan clamp boxes.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
1.22.2:Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.100 mm X 100 mm X 60 mm deep
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
OD114982/2025-2026:Supply and fixing 20mm corrugated flexible pvc conduit.
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.14:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.1.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 10 sq mm
90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
OD50816/2025-2026:Supply and Installation of dust and vermin proof , wall mounting , Sintex 3 Phase meter box of size 650x350x250 mm suitable for fixing KSEB meter ,fuse units etc, hinged door connection for the front side with compartments if necessary , providing vision panel for the meter component , knock out for cable entry and exit.( GSMB-6535 )
OD50815/2025-2026:Supply and fixing 63 A 2 way neutral link mounted on DMC/SMC base and giving connections in the existing meter board/panel.
OD50819/2025-2026:Supply and fixing 63 A backelite fuse base with HRC fuse link in the existing meter board and giving connections etc
OD50817/2025-2026:Supply and providing iron hook for binding service wire
OD118917/2025-2026:Supply, conveyance, installation, testing and commissioning of 2.5/ 3KVA 24V DC INTERNAL ISOLATION MODEL 1PHASE IN AND 1PHASE OUT SINE WAVE OUT HOME UPS SYSTEM. ( EXIDE /MICROTECH/EQUALENT MAKE ) along with battery bank .. The UPS shall be housed in a free standing enclosure, and free from defects, sharp edges, nicks, scratches, burs etc. and provisions for suitable ventilation, easy maintenance, etc. The supplier should submitting Tested documents, Operation manual, service manual, etc. while the UPS is supplied and 2 Nos of ISI marked suitably rated External AMARON /Exide/its equivalent make Make 12V, 150AH, C 10 TUBULAR Battery 2 NUMBERS FOR THE BACKUP 90-120 MINUTES IN PRESENT LOAD with lead and terminals, metal rack with enclosure and DC breaker switch etc as required Warranty and Periodical service 36 Months for UPS and Tubular Battery ..
OD118983/2025-2026:Supply Installation Testing and Commissioning of 8 Ltr Capacity Water purifier RO+UF+TDS control, UV LED tank, 20LPH flow and the unit shall be conveyance to the site ,installed , testing and commissioning in the convenient location suggested by engineer in charge with using suitable accessories like Water Purifier, Accessory (Input pipe, Reject water pipe, Diverter valve) Warranty Card etc .- KENT or its equivalent make.
OD118678/2025-2026:Painting letters or figures of the 2.50 cm, 4 cm or 5 cm height sizes with enamel paint as identification mark to SB, DB, panel board etc as required<br
OD118679/2025-2026:ABC TYPE FIRE EXTINGUISHER :- Supply &Fixing of ABC type Fire Extinguisher 5 Kg capacity consisting of welded M.S cylindrical body, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube, 30 cm long high pressure discharge hose, nozzle etc. fixed on the wall using suitable screw and metal fastener etc as required .
Angel electricals (BID ID -2281578)
Bidder Name
RAMESH KARUNAKARAN
Angel electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1284332.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .