Construction of Store godown, Scrap dumping godown at CSL/VSKP depot in the section of SSE/W/MPM/WAT under the jurisdiction of ADEN/Estate/WAT.
eT-HQ-WAT-02-2026
eT-HQ-WAT-02-2026
Open
8 Months
Visakhapatnam, Andhra Pradesh
₹0
₹3.2 L
23 Jan 2026
23 Jan 2026
5 Feb 2026
D-Preparation of Architectural Plans 223284.00 Below/P
Item Breakup - A-CPWD DSR 2023 ITEMS
Item Breakup - B-STEEL REINFORCEMENT
Item Breakup - C-STRUCTURAL STEEL ITEMS
Item Breakup - D-Preparation of Architectural Plans
Soil Architectural Plans, Elevations, Structural Designs, Drawings including proof check etc.,. Total 223284.00
Item Breakup - E-ELECTRICAL ITEMS
Supply, Commissioning of out door feeder pillar consisting of copper bus bar 400Amp for RYB & N with LED type indication lamp for RYB in incoming side in a CRCA sheet with double door provision & locking arrangement. The panel shall consist of I/C:1X250A MCCB 4P Ics 35KA with 250/5A CTs, O/G:4x100A MCCB 4P Ics 25KA, 1x63A MCB DP, 7x32A MCB DP,10KA, Timer with contactor, size: 700mmX 900mmX350mm approx., sheet :1.6mm thick, Angle :40x40x6mm, Channel:75X40 mm (For MCCB's Ics=100% Icu). :-- The price also covers the cost of Supply, Erection, Testing and Commissioning of out door feeder pillar consisting of copper bus bar 400Amp for RYB & N with LED type indication lamp for RYB in incoming side in a CRCA sheet with double door provision & locking arrangement. The panel shall consist of I/C:1X250A MCCB 4P Ics 35KA with 250/5A CTs, O/G:4x100A MCCB 4P Ics 25KA, 1x63A MCB DP, 7x32A MCB DP,10KA, Timer with contactor, size: 700mmX900mmX350mm approx., sheet :1.6mm thick, Angle :40x40x6mm, Channel:75X40mm (For MCCB's Ics=100% Icu). The price shall cover the cost of all materials required for the above work including labour charges. Before supply of contractor has to take a p p r o v a l of drawing, switchgear, components other accessories of LT panel board from SrDEE/G/WAT or his authorized official.
Supply, erection, testing and commissioning Numbers of Combined Unit of 63A Capacity Industrial Plug Socket 380/415V 3P+N+E panel mounting IP/66/67 and 63A MCB TPN with enclosure :--- The price also covers the cost of Supply, erection, testing and commissioning of Combined Unit of 63A Capacity Industrial Plug Socket 380/415V 3P+N+E panel mounting IP/66/67 and 63A MCB TPN with enclosure. The price shall cover the cost of all materials required for the above work including labour charges. Before supply of contractor has to take a p p r o v a l of drawing, switchgear, components other accessories of LT panel board from SrDEE/G/WAT or his authorized official.
Erection, testing and commissioning of Numbers Railway supplied LED flood light luminaire with supply & fixing of GI Clamps, hardware & fasteners with connection from nearest Junction Box to make the light fitting functional but except point wiring for illumination of cover shed etc,. :---- The price also covers the cost of Erection, testing and commissioning of Railway supplied LED flood light luminaire with supply & fixing of GI Clamps, hardware & fasteners with connection from nearest Junction Box to make the light fitting functional but except point wiring for illumination of cover shed etc. The price shall cover the cost of all materials required for the above work including labour charges. WALTAIR DIVISION-ENGINEERING/ECOR
Supply, erection, testing and commissioning Numbers of All-in-one Solar Steet Light System 25W LED, IP:65 or better, Power output of PV module: >/=75Wp, LiFeP04 Battery capacity >/= 12.8V (nominal), 30 Ah, provided with 2 LED indicators for chaning in progress, deep discharge condition, 7m height pole, nominal bore size/thickness: 65mm/4.5mm, battery box: battery included in the luminaire enclosure and corrosion resistant, with solar PV modules with efficacy >/=75Wp at 16.4+/-0.2 V at STC, necessary control electronics, interconnecting wires/cables, module mounting structures etc. to operate from dusk to dawn etc. as per other conditions in specification similar to model No. Havells 7. Price also include cost of concrete foundation, erection of lighting sytem with grouting bolt etc. for commissioning of the entire system :--- The price also covers the cost of Supply, erection, testing and commissioning of All-in-one Solar Steet Light System 25W LED, IP:65 or better, Power output of PV module: >/=75Wp, LiFeP04 Battery capacity >/= 12.8V (nominal), 30 Ah, provided with 2 LED indicators for chaning in progress, deep discharge condition, 7m height pole, nominal bore size/thickness: 65mm/4.5mm, battery box: battery included in the luminaire enclosure and corrosion resistant, with solar PV modules with efficacy >/=75Wp at 16.4+/-0.2 V at STC, necessary control electronics, interconnecting wires/cables, module mounting structures etc. to operate from dusk to dawn etc. as per other conditions in specification similar to model No. Havells 7. Price also include cost of concrete foundation, erection of lighting sytem with grouting bolt etc. for commissioning of the entire system. The price shall cover the cost of all materials required for the above work including labour charges.
Erection, testing and commissioning of Numbers Railway supplied wall mounting industrial air circulator Electric Fan 600mm/750mm sweep with all required GI fasteners, GI hardware and welding work as per site requirement, at location specified by Engineer-in-charge :--- The price also covers the cost of Erection, testing and commissioning of Railway supplied wall mounting industrial air circulator Electric Fan 600mm/750mm sweep with all required GI fasteners, GI hardware and welding work as per site requirement, at location specified by Engineer-in-charge. The price shall cover the cost of all materials required for the above work including labour charges. WALTAIR DIVISION-ENGINEERING/ECOR
Supply, erection, testing and commissioning Numbers of 12-Way SPN DB, IP-43, IK-09 with metal door, double door DB similar to Model No.
and O/G: 8x16A to 32A SP MCB. All MCBs shall be 10KA, C-curve. The price also covers complete wiring with FLRSH PVC flexible copper wire of rated cross-section and materials required for erection of DB at specified location. Make: Legrand, ABB, Siemens, C&S and L&T :--- The price also covers the cost of Supply, erection, testing and commissioning of 12-Way SPN DB, IP- 43, IK-09 with metal door, double door DB similar to Model No. 5076 12 consisting of I/C: 1x63A FP MCB and O/G: 8x16A to 32A SP MCB. All MCBs shall be 10KA, C-curve. The price also covers complete wiring with FLRSH PVC flexible copper wire of rated cross-section and materials required for erection of DB at specified location. Make: Legrand, ABB, Siemens, C&S and L&T. The price shall cover the cost of all materials required for the above work including labour charges.
Single Cable Laying Along the road/Track :-- Metre - The price shall cover the cost of transporting the UG cable from stores of work incharge office, or, other premises as directed by work incharge to work site& laying of cable shall be completed with contractors men & materials and laying after excavation of earth in any type of soil. The dimension of trench number of bricks, sand bedding etc., shall be confirmed to the CEE/ECoR/BBS drawing No. CEE/GS/Cable Trench/01 (mod-01) or latest. Price is also inclusive of refilling levelling and dressing of earth to be done contractors labour, tools and materials. The IR values of cable is to be measured before and after laying of the cable.
Single Cable Laying Across the road/track :- Metre --- The price shall cover the cost of transporting the UG cable from stores of work incharge office, or, other premises as directed by work incharge to work site. & laying of cable shall be completed with contractors men & materials. The cable laying shall be in accordance with CEE/BBS's latest drawing No. CEE/GS/Cable trench/01 (mod-01). Price is also inclusive of refilling levelling and dressing of earth to be done contractors labour, tools and materials. The IR values of cable to be measured before and after laying of the cable.
Laying of Cable in open air :---- The unit Metre price shall cover for fixing of the cable on plinth/structure/column/culvert to be done by GI Clamp of suitable size as per site requirement. The distance of each clamp should not be more than 1 meter. The work should be completed with contractors' materials, tools & plants etc. WALTAIR DIVISION-ENGINEERING/ECOR
Laying of cabling by HDD Trench less :---- Metre The rate includes pushing of HT/LT cable through HDPE Pipe casing (PE 80 grade, 160 mm OD, 0.6 MPa working pressure, 9 mm thick) by adopting trenchless construction method. The contractor shall join the HDPE pipe and make necessary interlocking as directed by the site in charge. The rate is inclusive of supply of PE 80 grade, 160 mm OD, 0.6 MPa working pressure, 9mm thick HDPE Pipe confirming to IS: 4984:1995 and all other associated items required for the work. The horizontal bore should be done by using an auger boring machine (ABM). The price shall also include construction of required launch pit and reception pit at minimum depth of 3 meters, cleaning out the HDPE pipe casing and restoring the area as required with the help of contractor's men and material.
Cable Laying Through HDPE Pipe :--- The Metre price includes laying of cable through HDPE Pipeto be done by the contractor and the work shall be completed as per the direction of Engineer in Charge of work at site. The IR values of cables shall be tested jointly signed by Rly representative and authorized contractors representative prior to laying, after laying and just before charging the cable.
Laying of Railway supplied UG Cable of Metre different size: Along the Road double Cable :---The price shall cover the cost of transporting the UG cable from stores of work incharge office, or, other premises as directed by work incharge to work site & laying of double cable shall be completed with contractors men & materials. Double cable laying along the road/track after excavation of earth in any type of soil. The dimension of trench, number of bricks, sand bedding etc., shall be confirming to the CEE/ECoR/BBS latest drawing No. CEE/GS/Cable Trench/01 (Mod-1). The cost is also inclusive of refilling of earth, levelling of earth to be done by contractors' labour, tools and materials. The work is to be completed with the contractors' labour, tools and all required materials including erection, testing and commissioning. Price is also inclusive of refilling levelling and dressing of earth to be done contractors labour, tools and materials. The IR values of cable to be measured before and after laying of the cable. WALTAIR DIVISION-ENGINEERING/ECOR
Laying of Railway supplied UG Cable of Metre different size: Across the Road/Track double cable :---- The price shall cover the cost of transporting the UG cable from work in- charge office, store, other premises as directed by work in-charge to work site & laying of double cable across the track/hard soil with contractors' men &material. The double cable laying shall be in accordance with CEE/BBS's latest drawing No. CEE/GS/Cable trench/01 (mod-01). Price is also inclusive of refilling levelling and dressing of earth to be done contractors labour, tools and materials. The work is to be completed with the contractors' labour, tools and all required materials including erection, testing and commissioning. Price is also inclusive of refilling levelling and dressing of earth to be done contractors labour, tools and materials. The IR values of cable to be measured before and after laying of the cable.
Earthing arrangement :---- The price shall Numbers include the cost for excavation of earth pits in any kind of soil, supply and erection of earth cone and strip including refill with salt, charcoal as per CEE/BBS's Drawing No. CEE/GS/Earthing/02 dt. Dt.21/02/2006 and connected by means of 6 SWG GI wire. The work shall also cover the cost of materials and labour charges for construction of sump as shown in the aforesaid drawing and the earth treated to obtain earth resistance of as per Rule. Connection of earth electrode should be made by providing clamp, nuts, bolts and 6 SWG GI wire. The price shall cover for supply and erection of earth pit cover made by RCC and make it complete in all respects as per above drawing. The price also covers 6 SWG GI wire from earth pit to nearest main supply point and installation. The makes and specifications are shown in Annexure.
Supply & erection of cable route marker :--- Numbers The price shall cover the cost of supply and erection of cable route marker as per sample approved by Sr.DEE(G) or his authorised representative. Cable route marker should be provided along straight runs of the cables at intervals of 50m or by site in-charge. The price shall cover the cost of all materials required for the above work including labour charges.
Supply & erection of outdoor type MS/FRP Numbers loop in loop out box made of 1.6mm thick MS sheet/FRP of size 200X150X100mm & 4way stud connector with provision of door in front side with locking arrangement :---- The price also covers the cost of Supply & erection of outdoor type MS/FRP loop in loop out box made of 1.6mm thick MS sheet/FRP of size 200X150X100mm & 4way stud connector with provision of door in front side with locking arrangement. The price shall cover the cost of all materials required for the above work including labour charges. Before supply of materials, contractor has to take approval from Sr.DEE(G)/WAT or his authorized official. WALTAIR DIVISION-ENGINEERING/ECOR
Supply, erection, testing and commissioning Numbers of out door feeder pillar consisting of copper bus bar 200Amp with LED type indication lamp for RYB in incoming side in a CRCA sheet with double door provision & locking arrangement. The panel shall be consist of I/C: 1X100A MCCB 4P 35KA with multifunction energy meter with 100/5A CTs, outgoing: 2X63A MCB TPN 10KA, 4x32A MCB TPN 10KA. Size:800mmX 600mmX 375mm approx., sheet:1.6mm thick, Angle:40x40x6mm, Channel:75X40x6mm). Erection price also covers brick pedestal :---- Supply, erection, testing and commissioning of out door feeder pillar consisting of copper bus bar 200Amp with LED type indication lamp for RYB in incoming side in a CRCA sheet with double door provision & locking arrangement. The panel shall be consist of I/C: 1X100A MCCB 4P 35KA with multifunction energy meter with 100/5A CTs, outgoing: 2X63A MCB TPN 10KA, 4x32A MCB TPN 10KA. Size:800mmX 600mmX375mm approx., sheet:1.6mm thick, Angle:40x40x6mm, Channel:75X40x6mm). Erection price also covers brick pedestal.
Supply 50X6mm/25X6mm flat for connection to earth :---- The rates are inclusive of Supply and erection of GI flat 50X6mm/25X6mm flat for connection to earth. The price shall cover the cost of all materials required for the above work including labour charges.
Laying of cable along the concrete Metre floor/black top road by cutting floor/black top road without G.I pipe/HDPE Pipe :--- The price includes laying of cable along the concrete floor/black top road by cutting floor/black top road to be done by the contractor and the work shall be completed as per the direction of Engineer in Charge of work at site. The price shall be inclusive of charges for laying of cable in the concrete floor by digging the floor with contractor's labour and tool and top up to be done with suitable cement or black top. The work shall be executed as per the direction of Engineer in Charge of work at site. The IR values of cables are to be tested prior to laying, after laying and just before charging the cable and the values recorded should be jointly signed by Rly representative and authorized contractors representative.
Supply & erection of 40 mm Diameter PN-6, Metre PE-80 HDPE Pipe conforming to IS- 4984:2016 and Clamps including cutting and making good the walls etc,. :---- The price also covers the cost of Supply & erection of 40 mm Diameter PN-6, PE-80 HDPE Pipe conforming to IS-4984:2016 and Clamps including cutting and making good the walls etc.. The price shall cover the cost of all materials required for the above work including labour charges. WALTAIR DIVISION-ENGINEERING/ECOR
Supply & laying of 6/8/12 SWG GI steel wire Kg :---- The rates are inclusive of supply and laying of 6/8/12 SWG GI wireas per IS 12776/2002 specification and laying with the contractors, man power, materials, tools & clamps etc., from earth pit to transformers, distribution boards and all electrical equipment's as per the site engineer's instructions. The price shall cover the cost of Supply and laying of 8SWG GI wire as per relavant IS specification The work shall be executed as per the direction of Engineer in Charge of work at site. The price shall cover the cost of all materials required for the above work including labour charges.
Fabrication, supply, laying and fixing of S.S Metre perforated cable tray of size 300mm x 100mm x 1.5mm thick (12" x 4") with cover, SS 202 thickness grade, 16 guage. The sample should be got approved by Sr.DEE. The cable trays should be fixed on the roof, under COP, wall, with suitable clamps, bolts & nuts etc., firmly and rigidly : - - - The price also covers the cost of Fabrication, supply, laying and fixing of S.S perforated cable tray of size 300mm x 100mm x 1.5mm thick (12" x 4") with cover, SS 202 thickness grade, 16 guage. The sample should be got approved by Sr.DEE. The cable trays should be fixed on the roof, under COP, wall, with suitable clamps, bolts & nuts etc., firmly and rigidly. The price shall cover the cost of all materials required for the above work including labour charges.
Supply and fixing of PVC RJ box/ square Numbers 200.00 junction box on wall/roof/truss :---- The price shall cover the cost of supply and erection of PVC circular box/ round junction box/ square junction box conforming to IS: 9537- 3 of 1983 or GI square junction box as and when required on the roof/wall/truss with contractor's tools &labours. The price shall cover the cost of all materials required for the above work including labour charges. WALTAIR DIVISION-ENGINEERING/ECOR
Concealed/Surface fan/call bell point wiring (without supply and laying of pipe) with (2x1.5+1x1) Sq.mm FRLS PVC insulated flexible copper conductor 1100V grade :--- Supply of materials, testing & commissioning with single core FRLS PVC insulated multi stranded copper conductor of size 1.5 sq. mm 1100V grade confirming to IS 694/1990 each for phase & neutral and 1.0 Sq.mm FRLS PVC insulated copper wire for earth continuity conductor. The rate includes concealed wiring of light/Ceiling fan/Exhaust Fan/Air circulator in any type of wall complete with supply of materials, testing & commissioning with single core FRLS PVC insulated multi stranded copper conductor of size 1.5 sq. mm (1100V grade) each for phase & neutral and 1.0 Sq.mm FRLS PVC insulated copper wire for earth continuity conductor drawn inside suitable size of PVC pipe of 2mm thick. The wiring shall be in Loop method where the phase/Live wire shall be looped at Switch and Neutral only. No joints shall be allowed. In case of angular lamp holder it should be fixed properly on 4"x4" size GI box concealed in the wall. In case of FL light point and fan point, connection is to be terminated in a Poly carbonate three terminal ceiling rose fixed on top of the suitable size GI box fixed inside the wall / ceiling. The control shall be of 6 amps 250V grade modular type switch shall be supplied and fixed by contractor on suitable size of GI flush box to accommodate number of switches in that sub circuit and as decided by the site in-charge with modular cover plate. The cost includes fixing of the board with required material and fasteners etc. on the wall. The location of the board shall be decided by the site in charge. The number of switches in the Switch board will depend on number of points in that sub circuit or as decided by the site in-charge. The cost of wiring point includes supply of Fasteners, PVC Sleeves, Elbow, Tee of appropriate size of PVC conduit pipe, flush box, cover other items required for completion of work with contractor manpower and material and as directed by site in charge. The cost also includes connection of wires on both sides. The price also covers groove cutting in the wall and makes it the original position cement plastering with contractor's labour, materials and tools as directives of engineer in-charge at site. Before supply of material the make and specifications shall be as per Annexure.
Modular wiring on board 6A 5-pin plug point Numbers with (2x2.5+1x1) Sq.mm FRLS flexible copper conductor 1100V grade :---- The price shall covers the cost of Provision for modular wiring on board 6A plug point with 2.5 sq.mm. copper wire. The price shall cover the cost of all materials required for the above work including labour charges. Before supply of materials, contractor has to take approval from Sr.DEE(G)/WAT or his authorized official. WALTAIR DIVISION-ENGINEERING/ECOR
Concealed/surface wiring (without supply Point and laying of pipe) for separate plug point 6A 5-pin 250V modular type with (2x2.5+1x1) Sq.mm FRLS flexible copper conductor 1100V grade :---- The rate includes concealed wiring of 6A capacity socket point in any type of wall, complete with supply of materials, testing & commissioning with single core FRLS PVC insulated multi stranded copper conductor of size 2.5 sq. mm 1100V grade confirming to IS: 694/1990 each for phase & neutral and 1.0 Sq.mm FRLS PVC insulated copper wire for earth continuity conductor drawn inside suitable size PVC conduit pipe of suitable size of 2mm thick. The circuit shall be drawn from sub service main/nearest Switch board for phase and neutral and shall be terminated on the socket. The concealed wiring shall be in loop in loop out method. No joints shall be allowed. The control switch and socket shall be of 6 amps capacity 5 pin socket modular type fitted on the separate metal flush box with modular cover plate. The cost includes fixing of the board with required material and fasteners etc. on the wall. The location of the board shall be decided by the site in charge. The cost of wiring point includes supply of Fasteners, PVC Sleeves, Elbow, Tee of appropriate size of PVC conduit pipe, and other items required for completion of work with contractor manpower and material and as directed by site in charge. The cost also includes connection of wires on both sides. The cost also include, Fixing of socket, switch and making connection with three wires (Phase, Neutral & Earth). The price also covers groove cutting in the wall and makes it in the original position cement plastering as directives of engineer in-charge at site. Before supply of material the make and specifications shall be as per Annexure. WALTAIR DIVISION-ENGINEERING/ECOR
Concealed/surface wiring (without supply Point and laying of pipe) for separate plug point 6A+16A 250V modular type with (2x4+1x1.5) Sq.mm FRLS flexible copper conductor 1100V grade :--- The rate includes concealed wiring of 16A capacity socket point in any type of wall, complete with supply of materials, testing & commissioning with single core FRLS PVC insulated multi stranded copper conductor of size 4. sq. mm 1100V grade confirming to IS: 694/1990 each for phase & neutral and 1.5 Sq.mm FRLS PVC insulated copper wire for earth continuity conductor drawn inside suitable size PVC conduit pipe of suitable size of 2mm thick. The circuit shall be drawn from sub service main/nearest Switch board for phase and neutral and shall be terminated on the socket. The concealed wiring shall be in loop in loop out method. No joints shall be allowed. The control switch and socket shall be of 16 amps capacity 5 pin socket modular type fitted on the separate metal flush box with modular cover plate. The cost includes fixing of the board with required material and fasteners etc. on the wall. The location of the board shall be decided by the site in charge. The cost of wiring point includes supply of Fasteners, PVC Sleeves, Elbow, Tee of appropriate size of PVC conduit pipe, and other items required for completion of work with contractor manpower and material and as directed by site in charge. The cost also includes connection of wires on both sides. The cost also include, Fixing of socket, switch and making connection with three wires (Phase, Neutral & Earth). The price also covers groove cutting in the wall and makes it in the original position cement plastering as directives of engineer in-charge at site. Before supply of material the make and specifications shall be as per Annexure.
Concealed/surface (2x6+1x2.5sqmm) FRLS copper wire 1100 Metre volt grade (without supply and laying of pipe) on truss/roof/wall :---- The rate includes PVC Pipe wiring of sub main wiring (concealed) from distribution board to the sub main board in any type of wall, complete with supply of materials, testing & commissioning with single core PVC FRLS insulated multi stranded copper conductor of size 6 sq.mm 1100V grade confirming to IS: 694/1990, 2 wire. The copper conductor shall drawn inside of suitable size of PVC Pipe. Connection is to be tapped off from the Distribution board. 2.5 sq mm copper wire is to be drawn as earth wire. 1 meter length consists of two wires of 6 sq.mm and one wire of 2.5sqmm (Phase, Neutral Earth). The price also covers groove cutting in the wall and makes it in the original position cement plastering with contractor's labour, materials and tools as directives of engineer in-charge at site. Before supply of material the make and specifications shall be as per Annexure. WALTAIR DIVISION-ENGINEERING/ECOR
Concealed/surface (2x4+1x1.5sqmm) FRLS copper wire 1100 Metre volt grade (without supply and laying of pipe) on truss/roof/wall :---- The rate includes PVC Pipe wiring of concealed wiring from distribution board to the sub distribution board or for AC point in any type of wall, complete with supply of materials, testing & commissioning with single core PVC FRLS insulated multi stranded copper conductor of size 4 sq mm 1100V grade confirming to IS: 694/19902 wire. The copper conductor shall drawn inside of suitable size of PVC Pipe. 1.5 sq mm copper wire is to be drawn as earth wire. 1 meter length consists of two wires of 4 sqmm and one wire of 1.5sqmm (Phase, Neutral Earth). The price also covers groove cutting in the wall and makes it in the original position cement plastering with contractor's labour, materials and tools as directives of engineer in-charge at site. Before supply of material the make and specifications shall be as per Annexure.
Concealed/surface (2x2.5+1x1.0sqmm) FRLS copper wire 1100 Metre volt grade (without supply and laying of pipe) on truss/roof/wall :--- The price shall cover cost of supply &concealed/surface wiring (without supply and laying of pipe) for separate plug point 6A 250V modular type long run with (2x2.5 )Sq.mm1100V grade PVC insulated flexible copper conductor cable (for phase and neutral ) and (1 x 1) sq.mm1100V grade PVC insulated flexible copper conductor cable(for earth)with supply of Modular Switch 6A,250V AC, Modular Socket 6A,250V AC on 3 way module metal box and 3way module white plate. The price excludes supply & laying of PVC conduit pipe/casing & caping. The price shall cover the cost of all materials required for the above work including labour charges. approval from Sr.DEE(G)/WAT or his authorized official before execution of work.
Supply & laying of PVC rigid Conduit pipe Metre 25mm outer dia (Heavy) on truss with proper saddles/GI clamps :----- The price also covers the cost of Supply & laying of PVC rigid Conduit pipe 25mm outer dia (Heavy) on truss with proper saddles/GI clamps. The price shall cover the cost of all materials required for the above work including labour charges. Before supply of materials, contractor has to take approval from Sr.DEE(G)/WAT or his authorized official.
Supply & laying of PVC rigid Conduit pipe Metre 32 mm outer dia (Heavy) on truss with proper saddles/GI clamps :---- The price also covers the cost of Supply & laying of PVC rigid Conduit pipe 32mm outer dia (Heavy) on truss with proper saddles/GI clamps.. The price shall cover the cost of all materials required for the above work including labour charges. Before supply of materials, contractor has to take approval from Sr.DEE(G)/WAT or his authorized official. WALTAIR DIVISION-ENGINEERING/ECOR
Concealed/surface (4x6+1x2.5)sq.mm Copper Wire 1100 volt Metre grade (without supply & laying of PVC pipe) : - - - - The price shall cover cost of Concealed/surface wiring with (4x6+1x2.5)sq.mm Copper Wire 1100 volt grade (without supply & laying of PVC pipe). The price shall cover the cost of all materials required for the above work including labour charges. approval from Sr.DEE(G)/WAT or his authorized official before execution of work.
Concealed/surface (2x1.5+1x1.0) sq.mm Copper Wire 1100 Metre volt grade (without supply & laying of PVC pipe) :---- The price shall cover cost of Concealed/surface wiring with (2x1.5+1x1.0) sq.mm Copper Wire 1100 volt grade (without supply & laying of PVC pipe).The price shall cover the cost of all materials required for the above work including labour charges. approval from Sr.DEE(G)/WAT or his authorized official before execution of work. Total 1758130.96
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
SpecialConditionsforCivilWorks.pdf
ATTACHMENT
SpecialConditionsCementandSteel.pdf
ATTACHMENT
INSTRUCTIONSTOTENDERERSNEW.pdf
ATTACHMENT
BidSecurityBond_.pdf
ATTACHMENT
Board Letter Graduate Engineer
ATTACHMENT
Boardletter-Graduate-DiplomaEngineerRegards.pdf
ATTACHMENT
AnnexureVI-B_.pdf
ATTACHMENT
GCC-2022_.pdf
ATTACHMENT
AnnexureVandVAmodified.pdf
ATTACHMENT
TenderFormFirstsheetNEW.pdf
ATTACHMENT
Anx-I-GuaranteeBond.pdf
ATTACHMENT
EFTFORM.pdf
ATTACHMENT
ELECTRICALSPECIALCONDITIONSRECENT2026.pdf
ATTACHMENT
MAKESANDSPECIFICATIONS.pdf
ATTACHMENT
CompositetenderElectricalGconditions.pdf
ATTACHMENT
GCC-2022-ACS-1to10_.pdf
ATTACHMENT
Annexure-VI-BidCapacity.pdf
ATTACHMENT
JPO-Circular-GuidelinesforprotectionofCables.pdf
ATTACHMENT
ElectricalSchedulestorecanteen_c.pdf
ATTACHMENT