CWE AHMEDABAD
CWE Ahmedabad Hanuman Camp Shahibaug Ahmedabad PIN-380003
PROVN OF TRANSFORMER AND OTHER ALLIED SERVICES FOR GK URC AND SHOPPING COMPLEX UNDER GE (A) AHMEDABAD
2026_MES_799360_1
87647/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
ARMY AREA AHMEDABAD
AS PER NIT
6 documents required · 6 mandatory
₹500
GE (A) GANDHINAGAR
₹85,500
Yes
18 Nov 2026
18 Nov 2026
10 Dec 2026
18 Nov 2026
8 Dec 2026
2 Dec 2026
18 Nov 2026 - 1 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and install of copper wound transformer step down, outdoor type complete with standard fittings, HT 11KV 3 phase, LT 433 Volts, 3 phase 4 wire of capacity 500 KVA, 11/0.433 KV, (copper wound), Energy efficient, Level-3, oil immersed , outdoor, delta-star Transformer with off-load tap changer on HT side to vary secondary voltage within limit, as per BIS 1180-2014 (Part-I) and IS-2026 specifications.
(a) Capacity - 500 KVA, Level 3, Energy efficient, with losses at 50% & 100% are 1354 watt & 3909 Watt respectively.
(b) Type - Oil immersed / copper wound.
(c) Number of phases - Three
(d) No Load Voltage Ratio - 11000/433 Volts.
(e) Frequency - 50Hz,
(f) Duty- Outdoor,
(g) Vector Group - Dyn-11, Delta/Star
(h) Type of Tap Switch Changer - 6 - Step, 7-Positions, Off-load Tap Changer
(j) Taping Range - +5% to -10% of HV in 6- steps @2.5% Each.
(k) Temperature Rise Oil/Winding - 40 to 45 degree celcius
(l) Type of Cooling - ON AN
Standard Fittings:-
1. Metal Parts for HT and LT fittings with HT bushings on Top cover and LT cable box.
2. Conservator fitted with CI Oil Gauge, Oil Filling Hole and CI cap & Drain Valve.
3. 6-step, 7-Positions, off-load tap changer
4. Dial, Thermometer for oil temperature
5. Dehydrating silica gel Breather, Arcing horns and Earthing Terminals,
6. Providing both (HT/LT) side cable box for HT/LT connection of cable. | 1 | Each | - | - |
| 2.01 | Supply, laying, jointing, testing and commissioning of LT underground cable 1100 Volt grade, PVC insulated and PVC/XLPE sheathed, heavy duty armoured with multi stranded aluminium conductor IS:1554 marked laid in trenches/duct/fixed to pole/walls/laid under road rossing/ paths/ drains/ culvert or encased in GI pipe complete all as specified and directed for the folloeing sizes:-
(a) 630 sqmm single core (unarmoured) | 48 | RM | - | - |
| 2.02 | (b) 185 Sqmm 3.5 core | 100 | RM | - | - |
| 2.03 | (c) 120 Sqmm 3.5 core | 300 | RM | - | - |
| 2.04 | (d) 95 Sqm 4 core | 100 | RM | - | - |
| 2.05 | (e) 70 Sqmm 4 core | 100 | RM | - | - |
| 2.06 | (f) 35 Sqmm 3.5 Core | 300 | RM | - | - |
| 3 | Material and labour for double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls/ pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed. | 470 | RM | - | - |
| 4 | All as per item No-3 above but of size outer dia 77 mm and inner dia 63 mm. | 380 | RM | - | - |
| 5 | All as per item No-3 above but of size outer dia 120 mm and inner dia 103 mm. | 42 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
TENDER.pdf
Tender Documents • 0.91 MB
BOQ_896847.xls
BOQ • 0.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .