The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under 66 KV Vesu-1 Sub Station MAGDALLA sub division as well as all Sub-Division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
320418
DGVCLDPPL/0683/06/2026 Approved Date: 25-06-2026
Open
Electrical
Surat
1 document required · 1 mandatory
₹1,180
SURAT DGVCL
₹30,000
3 Jul 2026
3 Jul 2026
3 Jul 2026
20 Jul 2026
3 Jul 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable
end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under 66 kv Vesu-1 substation of MAGDALLA sub
division as well as in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm width x 1200mm Meter
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half
trench length is to be considered)
2 9925000002 Labour charge for excavation of cable trench of 600mm width x 1200mm Meter
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half
trench length is to be considered)
3 9925000003 Labour charge for excavation of cable trench of 400mm width x 1500mm Meter
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half
trench length is to be considered)
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 Meter
& preparation of sand layer 100mm thick, in the cable trench & covering
the cable with 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC
half round muffs and providing and fixing of 4inch width yellow colour
polyethylene tape with printing "CAUTION ELECTRIC CABLE BELOW" at
m depth from ground surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as to protect cable
from mechnical injuries, refilling the same, as per Instruction of Engineer in
5 9925000005 Labour charge for horizontal drilling using Auger machine without damage Meter
to surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-
4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS
4984-1987(3rd revision) and BIS certification and laying of 11KV/22KV XLPE
cable of size up to 300 mm2 in HDPE pipe, as per Site Condition (excluding
cost of pipe). The detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth and distance from
adjacent landmark for each segment for HDD is must required to be
submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per site
conditions and as per instruction of EIC.
6 9925000006 Labour charge for horizontal drilling manually without damage to surface Meter
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color,
110mm O.D., 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up
to 300 mm2 size, as per Site Condition (excluding cost of pipe). The detail
map and excell sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment of cable to be
submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to
mtrs as per site conditions as per instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5 mm thickness Meter
H.D.P.E. pipe confirms to IS 4984 and BIS certification for laying of
underground 11KV / 22KV XLPE cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of CMT
damage portion of road crossing for the work carried out for roads crossing
as well as concreting & muffing of ploes including all materials (1:2:4)
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 mm No
thick x 650 mm height embedded in earth at least 300 mm below &
mm above ground level respectively at distance approx 50 meters along the
length of cable. The RCC concreting (1:2:4)(all necessary maeterials will be
in bidder's scope) of route marker is to be carried out 300 mm width x
mm thick x 300 mm below ground level as per instruction of EIC. The
route marker should be with name of company with approved yellow
colour-DGVCL. The distance from marker to cable and cable depth with
feeder name etc., marked with arrow sign is to be painted on it.The route
marker is to be fixed at location near to any fixed permanent location (not
necessary to fix exact on top of cable) as per instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 300 mm2 Per Job
on DP Structure with fixing of 02 Nos polymer cleats on top and middle
part . Polymer cleats, nut bolts etc. fixing material to be provided by
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5mm Per Job
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification on the
erected DP structure for the mechanical protection of cable by inserting the
cable inside HDPE pipe. The HDPE pipe shall be erected in such a way that
300mm shall be below the ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No Polymer cleat. All materials
including polymer cleat and Nut bolt to be provided by contractor.
12 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe No
with pit to be filled with salt & coke and construction of chamber as per
DGVCL Drg. No. dg /100 for DP and cable. The earthing pit should be joined
with cable by G.I. strip of size 1” width & 2 mm thick. All material GI pipe,
Coke, Salt etc will be supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for upto No
11kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 No
kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
15 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 No
kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
17 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x No
185 mm2 size XLPE cableas per DGVCL technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto 22kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm No
deep joint pits for installation of 11kV/22kV Straight through joints as per
instruction of engineer-in-charge & covering the cable with 150 mm dia
(Outer), thickness 25 mm, 1.0 meter long RCC half round muffs & refilling
same as per instruction of EIC .
20 9925000024 Providing and fixing of insulating bus bar , made from 11KV/22KV XLPE No
cable after removal of semi conducting layer and applying of PVC heat
shrinkable anti-tracking core insulating tubing (1.1KV), on both end terminal
using Aluminium long barrel heavy duty up to 240 sq mm lugs, Aluminium
bus connector. Taping with PG- clamp for bus conductor as per drawing
and as per instruction of EIC. The Alluminium lugs and PG clamp shall be
covered with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will be
in scope of DGVCL while all other materials will be in bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the feeder as per No
instruction of engineer-in-charge. Test result shall be submitted by
contractor with bill.
22 9925000026 Preparation and submission of 6 (six) copies, of complete layout drawings Set
with GIS mapping as per actual cable routing showing road crossing, HDPE
pipe sleeving, jointing locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm No
aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre
treated with phosphate process and acid etching coated with one coat of
epoxy primer and two coats of best quality paints, refloctrorised with Hi-
Intensity retro – reflective sheeting as per the latest and frame fabricated
from suitable size iron angle. The Sign Board is to be fixed on the base
prepared from channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500
mm to be grouted in ground). The details to be displayed on sign board will
be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
24 9925000028 Providing and fixing of Sign Board (Danger Board) on Distribution No
Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design,
pre treated with phosphate process and acid etching coated with one coat
of epoxy primer and two coats of best quality paints, refloctrorised with Hi-
Intensity retro-reflective sheeting as per the latest and frame fabricated
from suitable size iron angle. The Sign Board (Danger Board is to be fixed at
the location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 No
mm aluminium sheet along with 1.0 mm dia aluminium binding wire for
fixing of aluminium tag near end termination joint at DP structure for
identifyng the cable. The details of feeder i.e. 11 / 22 KV with feeder name
shound be punched on the tag by letter punch of size 16 mm as per
instruction of In-charge Engineer.
26 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C Nos
x 240 mm2 size XLPE cable as per DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV Nos
3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C Nos
x 240 mm2 size XLPE cable as per DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 Nos
mm2 size XLPE cableas per DGVCL technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
32 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in per
open space cable
33 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half mtr
35 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
36 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable NO.
connection arrangement along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles)
37 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
39 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable NO.
connection arrangement along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles)
40 Laying (including installation, testing and commissioning) of various size of mtr 335 as per rate derived by UGVCL letter
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable no ugvcl/r&c/ug/Cost Data-2022-
in ground 1200 mm deep and 300 mm wide trench, providing sand 23/816 Date:-27-01-2023
cushioning below (75 mm thick layer of sand) and above (75 mm thick layer
of sand) of the cable and covering it with RCC half round hume pipe (150
diameter with thickness of 30 mm and One meter in length) before refilling
pre-bonding tap/warning tap should provide below 700 mm from the
ground level and back filling the same to make ground level as per original.
As per specification and drawing of DGVCL. ( RCC half round pipe should be
provide throughout on cable without gap).
41 Laying (including installation, testing and commissioning) of various size of mtr 468 as per rate derived by UGVCL letter
Double circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable no ugvcl/r&c/ug/Cost Data-2022-
in ground 1200 mm deep and 500 mm wide trench, providing sand 23/816 Date:-27-01-2023
cushioning below (75 mm thick layer of sand) and above (75 mm thick layer
of sand) of the cable and covering it with RCC half round hume pipe (150
mm inner diameter with thickness of 30 mm and One meter in length)
before refilling pre-bonding tap/warning tap should provide below 700 mm
from the ground level and back filling the same to make ground level as per
original. As per specification and drawing of DGVCL. ( RCC half round pipe
should be provide throughout on cable without gap).
42 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x No 5549 as per rate derived by UGVCL letter
300 mm2 size XLPE cable as per technical specification. no ugvcl/r&c/ug/Cost Data-2022-
43 Supply & fixing of heat shrink type end terminations (outdoor) for upto No 6676 as per rate derived by UGVCL letter
11kV 3C x 300 mm2 size XLPE cable as per technical specification. no ugvcl/r&c/ug/Cost Data-2022-
44 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 300 No 8040 as per rate derived by UGVCL letter
mm2 size XLPE cableas per L technical specification. no ugvcl/r&c/ug/Cost Data-2022-
Rate as per SOR 30,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,