Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹19.3 LAccepted-AOC 46C 1P PONGHAT PUL DEFENCE INCLAVE COLONY BAMRAULI PRAYAGRAJ UTTAR PRADESH 211012 | PRAYAGRAJ | UTTAR PRADESH | 211012 | L-1 | Accepted-AOC Lowest Rates | |
| 2 | L-2₹21.7 L+₹2.4 L (12.4%)Rejected-Finance V P O MANPURA TEHSIL BADDI DISTT SOLAN H P | SOLAN | HIMACHAL PRADESH | 171102 | L-2 | Rejected-Finance High Rates | |
| 3 | L-3₹23.9 L+₹4.6 L (23.8%)Rejected-Finance DIC 138 INDUSTRIAL AREA BADDI DISTT SOLAN H P 173205 | BADDI | SOLAN | HIMACHAL PRADESH | 173205 | L-3 | Rejected-Finance High Rates |
Tender Value
₹22.2 L
EMD Value
₹55,590
Closing Date
15 Sept 2021, 11:00 amClosed
SE OP HPSEBL Bilaspur
SE OP HPSEBL Bilaspur
Tender for the work Survey, Design, Manufacturing, Supply of Material, Erection, Testing and Commissioning of 11 KV CT-PT Combined Unit Out door Type, 11/.4 KV 250 KVA Sub-Station and 11 KV H.T. Line for prov. S.O.P. on 11 KV for improvement and remo
2021_HPSEB_51689_1
NIT-07/2021-22
Open Tender
Electrical Works
Item Rate
90 days
Bilaspur
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,950
₹55,590
11 Nov 2021
26 Aug 2021
16 Sept 2021
27 Aug 2021
15 Sept 2021
27 Aug 2021
Amount
11 KV CT-PT Combined Unit Out door Type (Metering Equipment)
Prov. 11 KV CT-PT combined unit outdoor,Oil Immersed, Class.5 Consisting of three CT on R,Y & B and 1 No. 11KV/110V PT. Accuracy Class 0 .5S - (10-400/5A) - 15/5 Amps (To be supplied by HPSEBL)
Prov. Energy Meter 3Ø, 3/4 wire CT-PT Operated Static Tri-Vector Meter. (PT ratio-/110V, CT ratio-/5A), Accuracy Class:0.5S, Category-B, DLMS Compliant with RS 232 & RS 485 port. (To be supplied by HPSEBL)
Prov. STP Pole 9.00 mtr W/L 200 KG with base plate
Prov. Muff with Cement Concrete filling
Prov. C.I. X-Arm (100X50X6 mm), Length : 2800 mm X 4 Nos. = 11200 mm Say 11.20 Mtr. for Transformer/ CT-PT base main channel
Prov. M S C.I. (75X40 X 6 mm), Length : 2800 mm X 4 Nos = 11200 mm=11.20 Mtr for supporting DO fuse unit & G.O. Switch
Prov. C.I (100X50 X 6 mm), Length : 460 mm X 2 Nos. = 920 mm = 0.920 Mtrs. for supporting Main Channel of transformer/ CT-PT
Prov. M S A.I X Arm (50X50 X 5 mm) Length 2800 mm x( 1 No. for LA's + 2 Nos. for Distribution Box / Metering Equipment = 2800 X 3 nos.= 8400 mm= 8.40 Mtr.
Prov. CT-PT Belting & Knee Bracing
I) M S A.I (50X50x 5 mm), Length: 2800 mm X 4 Nos.= 11200 mm = 11.20 Mtr
II) M S A.I (35X35X 5 mm) Length: 460 mm X 2 Nos.= 920 mm = 0.920 Mtr.
Prov. G.O. AB Switch Unit ( 11kV, 400A 25 KA )
Prov. D.O.Fuse Unit
Prov Lightning Arrestor (Surge Arrester, 9kV Station Class Porcelain Type )
Prov. Discs Insulator sets (Comprising 1 No. Disc: ^^ (Porcilain, BS, 12 kV 90 kN) i/c Dead End Clamps etc.)
Prov. Stay Set complete
Prov. Stay Wire 7/4.00 mm ( @6.00 / 9.0 kg Per Stay Set)
Prov. Pipe Earthing set (With G.I. Strips 50x6mm,40x6mmx 25x6mm)
Prov. AAA Cond. 7/3.81 mm (80 mm2)
Prov. Half Clamp with Nuts & Bolts (M.S. Flat Iron 50X6 mm)
Prov. Full Clamp with Nuts & Bolts ( M.S. Flat Iron 50X6 mm )
Prov. Nuts and Bolts of Various Sizes Galvanised / Coated) (Prefeably 16 mm ɸ or more with flat and Spring Washers)
Prov. Alluminium Thimble
Prov. Alluminium Thimble
Prov. Danger Plate
Prov. Aluminium Paint
Prov. PVC 4 mm sq copper wire
Prov. G.I. Pipe 1 1/4" dia
Prov. Elbow
Prov Nipple
Prov.G.I.Gland
Prov. Meter Box
2x 11/.4 KV 250 KVA Sub-Station for Booster & Stage-Ist
Prov. 11/0.4 kV 250 KVA Distribution Transformer
Prov. M.S.C.I. X-Arm (100x50x5 mm),Length 2800 mm X 2 Nos.
Transformer Belting & Knee Bracing
Prov. LT Distribution Panel Box with MCCB (400A, 36kA, 4P, 1No.) and SFU (100A, 4 No., rewirable)
Prov. Half Clamp with Nuts & Bolts (M.S. Flat 50X6 mm)
Prov. M.S. Nuts and Bolts of various sizes (galvanised/ Coated) (Preferably 16 mm ɸ or more (With Flat & Spring Washers))
Prov. Aluminium. Thimble
Prov. Aluminium. Thimble
Prov. Danger Plate
Prov. LT Cable (3.5 Core) 240 mm2 (To be supplied by HPSEBL)
Prov. LT Cable (3.5 Core) 185 mm3 (To be supplied by HPSEBL)
Prov. Energy Meter LT, 3-Phase, 4 Wire CT OperatedStatic Trivector Meter ( CT-300-400/5A) Accuracy Class: 0.5S, Category-C, DLMS Compliant.
11 KV H.T. Line for Booster & Stage-Ist
Prov. Steel Tubular Pole 11.00 mtr Working Load >227KG with base plate
Prov. RCC Muff with Concrete Filling 2000mm length.
Prov. AAA Cond.7/3.15 mm ( 50 mm2)
Prov. G.I.No. 6/ 8 SWG for Earth wire for PCC & S/T Pole (To be supplied by HPSEBL)
Prov. 11 KV Pin Insulator with Pin Hellically formed fitting (Porcelain, 12kV, 10kN)
Prov. 11 KV Disc Insulator Set Cleaves & Toungue Hellically formed fitting (Porcelain, BS, 12kV, 90kN)
Prov. C.I.X-arm (100x50x6mm), Length(1500) for S. Pole Str.= 1500 x26= 39000 mm= 39.00 Mtr
Prov. C.I.X-arm (100x50x6mm), Length(2400) for S. Pole Str.= 2400x10= 24000 mm= 24.0 Mtr
Prov. C.I. X-arm(100x50x6mm),Length: 2800x2= 5600 mm= 5.60 Mtr for D.Pole Str.
Prov. C.I. X-arm(75x40x6mm),Length: 2800x3= 8400 mm= 8.40 Mtr for D.Pole Str.
Prov. A.I.X-arm(50x50x6mm), Length : 1800x16= 28800 mm= 28.80 Mtrs.for Gaurding
Prov. A.I.X-arm(50x50x6mm), Length : 2700x5= 13500 mm = 13.50 Mtrs.for Gaurding
Prov. A.I.X-arm(50x50x6mm), Length : 3000x2=6000mm =6.00 Mtrs.for Gaurding
Prov. A.I Knee Bracing set (50x50x6mm), Length (2x750) for Single Pole=750x2x16=24000 mm= 24.00 Mtr.
Prov. Belt Set (X-Bracing Set)M. S. Angle Iron (50x50x6mm) Length:1500x2x6=18000 mm =18.0 Mtrs.
Prov. Belt Set (X-Bracing Set)M S A. Iron(50x50x6mm) Length: 2700x2x2=32400 mm = 32.40 Mtrs.
Prov. Stay Set Complete in all respect i/c Guy Assembly with Helically Fitting
Prov. Stay Wire 7/3.15 mm/ 7.400 mm ( @ 6.0 KG /9.00 Kg per Stay Set)
Prov. H.T. Earthing for PCC /S/T Pole
Prov. Full Clamp with nuts & bolts M.S. Flat 50x6 mm (23+14 for Stay)
Prov. Half Clamp with nuts & bolts M.S. Flat 50x6 mm
Prov. Pole Top Clamp with nusts & bolts M.S .Flat 50x6 mm
Prov. Earth Hook for Earth Wire
Prov. Danger Plate (250x200x1.6 mm)
Prov. Nuts & Bolts Of various sizes ( Gaivanised/ Coated) ( Preferably 16 mmɸ or more with flat and spring washers)
Prov. Barbed Wire
Prov. Alluminium Paint
Prov. 11 KV G.O. AB Switch Unit (11 KV, 400A, 25 KA
Prov. 11 KV Fault Path Indicator
Extra manual carriage charges for 1.00 Km.from Road head to Site of Work. Average lead - 0.5 Km for 1.792 Km HT Line= 0.5 X 1.792= P/Kms
Bed/Plinth for 11/.4 KV, 250 KVA Sub-Station for Booster & Stage-Ist
Excavation in foundation,trenches etc.in earth work, lift upto 1.50 metres stacking the excavated soil not more than 3 meters clear from the edge of the excavation and then returning the stacked soil in 15 cm.layers, when required in to plinth sides of foundations etc. and then disposing of all surplus excavated earth as directed with in a lead of 20 mtrs. (PW/JW ). 50% each
Providing and laying Cement concrete 1:6:12 (1Cement:6 Sand: 12 graded stone aggregate 40mm nominal size) and curing complete excluding cost of centring and shuttering in: foundation and plinth
Providing and laying Cement concrete 1:2:4 (1Cement:2 Sand:4graded stone aggregate 20mm nominal size)and curing complete excluding cost of form work foundation and plinth
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm so as to give fair finish i/c centring,shuttering, strutting and propping etc. with wooden battens and ballies, height of propping and centring below supporting floor to ceiling not exceeding 4 mtrs etc.In (i) vertical surface such as walls (any thickness) partitions and the like.
Chain link Fencing around the 11 KV CT-PT Combined Unit Out door Type (Metering Equipment) & 11/.4 KV, 250 KVA Distribution Transformer for Booster & Stage-Ist
Excavation in foundation,trenches etc.in earth work, lift upto 1.50 metres stacking the excavated soil not more than 3 meters clear from the edge of the excavation and then returning the stacked soil in 15 cm.layers, when required in to plinth sides of foundations etc. and then disposing of all surplus excavated earth as directed with in a lead of 20 mtrs. (PW/JW ) 50% each
Providing and laying Cement concrete 1:2:4(1Cement:2 Sand:4graded stone aggregate 20mm nominal size)and curing complete excluding cost of form work foundation and plinth
Steel work in single section i/c cutting, hoisting, fixing in position and applying a priming coat of red paint in R.S. joists, channels, angles etc.
Supply and fixing wovenplane G I wire fencing of mesh 50mm to 150mm to any type of standard rails, straining bolts.etc. including provision of binding wire staples etc.
P/F M.S pressed butt hinges with necessary screws -75 x 47 x 1.70mm
Providing & fixing oxidized M.S. sliding door bolt with bolts and nuts, screws etc. complete (Size 250x16mm)
M/S AMAN ELECTRICAL AND ENGG WORKS
NATIONAL ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .