Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.8 CrAccepted-AOC | ₹6.8 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹7.4 Cr+₹58.4 L (8.63%)Rejected-Finance | ₹7.4 Cr+₹58.4 L (8.63%) | L2 | Rejected-Finance Not being L1 |
| 3 | Rejected-Technical INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | - | - | Rejected-Technical Not meets the required Criteria |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not meets the required Criteria |
Tender Value
Refer Docs
EMD Value
₹7.3 L
Closing Date
6 Jan 2021, 6:00 pmClosed
CHIEF ENGINEER
CHIEF ENGINEER (NW) KATARIBAGH, NAVAL BASE-PO KOCHI-682 004
PROVISION OF DEFICIENT SINGLE LIVING ACCOMMODATION FOR JUNIOR SAILORS AT INS VALSURA JAMNAGAR
2020_MES_348752_2
890955
Open Tender
Civil Works
Lump-sum
545 days
JAMNAGAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
GE(I)(NAVY) JAMNAGAR
₹7.3 L
Yes
27 Feb 2021
9 Dec 2020
9 Jan 2021
9 Dec 2020
6 Jan 2021
23 Dec 2020
9 Dec 2020 - 16 Dec 2020
Amount
Total amount of Sch 'A' part-I (Buildings )
Total amount of Sch 'A' part-II (Earth work & Site Clearance)
Total amount of Sch 'A' part-III (Internal Water supply)
Total amount of Sch 'A' part-IV (Internal Electrification)
Total amount of Sch 'A' part-V (External Water supply)
Total amount of Sch 'A' part-VI ((External Electric supply)
Total amount of Sch 'A' part-VII (Road /Path/Culvert)
Total amount of Sch 'A' part-VIII (Sewage disposal)
Total amount of Sch 'A' part-IX (Area Drainage)
Total amount of Sch 'A' part - X (Compound wall/Fencing/ Gate)
Total amount of Sch 'A' part-XI (Arboriculture)
Total amount of Sch 'A' part-XII (Gazebo ans Stainless steel Benches)
Sch 'A' Part- XIII ( Miscellaneous Items) (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.)
Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sqmm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked with valid CML No. through in and including medium grade PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked (IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories), including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the one light /Ceiling fan/Exhaust fan point controlled by one 5/6 Amps one way switch all as specified and as directed.
All as per item No 14.0 above but one socket outlet three / five pin, 5 Amps independent controlled by one 5/6 Amps one way switch or switch socket combination 5 Amps, 5 pin.
All as per item No 14.0 above but one socket outlet three / five pin, 5 Amps on same board controlled by one 5/6 Amps one way switch or switch socket combination 5 Amps, 5 pin.
All as per item No. 14.0 above but for one light point controlled by 2 Nos, 2 way switches 5/6 Amps.
Internal Electrification:- Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked with valid CML No. in and including medium grade, PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories), including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) , including PVC insulated multi-stranded copper conductor 2.5 Sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent:- ( Note: Switchs, sockes shall be measured separately)
TV socket coaxial, I Module with GI flush box, inner and outer plate complete
LED Batten light fitting with extruded aluminium housing 2 feet long, with all accessories and integrated electronic driver,20W Make:Philips model Smart Bright Cat part No. BN021C LED20S PSU CW GR S2 or its equivalent makes specified in the list of manufacturers.
Ceiling fan 1200mm sweep copper wound service value not less than 4.5 with power consumption 26 to 35 watts with operating ( with out remote control) minimum speed 320 RPM, min air delivery 220 m3/min , with 2 years minimum manufactures warranty, including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multi stranded copper conductor cable of size 0.5 Sq mm from ceiling rose connector to fan.
Modular fan regulator, step type 120W 2 module, 230 Volts AC all as specified and as directed.
Exhaust fan heavy duty 300 mm sweep 230 Volts AC 50 Hz, 1400 rpm, with high efficient heavy duty motor and die cast aluminium rotor mounted on two ball bearings, aero dynamically countered blades, rigid frames with rubber mountings etc for silent operation, including factory fabricated powder coated aluminium louvers, including connecting up from ceiling rose with 3 core flexible copper cable, PVC sheathed of size 1.5 sqmm, complete all as specified and directed at site.
LED Batten light fitting with extruded aluminium housing 4 feet long, with all accessories and integrated electronic driver,20W Make:Philips model Smart Bright Cat part No. BN021C LED20S PSU CW GR S2 or its equivalent makes specified in the list of manufacturers.
Surface down light fitting LED 16 W. Make:Philips model Cirrus Mini Pro 312 mm x 312 mm Cat part No. SM 200C LED 16 S 6500 PSU OD WH or its equivalent makes specified in the list of manufacturers.
LED security light fitting 45 Watts with IP 66 Protection, with 25 MM GI pipe bracket bent to shape and fixed with suitable clamps on wall mounting. Make:Philips model Greenline Smart BRPO22 LED 20 CW MR S1 PSU GR or its equivalent makes specified in the list of manufacturers.
TPN DB 6 way, double door IP 43 protection, 415V with 200A rated busbar, earth termination ISI Marked complete all as specified and as directed
TPN DB 4 way, double door IP 43 protection, 415V with 200A rated busbar, earth termination ISI Marked complete all as specified and as directed
SPN DB 8 way, double door IP 43 protection, with 200A rated busbar, earth termination ISI Marked complete all as specified and as directed
MCB TPN 63 Amps "C" Series all as specified and as directed
MCB TPN 32 Amps, 415 V "C" Series all as specified and as directed.
MCB TP 32 Amps 415V "C" Series all as specified and as directed.
MCB SPN 20 to 32 Amps "B" Series all as specified and as directed
MCB SP 06 to 32 Amps "B" Series all as specified and as directed
Sheet metal enclosure single pole and neutral enclosure with two pin and earth plug and socket complete with MCB single ploe 20 Amps for solar back up supply. Make as mentioned in list of manufacturer all as specified and as directed.
Submain wiring with 4 runs of 6 sqmm(for phases and neutral) multistranded copper conductor PVC FRLS insulated unsheathed with and one run of 6 sqmm multistranded PVC insulated unsheathed copper conductor (as earth continuity conductor) connected to common earth dolly drawn through and incuding concealed PVC conduit 32mm medium grade ISI marked with accessories etc complete all as specified and as directed. Note: Five runs of 6 sqmm wire and one run of PVC concealed conduit shall be measured as one run only
Submain wiring with 2 runs of 4 sqmm (for phases and neutral) multistranded copper conductor PVC FRLS insulated unsheathed with and one run of 4 sqmm multistranded PVC insulated unsheathed copper conductor (as earth continuity conductor) connected to common earth dolly drawn through and incuding concealed PVC conduit 25mm medium grade ISI marked with accessories etc complete all as specified and as directed. Note: Three runs of 4 sqmm wire and one run of PVC concealed conduit shall be measured as one run only
Submain wiring with 2 runs of 4 sqmm(for phases and neutral) multistranded copper conductor PVC FRLS insulated unsheathed with and one run of 4 sqmm multistranded PVC insulated unsheathed copper conductor (as earth continuity conductor) connected to common earth dolly drawn through and incuding surface PVC conduit 25mm medium grade ISI marked with accessories etc complete all as specified and as directed. (For backup of solar heater) Note: Three runs of 4 sqmm wire and one run of PVC concealed conduit shall be measured as one run only
Supply, installation, commissioning of Water cooler fully stainless steel, anti-corrosive, R-134a refrigerant, electric driven single phase having approx storage capacity 80 ltr and cooling capaity 40 ltr per hrs with built in RO + UV complete all as specified and as directed
INTERNAL WATER SUPPLY & HOT WATER SUPPLY :- Over head shower rose 100mm dia round shape single flow ABS body chrome plated wirh grey face plate and Rubi/ cleaning system and shower arm casted120mmlongheavy body round shape for wall mounted shower with wall flange complete of make Jaguar cat part No OHS1989 and SHA-487 or its equivalent make as mentioned in list of manufacturer .
Brass with cromium plated hand shower (health faucet) with 8 mm dia, 1 mtr long flexible tube & wall hook all as per Cat No. ALD 573 of Jaguar or its equivalent make as mentioned in list of manufacturer.
EXTENAL WATER SUPPLY Cutting of existing CI/DI pipe line of 100 mm bore for insertion of 150x150x80 mm Tee in potion including excavation and earth work complete all as specified and as directed.
Construction of brick masonry (with full brick valve) valve chamber size 900x900x900mm (internal dimension) with earth work on any type of soil, PCC M-10 type C-2 as in foundation, brick work in CM 1:4, 15mm thick plaster in CM 1:4 internally and externally flush pointed in same mortar as work proceeds, 75mm thick PCC coping all round (M-15 with 20mm aggregate), flooring shall be 40mm thick PCC M-15 (Nominal mix) laid over 75mm thick hardcore. Top cover shall be made out of MS sheet 3.00mm thick fixed in angl iron frame made out of angle iron size 40x40x6mm with two number of hinges on one side and locking arrangement of other side complete including painting with two coats of synthetic enamel paint over a coat of red oxideprimer etc complete all as specified and as directed.
EXTENAL ELECTRIC SUPPLY Supply, install, testing & commissioning of LT panel out door type 415 Volts 3 phase 4 wire from CPRI approved manufactur made out of 3.0 mm thick CRCA sheet dust and vermin proof cubical type with front and rear operated doors, cable alleys,with necessary hinges consisting of chamber with Aluminium bus of 800 Amps capacity for phase and 400 Amps for neutral and earth with necessary tinned copper strip connections supported by epoxy insulators for incoming and out going duly powder coat painted including locking arrangements having legs 60 cms made out of 45x45x6 mm angle iron grouted on PCC 1:3:6 plateform upto 15 cms including the following complete all as specified and as directed.Note: Before proccurement of panel, contractor shall submit GA Drg for approval by Accepting officer.
MCCB 100 Amp, 4 Pole, 50 Hz, 415 V with rupturing capacity 25 KA to existing panel for tapping connection all as specified and as directed.
Supply and errect 6 mtr height hot dip galvanized steel pole hexagonal / octagonal cross sections grade S355JO of diamensions top dia 70 mm, bottom dia 130 mm, sheet thickness 3 mm, base plate diamensions 200x200x12 mm, foundation bolt size 4 nos x 20 mm dia, pitch circle dia 200 mm, bolt length 600 mm, projected bolt length 100 mm, anchor plate thickness 3 mm with inbuilt compartment for mounting switch box, earthing etc covered with hinged door confirming to IS:2629 / BS EN ISO 1461 including MCB SP 6A-1 No,, MCB TP 32 Amp 10 KA-1 No, Neutral connector - 63 amp cap- 1 No with electrical connections complete all as specified and directed by Engineer-in-charge. Make: Bajaj BOP-6030 or its equivalent make as mentioned in list of manufacturer . (Note : Earth work and PCC foundation shall be measured and paid separately)
Supply, fix, test and commissioning 90 Watt LED street light fittings, High Efficiency IP 66 protection, powder coated pressure die cast aluminium housing and clear injection moulded polycarbonate / toughened glass have multi chip on board LED and metal clad PCB. The minimum lumen output of he system shall be greater than 7200 lumens with minimum lumens per watt 101±3% and must maintain 70% of lumens output at 50000 bhrs, asymmetric fixing to existing bracket including nut bolts, 6 sqmm copper cable 3 turns on one unit tapping from the junction box to light fitting through PVC conduit and applying approved aluminium painting to existing bracket including taking down existing fittings and fixures, including dismantling of existing concrete/ steel poles complete all as specified. Make: Bajaj Cat No. BRTFG 90W LED / Havells Cat No. ENDURACITYLINERNEOSL90WLED757SASYBOTG / Jaquar Cat No. LSRT01S090XC/ Crompton Cat No. LSTN-90-CDL-A / Schreder
3 core, 2.5 sqmm PVC insulated unsheathed multistranded copper conductor cable drawn through suitable 20 mm dia size PVC heavy duty conduit pipe from junction box to fitting complete all as specified.
Cutting of existing road Approx 5.5meter for insrtion of GI pipe of 50/80 mm dia for protection of cable including making good to the distrubed surface by PCC all as directed.
Riddeled soil as earth cushioning to UG cable by using IS sieve to separate the composite particle/ roots etc and refilling/ spread in all trenches as cushioning and rammed down to form a solid bed all as specified and as directed.
XLPE cable insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core. ( From panel to 8 accn and APFC Panel )all as specified and as directed.
Supply, laying, testing XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (Heavy duty) with standed aluminium conductor, 1100 volts grade conforming to IS-1554 Part - I in floor/wall through GI cable stray/pipe of cross-sectional area 50 Sq.mm, 3.5 core complete all as specified and as directed.
Supply, laying, testing XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (Heavy duty) with standed aluminium conductor, 1100 volts grade conforming to IS-1554 Part - I in floor/wall through GI cable stray/pipe and laid in trenches of cross-sectional area 10 Sq.mm, 2 core complete all as specified and as directed.
ARBORICULTURE :- Digging pit of sizes 0.60 m x 0.60 m and 0.60 m deep in any type of soil for plantation of sapling of trees and removal of rubbish and surplus earth not exc 50m and uprooting of all vegetation around 2.0m radius of planted sapling etc complete all as specified and directed.
Sl.item No. 56 Note:-. (i) Bottom halves excavated earth is not used to refill pit. It shall be removed. (ii) sapling shall be measured as supply only under relevent items however labour element for plantation of sapling included in this item (iiI) Cost of Bio farmyard manure ( compost) included in this item.
Polyalthia longifolia Ashoka,Mango,Guava,cheeku)(Sapling should be healthy grown up with good root system and minimum 4 feet high from ground level).
Phoenix dactylifera (Palm) (Sapling should be healthy grown up with good root system and minimum 4 feet high from ground level).
Services for maintenance of planted trees covered the following: (i) Watering the plant thrice a week having each irrigation of 10Litres (ii) Hoeing or loosening of soil after every 30 days (iii)Weeding, pruning, removal of garden rubbish. (iv) spraying of insecticides, pesticides (like Monocrotophus, Miticide, Rogor etc) after every 60 days using 25ml in 15 litres of water or using Methyl parathion or Furadan mixed in powder form with earth using 50gm per tree. (v) applying manure vermin-compost, neem cake & micro nutrients mixed with the earth in the ratio of 1:4 etc as per standard procedure and as directed by Engr-in- charge/GE, protecting the trees and shrubs, keeping good health of the plants so as to keep the plants live in entire period of 24 months and replacing the dead trees and shrubs with the size as per time grown new live trees & shrubs (with in 48 hours) etc.
Sl.item No. 60 Note:-. It is the responsibility of the contractor to make all necessary arrangement : (i) To keep the plant live and healhy for the entire period of 24 months. (ii) Replacing dead plants with the new ones. (iiI) Cost of Bio farmyard manure ( compost) for manuring the plants. (iii) Sweeping of area around trees/shrubs thrice in a week. (iv) The plants shall be handed over to users after 02 years from the physical date of completion and the responsiblity of maintaining the plants shall be done by the users.
Supply only approved earth for planting of grass
Supply only river sand
Labour only for mixing, spreading, levelling, watering and well ramming approved earth and sand in reqd proportion as directed for planting of grass in layers n exc 25 cm thick incl supply and mixing of 0.5Kg/Sqm of cow dung, 0.25kg/sqm of bone meal and 15 g/Sqm of insecticides at site
Supply and planting Mexican grass including providing manure as directed.
Gazebo &Stainless steel benches :- Stainless steel pipe for benches (grade 316 SS with medium wt sections) comprising any dia SS pipe rails, plates, angles etc including welding, buffing, polishing welded joint to match with pipe complete all as specified and as directed
Labour only, transport & plant tree retransplantation of any girth, any type and lead upto 1 KM including neceassary excavation, refilling and applying fertiliser complete all as specified and directed.
Lotus Construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .