Supply, Installation, Testing and commissioning of 2000 KVA transformer, VCB Panel with accessories and allied Electro-Mechanical work at Rundh (Bhalod) water supply pumping station Jhagadia.
278820
TENDER NOTICE NO: 9/2025-26 SR. NO - 04
Open
Electrical - All
Works
Bharuch
11 documents required · 11 mandatory
₹2,400
Chief Officer, Notified Area, Jhagadia
₹82,350
20 Feb 2026
20 Feb 2026
20 Feb 2026
5 Mar 2026
20 Feb 2026
Name of work: -Supply, Installation, Testing and commissioning of 2000 KVA transformer,
VCB Panel with accessories and allied Electro-Mechanical work at Rundh
(Bhalod) water supply pumping station Jhagadia
Item Description Qty Unit Amount
Providing, and erecting 11 KV D.P. 9 mtr.
High Structure made of 6" x 3" ‘I’-Section
Girder, 4" x 2"channels, clamps, nuts, bolts
etc. Suitable for erection of the followings
duly connected with necessary ACSR
conductors. As per drawing approved by the
Engineer- in charge complete with following.
Height as per IS 7 Mtr. above ground ) (A)
KV 200 Amps Drop out fuses with S.R.B.P.
1 tubes carries.-Three nos (B) 11 KV G.O.D. 1.00 Set 97459.00
switch complete with insulators, operating
handle with galvanised pipe, Sq .bar etc.
Amp.- One Set, (C) 11 KV lightening arrestor
with clamp- Three Nos. (D) 11 KV shackle
insulators- Six Nos. (E) The above D.P.
structure should be earthed with 25 mm. X
mm thick double copper earth strips run
separately and connected with separate
copper plate earth electrode.
Supply, installation, testing & commissioning
both side extensible, Indoor type HV
Switchgear panel confirming to IS-3427, IS-
2516 (Part I & II.sec.1 ) & IEC-60056 & IEC-
62271-100/200 for use on 3phase, 50 Hz,
unearthed AC supply system and having
breaking/ rupturing capacity of 500 MVA
(26.3 kA for 3sec) complete with spring
charged mechanism, ON-OFF mechanical
push button, operation counters, Breaker
TNC switch, Breaker L/R switch, necessary
auxiliary switches, closing coil, shunt trip,
protection relays & Indicators etc. complete.
The panel shall comprise of air insulated
busbars provided with heat shrinkable PVC
sleeves. The VCB trolley shall comprise of
three vacuum interrupters with epoxy
support insulators and self aligning finger
type isolating contacts and necessary
mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable
from front as well as rear end. The breaker
shall be Manual cum motorised mechanism
with following accessories. a) 96 x 96 mm
square flush mounting type Ammeter & Volt
meter with selector switches. b) Multi-
function meter. c) Double core, cast resin type
current transformer having ratio as per
requirement, one core for metering & one
core for protection having required class of
accuracy. d) Instantaneous under voltage
relay & Temperature rise tripping Relay, e)
Triple pole IDMTL two over current and one
earth fault relay with current setting range
50-200% and 10-40%f) Electrical closing.
Coil & shunt trip coil operating on 110 V DC.
g) Auxiliary relay for anti-pumping device. h)
Three limb, draw out type, feeder connected,
cast resin insulated, three phase Potential
transformer having ratio & burden as per
requirement & Class 0.5 accuracy. i)
Annunciator Windows, Common Hooter /
Alarm bell operating on 230 AC/ 110 V DC. j)
Cable boxes suitable to terminate 3 core XLPE
cable of required size (As per design). k)
230V AC to 110 V DC power pack for closing
& tripping circuit common. l) Breaker ON-
OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination
lamps with plug socket.n) Space Heater with
Thermostat. 11 kV HV Switchgear Panel-
Comprising of 800 A Vacuum circuit breaker
for 1 nos. Incomer, 2 nos. O/G feeders for 11 /
0.433 kV stepdown transformers.
Supply, laying, testing & commissioning of
kV (UE) grade, XLPE insulated, stranded
Aluminium conductor, galvanised steel flat
strip / round wire armoured, extruded PVC
type ST2 sheathed, heavy duty cable (to be
3 laid on wall surface with necessary clamps / 50 Mtr 3162.00
in existing cable trench / cable trays / conduit
/ pipe sleeves at road crossing or floor as per
site requirement) conforming to IS:
(Part- 2) & IEC: 60502 (Part-2) of following
sizes : 3 Core x 300 Sqmm
Providing & fitting heat shrink cable
termination / jointing kits for 11 kV (E)
grade XLPE insulated cable including
necessary earth connectivity connection,
4 material & consumables making the
termination/ joint complete ensuring the
joint resistance is within the permissible limit
as per IS, of following types & sizes: 3 Core x
a Indoor Type 4 Nos 20000.00
b Outdoor Type 1 Nos 25000.00
Casting of transformer plinth / foundation
including oil soak pit (where required) in situ
reinforced cement concrete in M 20 using
granite, quartzite trap metal of size 6 mm to
20 mm for RCC work including providing of
53 grade cement & Fe 415 grade TMT bars,
scaffolding, centering, form work, curing etc.
complete. RCC plinth / foundation for
distribution transformer of capacity
SITC of outdoor type, three phase, oil
immersed, distribution transformer of
required KVA & voltage ratio, copper double
wound, vector group - Dyn11, HV delta
connected & LV star connected with neutral
brought out connected to provide separate
earthing terminals, bushing / cable box on HV
side and cable box on LV side suitable for
cables or bus duct as per requirement with
standard fittings, conforming to IS:
(Part-1) / 2014 with its latest amendment
including first fill of transformer oil &
following accessories. (a) Oil conservator
with filling holes with cap and prismatic oil
level gauge. (b) Silica Gel dehydrating
breather charged with silica gel (c) Oil drain
cum sampling valve with plug (d) Oil filter
valve (e) Lifting Eyes / Hooks / Lugs (f) Two
earthing terminal (g) Diagram and rating
plate (h) Air release plug (i) Explosion vent
with diaphragm (j) Thermometer pocket (k)
Four bi-directional plain roller with base
channel with hauling holes (l) Fixed /
Separate type radiator banks, (m) Off circuit
externally operated tapping switch (For
rating < 1000 kVA) (n) 100 mm stem type oil
temperature indicator (For rating < 500 kVA)
(o) Bucholtz relay with shut off valve (For
rating ≥ 500 KVA) (p) 150 mm dial type oil
temperature indicator with Alarm / Trip
contact (For rating ≥ 500 kVA) (q) 150 mm
dial type winding temperature indicator with
Alarm / Tip contact (For rating ≥ 1000 kVA)
(r) Marshalling box (For rating ≥ 500 kVA) (s)
150 mm dia. magnetic type oil gauge (For
rating ≥ 1600 kVA) (t) Inspection cover &
Jacking lugs (For rating ≥ 1600 kVA) For
transformer having oil storage capacity for
2000 litres and higher, nitrogen injection fire
protection system (NIFPS) is to be provided.
With on load tap changer +10% to -10% in
steps of 1.25% with RTCC & AVR -
KVA (Eff. Level-3), 11KV/0.433kV,
Phase, 50Hz, Dyn-11
Supply, Installation, Testing & Commissioning
of Busduct system including all necessary
accessories i.e., End Feed Unit, Flange End,
Straight lenghts, Horizonatal & Vertical
Bends, Vertical spring Hanger, Fix Hanger,
Tinned copper braided Flexibles, Empty
adapter box, Aluminium extention link, Phase
cross over, Flexible copper busbar, Empty
adapter box etc. as per drawing, requirement,
specification and as per the instruction of
engineer-in-charge. The unit rate shall
include unloading from vendor vehicle to site
store and shifting from site store to the place
of installation including loading / unloading
within necessary supports on wall,
assembling of loose accessories supplied by
the manufacturer and supply of all necessary
hardware. Aligning, levelling, grouting and
testing of all hardware. Rate of support
requirement for Busbar trunking should not
be considered in unit rate. Note: GA drawing
to be approved from Client and Consultants
prior to start fabrication for all accessories of
BBT from Panel to End Cap. Contractor shall
take exact measurement of Busduct Before
manufacturing / fabrication. Busduct shall be
installed at 4 mtr. Height from finished floor
level. SITC of 3200A, 50kA, Aluminium
Sandwich Busduct Straight Length of BBT
system of 415V, IP54, Insulation Class-F,
3Phase + 100% Neutral + Internal Earthbus
50%, Sandwich type, Aluminium conductor in
Powder coated GI housing. (Measurement as
per actual site conditions)
Supply, Installation, Testing and
Commissioning 1 Nos 3200 A 4P EDO 65 KA
ACB LSIG, 3200A 4P EDO 65KA ACB LSIG
with Microprocessor release (O / C, S / C & E
/ F) having breaking capacity Icu of 65 kA at
415V with 6NO+6NC potential feee auxiliary
contacts, secondary Isolating contacts with all
8 necessary Electro Mechanical protections & 1 Lot 550000.00
interlocks etc. job also including busbar
modification and hook-up with existing DG
AMF System, remove existing ACB and SITC in
place of 3200 Amp New 4 P ACB with all
required labour and machinery etc.
completed as per direction and as
modification required on existing PCC Panel.
Supply, laying, testing and commissioning of
A2XFY Cable having Aluminium Conductor,
XLPE insulated PVC inner sheathed and FRLS
9.0 PVC outer sheath of 1100 volts grade suitable
for 1100V class confirming to IS. Complete as
per Technical specification, Data Sheet,
Drawing & directed by employer / employee
19C x 2.5 sq.mm FRLS A2XFY Cable (OLTC to
12C x 2.5 sq.mm FRLS A2XFY Cable
(Marshalling Box to RMU)
4C x 2.5 sq.mm FRLS A2XFY Cable (OLTC to
2C x 2.5 sq.mm FRLS A2XFY Cable (RTCC to
Providing and fitting of Cable Gland and
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
10 following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
19C x 2.5 sq.mm FRLS A2XFY Cable (OLTC to
12C x 2.5 sq.mm FRLS A2XFY Cable
(Marshalling Box to RMU)
4C x 2.5 sq.mm FRLS A2XFY Cable (OLTC to
2C x 2.5 sq.mm FRLS A2XFY Cable (RTCC to
Providing, installing & commissioning &
getting Plan Approval as well as NOC from
Electrical Inspector for draw out type 11 KV
outdoor/indoor extensible type totally
enclosed, single busher floor mounting metal
clad 400A. vacuum tube circuit breaker
confirming to IS: 2516 (Part- I &11, Sec.1) ‘for
use on 11 KV, 3 phase, 50 c/s. unearthed A.C.
supply system having breaking / rupturing
capacity of 350 MVA complete with spring
operated mechanism, mechanically ON-OFF
and spring mechanism charged, discharged
indicators, ON-OFF mechanical push button,
operation counters necessary auxiliary
switches, closing shunt trip, air insulated
busbar chamber having heat shrinkable PVC
sleeves, mechanical interlocks safety shutters,
isolating plugs and a VCB trolley with three
vacuum interrupters with epoxy support
insulators and self aligning finger type
isolating contacts. The breaker shall be
Manual cum motorised mechanism with
following accessories. 1. HTMC Panel,
KVA Transformer(11KV/0.433 V) - 1 Nos,
VCB Panel - 1 Nos, Outdoor Type VCB, PCC
Panel, MCC Panel all accessories as per
Installation required. Cable boxes suitable up
to 22 KV 3core 185 sq.mm XLPE cable.
230V. A.C. to 110V. D.C. power pack for
closing & tripping circuit common.. (for each
VCB) 12.Breaker ON-OFF, Auto trip and
spring charged indicators, Phase indicating &
panel illumination lamps with plug socket
14.Numerical Communicable type non
directional O/C & E/F Relay with a setting of
5-250% both in O/C & E/F. complete with
necessary interconnection with air insulated
high grade copper busbar {Breaker Testing
scope include Closing Time, Opening Time,
VCB Hi-Pot test at Site}{ Relay Testing Scope
Include testing of all protection by three
phase testing kit at site }(VCB Trolley is to be
provided) Charges for Liasoning-Load
Increasing for existing connection and in
other connection load extention -Drawing
approval-CEIG Approval
Providing and erecting required size HOT
deep Galvanised iron strip for earthing of H.T.
12 , OCB/ ACB/ Transformer LT panel board, 300 Kg 77.00
Motors etc. using proper clamp. Size - 50 mm
Providing and erecting required size Copper
strip for earthing of H.T. OCB / ACB/
13 Transformer, LT panel board, Motors etc. 200 Kg 787.00
using copper clamp. Size - 50 mm x 6 mm,
Supplying & erecting earth pit of minimum
bore dia.150mm size approved make
Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of
corrosion free hot dipped G.I.Pipes having
Outer pipe dia of 50mm having 80-200
Micron galvanising, Inner pipe dia of 25 mm
having 200-250 Micron galvanising,
connection terminal dia of 12mm with
constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications with chamber and heavy duty
cover.(approved make OEM has to submit
14 test certificate) & having back filling 6 Nos 10489.00
compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 W/ meter
testing as per IEC 62561-2017, Voltage drop:-
< 1 volt at no load & dry form, Sulphur
content:- <2%(C) Back fill Compound :-
Earthing compound should be capable to
retain moisture for long time Necessary test
report must be submitted. (c) For Electrical
Installation covering Transformer Neutrals,
Lightning arrester Earthing, A.C.Plant &
Sensitive Computer System(like Automation,
SCADA) i.e independent Earthing in normal
soil. Length of Pipe : 3.00 mtrs, Back filling
Compound :2 nos Bags of 25 Kg.
Do as above I. No. 16 but Copper Bonded Rod
15 manufactured with Conductive BFC 2 Nos 11615.00
compound with readymade chamber and
Providing and Fixing MS section works, Such
as Joint, Channels, Angles, BOX Pipe, Flats,
Iron rails etc. complete with labour for
lowering, laying, erecting, fixing, of various
16 size of MS Section. Job including to provide 500 Kg 150.00
labour with all tools and tackles as required
for Site. Painting of MS Structure with two
coat red oxide and one coat oil paint as
directed by engineer in charge.
Dismantling, Remove, Loading, Shifting, of
existing Transformer , VCB panel , ACB & Bus
duct , Two pole structure etc with required
labour, tools, machinery from Rundh water
17 works as per instruction of engineer In- 1 Job 300000.00
charge. Job also including to loading,
unloading and transportation of all
equipment from existing pump house to go
dawn within 30 KM lead.
Total of Part-A
Buyback old Transformer - 1Nos, VCB Panel
Set, 1-Nos ACB, and Busduct-1Nos as on
condition, job also including loading, 1 Set 774236.00
unloading and transportation including in
Total of Part-B
Total Rs. Part-A - Part-B
I / We agree to carry out the above work at ____________ % above the estimated rate
Estimated Tender Rate.
I / We agree to carry out the above work at ____________ % below the estimated rate
Estimated Tender Rate.
Estimated Amount Estimated Amount
Put to Tender Rs.82,34,720.00 Put to Tender Rs.82,34,720.00
Add % Above Rs.______________ Deduct % Below Rs. ______________
Net Amount Rs.______________ Net Amount Rs.______________
Net In Figure Rs. _____________ Net in Figure Rs. ______________
I / We have read the Condition mentioned in this tender and agree to abide by the
Signature of Contractor with Seal Chief Officer
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Sr no 4 Transformer Rundh.pdf
BOQ Sr no 4 Transformer Rundh.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .