Rate contract for SITC of different types of Air Conditioning system work in different offices and building premises of AMC.(Within the limit of Amount Rs.1.00 Crore)
301440
2026-2027
Open
Miscellaneous Works
Ahmedabad
3 documents required · 2 mandatory · 1 optional
₹2,400
Municipal Commissioner, Ahmedabad
₹1 L
5 May 2026
5 May 2026
5 May 2026
12 May 2026
5 May 2026
VOL-I TECHNICAL BID
1 Tender documents available On web site https://tender.nprocure.com
2 Last Date & Time of submitting the filled till Dt.12/05/2026 up to 6.00 p.m only on website
up tender online https://tender.nprocure.com
3 Last Date- Time and Place of submission Up to Dt.13/05/2026 4:00 p.m. only At the Office of
of Volume-I (Technical Bid only) of Tender Officer, Central Record Office, Mezzanine Floor,
Tender in Physical form Block-B, Sardar Patel Bhavan, Danapith, Ahmedabad-
380 001,Gujarat,India.
4 Tender Vol-I (Technical Bid only) Opening Dt.13/05/2026 at 4:05 p.m. onwards
Date-Time and Place Online Opening:-At the Office of Additional Chief
Engineer (Electrical), Light Department,5th Floor “C”-
Block, Sardar Patel Bhavan, Danapith , Ahmedabad-380
001, Gujarat, India.
Physical Opening :-At the Office of Tender Officer,
Central Record Office, Mezzanine Floor, Block-B, Sardar
Patel Bhavan, Danapith, Ahmedabad-380 001,Gujarat,
India or at the above said office
MUNICIPAL COMMISSIONER
Ahmedabad Municipal Corporation
AHMEDBAD MUNICIPAL CORPORATION
Sardar Patel Bhavan,Danapith
ELECTRICAL DEPARTMENT Ahmedabad - 380
BRIEF TENDER NOTICE FOR WORK,TENDER FEE AND EARNEST MONEY DEPOSIT
S.N. WORK DESCRIPTION TENDER FEE E.M.D.
Rate contract for SITC of different types of Air Rs.2400/-( Non Rs. 1,00,000/-in the
1 Conditioning system work in different offices and Refundable) form of demand draft
building premises of AMC.(Within the limit of or bank guarantee of
banks mentioned as per
Amount Rs.1.00 Crore)
Interested Only Eligible tenderer may obtain further information and clarification on any
matter relating to the tender documents from the Office of Additional Chief Engineer
(Electrical),5thFloor,”C”-Block,Sardar Patel Bhavan,Danapith,Ahmedabad-380
Tender Fee-Demand Draft only
Tender must be accompanied by the Tender Fee through Demand Draft only in favourof
“Municipal Commissioner,AMC”payable at Ahmedabad from banks mentioned in
Annexure-I only with their tender documents.
Without tender Fee tender will be strictly rejected.
Earnest Money Deposit (E.M.D.) – Demand Draft or bank guarantee only
Tender must be accompanied by the E.M.D. through demand draft or bank guarantee in
favour of “Municipal Commissioner, AMC” payable at Ahmedabadof banks mentioned in
Annexure-I only with their tender documents.
Without E.M.D. tender will be strictly rejected
Signature of the Tenderer Addl. Chief Engineer
Name : (Electrical)
Company’s seal AMC
LIST OF BANKS FOR TENDER FEE,EARNEST MONEY DEPOSIT(E.
M.D.) , SECURITY DEPOSIT AND PERFORMANCE GUARANTEE
Tender Fee must be in form of Demand Draft only of following banks only.
Earnest Money Deposit / Security Deposit /Performance guarantee shall be in form
of Demand Draft or Bank Guarantee only of following banks only.
A. Guarantees issued by following banks will be accepted as SD/EMD on
permanent basis.
All nationalized Banks
B. Guarantees issued by following banks will be accepted as SD/EMD
forthe period up to March- 31, 2026. The validity cut-off date in the GR
is with respect to the date of issue of Bank Guarantee irrespective of
the date of termination of Bank Guarantee.
1. Commercial Banks:-
2. AU Small Finance Bank
3. Bandhan Bank
4. Barclays Bank
5. City Union Bank
7. DBS Bank India Limited
9. Equitas Small Finance Bank
10. ESAF Small Finance Bank
11. Federal Bank
16. IDFC First Bank
17. Jammu and Kashmir Bank
18. Jana Small Finance Bank
19. Karnataka Bank
20. Karur Vysya Bank
21. Kotak Mahindra Bank
22. South Indian Bank
23. Standard Chartered Bank
24. Tamilnadu Mercantile Bank
25. Utkarsh Small Finance Bank
2. Co-operative and Rural Banks Of Gujarat:-
1. The Ahmedabad Mercantile Co-operativeBank Limited
2. Nutan nagrik Sahakari Bank Limited
3. Rajkot Nagarik Sahakari Bank Limited
4. Saraswat Co-operative Bank
5. SBPP Co-operative Bank
6. SVC Co-operative Bank
7. The Cosmos co-opretive Bank
8. The Gujarat State Co-Operative Bank
9. The Mehsana Urban Co-operative Bank Limited
10. The Surat District Co-operative Bank
11. The Surat Peoples Co-operative Bank
12. The Kalupur Commerical Co-operative Bank Limited
13. The Panchmahal District Co-operative Bank
14. The Baroda District Co-operative Bank
15. Baroda Gujarat Gramin Bank
16. Saurashtra Gramin Bank
Bank guarantee of above mentioned banks accepted only for Ahmedabad City branch
Addl.Chief Engineer
Signature of the Tenderer AMC
VOLUME - I : TECHNICAL BID
MUNICIPAL COMMISSIONER,
Ahmedabad Municipal Corporation,
Sardar Patel Bhavan,
Danapith,Ahmedabad.
Work:- Rate contract for SITC of different types of Air Conditioning system work in different
offices and building premises of AMC.(Within the limit of Amount Rs.1.00 Crore)
1. Hereby Rate Contract of SITC of different types of Air Conditioning system work in different
offices and building premises of AMC.(Two-Bid System) invited on behalf of Municipal
Commissioner, for Rate Contract for S.I.T.C. work of Ductable , Cassette &Tower Air-conditioners.
2. Tender along with conditions of contract shall be available from the
websitehttps://tender.nprocure.comTenderer shall have to submit D.D. of banks mentioned in
Annexure-Ionly in favour of “Municipal Commissioner, Ahmedabad” Payable at Ahmedabad of
amount Rs.2400/-as tender fee along with the tender submission. Tender received without tender
fee shall be considered as Non-Responsive and shall stand rejected outright.
3 Earnest Money Deposit (E.M.D.)shall be in the form of Demand Draftor bank guarantee infavour of
Municipal Commissioner, Ahmedabad” payable at Ahmedabad from banks mentioned in Anexure-I
only of Rs. 1,00,000/-with their tender documents.
4 SUBMISSION OF TENDER
Tenders shall be submitted together with the other documents that form the tender. In the event of
a Contract, the tender and the documents attached there to shall be considered as forming part of
the Contract Documents.
VOLUME-I TECHNICAL BID
• Separate envelop for Tender fee (D.D. only)
• Separate envelop for E.M.D. (D.D./B.G. only)
• Volume-I ,General condition, Common condition etc
• All supporting documents mentioned in Eligibility Criteria
• Addendum, if any
• All the pages of tender documents has to be stamped and signed by the tenderer
VOLUME-II FINANCIAL BID
• Schedule of Quantities & Rates/B.O.Q.(online only)
Two sets of technical bid only (One Original + One Xerox copy) of tender documents duly completed
in all respects shall be submitted so as to reach at the above stated address on or before the date
and time mentioned in tender notice.
E.M.D and Tender Fee in the form of Demand Draft / Bank guarantee should be sealed in separate
envelope and the same shall be enclosed along with Tender document Volume-I (put original copy in
original document envelop and one Xerox copy in Xerox copy document envelop).
Both Original and Xerox copy tender document envelope should be sealed in one large envelope. On
this envelope, the Name and address of Tenderer, Name of Work, and date of opening of the tender
shall be written invariably. No condition will be accepted along with the given bid. Price bid fulfilled
by the contractor online only.
The tender shall be considered non-responsive if not sealed. Tenderer shall not be allowed to fill in or
seal their tenders at the AMC Office. Tenderer are requested to present the tenders well in time
before stipulated date and time of receipt; so as to avoid rush at the closing hours.
5 Erasures and other changes shall be noted over by the initials of the person signing the tender.
6 The successful tenderer shall have to pay Security Deposit worth 5% amount of the Ordered Value in
Indian Rupees as per Form “A” enclosed with tender documents or as per acceptable form to AMC
within 15 days from receiving date of Purchase Order in the form of demand draft or Bank
Guarantee from banks mentioned in Annexure-I only ,the condition of which strictly followed by
successful bidder, failure of which tender shall be liable to reject.
Validity of Security deposit (S.D.) will be refund after completion of warranty of Last given sub-order
in the tender. EMD will release upon submission of S.D.
The E M D of the contractor, whose tender is accepted, shall be forfeited in full in case He/She
does not remit the initial security deposit within the stipulated period and does not complete
the contract with AMC within 15 days from receiving date of Purchase Order.
Additional Performance Security:-
In the case of any Bid where quoted rate appear unrealistic, such Bid will be considered as
unbalanced and; in case the Bidder is unable to provide satisfactory explanation, such a Bid is liable
to be disqualified and rejected. However, the Bidder may be asked; at the discretion of the Authority
only to submit the Additional Performance Security calculated as under:
(i) If the bid price offered by the Successful Bidder is lower than 15% but up-to 20% of the Estimated
Cost of work, then the Additional Performance Security shall be calculated @20% of the difference in
the [(a) Estimated Cost of work (as mentioned in BOQ)-10% of the Estimated Cost of work] and [ (b)
the Bid Price offered by the Selected Bidder]
(ii) If the bid price offered by the Successful Bidder is lower than 20% of the Estimated Cost of work,
then the Additional Performance Security shall be calculated @30% of the difference in the [(a)
Estimated Cost of work (as mentioned in RFP)-10% of the Estimated Cost of work] and [(b) the Bid
Price offered by the selected Bidder]
The Additional Performance Security shall not be treated as part of Performance Security
7 Unsuccessful Tenderer’s(i.e. L2&L3) Earnest Money will be refund after submission of security deposit
of lowest tenderer(i.e. L1). No interest will be paid on Earnest Money deposit.
8 The Conditional Tender will not be accepted and shall be rejected outright, unless, the nature of
condition(s) put up by the tenderer is acceptable to AMC. Any suggestions/alteration from the
tender must be mentioned in the main forwarding letter.
10 Tender shall also be liable to be rejected if –
i) Any of the page or pages in the tender is / are removed or replaced or altered.
ii) All corrections, additions or pasted slips are not initialed by the tenderer.
iii) Any erasure is made in the tender.
iv) The tenderer or in the case of a firm, each partner or the person holding the power of
attorney thereof does not sign or the signature(s) is (are) not attested by the witness,
wherever it is required.
v) Tender fee and Earnest Money for required amount is not paid with the tender.
vi) Tender submitted without submission of document required as per qualification criteria,
signing relevant pages of the tender and amendments, if any.
11 Acceptance of the tenders shall rest with the competent authority of AMC, who does not bind
himself to accept the lowest tender.
12 The Technical Bid containing Vol-I (technical bids only) from the tenderer received, shall be
openedin the presence of the tenderer’s representativesat the time and date mentioned in
tender notice and the technical tenders shall be scrutinized by AMC for satisfying various
eligibility criteria prescribed for the tenderer for this work.
13 After this, the Financial Bids of only technically qualified tenderer who fulfils all eligibility
criteria as mentioned in tender will be opened. The actual date of opening of Vol-II (Financial
Bid) of tenders shall be communicated to technically qualifying tenderer only later after
scrutiny of tender documents.
14 Municipal Commissioner, AMC reserves the right
• To change, alter or to waive any technical or commercial terms, conditions and
• To reject all the tenders or the lowest or any other tender in part or full without
assigning any reason whatsoever
• For making changes / relaxation in eligibility criteria at any time
15 It must be clearly and distinctly understood that the conditions of contract and specifications
shall be rigidly enforced and no relaxation on the grounds of customs prevailing shall be
16 The Price quoted for work must be of Site / Store delivery of Corporation GST EXTRA as per Govt.
rules. Prices must be firm for this tender. Any additional Govt. tax changes will not be payable
to the Contractor for this tender.
17 Tender documents must be submitted as per original tender documents that published
in web site https://tender.nprocure.com. No Changes / Addition in any text, documents in
original tender documents are allowed, failing which tender is strictly rejected.
18 Errors and Discrepancies in Tenders
Should the Schedule of quantities and Rates filled in Vol-II (Financial Bid) be found to contain
any errors, or discrepancies, the owner / engineer shall not permit any tenderer to change the
substance or price of his tender after the tender opening.
In the event of any calculation error found in the BOQ in Rate, Quantity and Total amount then
In the event of any calculation error found in the BOQ in Rate, Quantity and Total amount then
lowest amount will be considered among following calculation (For Qty mentioned in Vol-II –
Scheduled Quantity only)
• Amount of Multiplication of Filled Rate and Quantity of particular item.
• Amount Written in cell of total calculated amount of particular item.
However AMC decision is final in this case and contractor has no excuse for the same Also the
tenderer shall not be permitted to correct or withdraw material deviations or reservations
once tenders have been opened.
19 The tender for the work shall remain open for a period of 120 Calender days from the date of
opening of Price bid of tender and the tenderer shall not be allowed to withdraw or modify the
offer on his own during this period.
Any modifications or additions in terms and conditions of his tender will also not be accepted
by AMC.In such caseMunicipal Commissioner shall without prejudice to any right or remedy, be
at liberty to forfeit in full the said earnest money absolutely.
20 If the tenderer wishes to offer any discount in the event of this entire work being awarded to
him, he shall state so in the tender. Tender documents are not transferable.
21 Any Falsei nformation given in the Tender will invite invalidation of any Contract awarded on the
basis of such false information at the discretion of the employer.
22 If first lowest tenderer not able to work properly then AMC reserves the right to give same work
to second lowest tenderer as first lowest sanction rate. if second lowest is not agreed with first
lowest rate then AMC reserves the right to give same work to Third lowest tenderer as first
lowest sanction rate.
23 No Advance payment or Performa invoice payment or bank through payment will be considered
even if any discount is offered for the same.
24 After satisfactorily Work Completed & Certified by AMC Staff, Payment will be given to tenderer
as early as possible on submission of bill. Taxes will be deducted from bill as per rules and
25 Bidder shall have to submit Name of Bank, Name of branch with address, A/C. No., MICR No. and
PAN No. of his firm. for refund of E.M.D.
26 Material supplied shall be new and of first quality according to the specifications and shall be
free from defects (Including concealed fault, deficiency in design, material and workmanship.)
27 No tender will be received after last date and time of receiving tender.
28 Joint Venture and sub contract must not allow in this Tender.
29 A tenderer should quote in figures of each item, the rates of subtotal in figures .The grand total
29 A tenderer should quote in figures of each item, the rates of subtotal in figures .The grand total
shall be written in figure and words. The amount for each item should be worked out and the
requisite total given. Special care shall be taken to write figures as well as in words and the
amounts in figures only. The total amount shall be written both in figures and in words. In case
amounts in figures only. The total amount shall be written both in figures and in words. In case
of figures the words Rs. should be written before the figure of rupees and the words ‘paise’
after the decimal figure e.g. Rs. 2.15 p. and in case of words the words ‘Rupees’ should proceed
and the words ‘paise’ should be written at the end. Unless the rate is in whole rupees and
followed by the word ‘only’, it should invariably be up to two places of decimal.
30 A tenderer shall submit the tender who satisfies each and every condition laid down in this
notice and tender documents, failing which, the tender shall be liable to be rejected.
31 This notice of tender shall form part of the contract documents.
32 Tender shall be received by Registered Post A.D. or Speed post or Hand Delivery only at The
Office of Tender Office, Central Record Office, Mezzanine Floor “B”-Block, Sardar Patel Bhavan,
Ahmedabad Municipal Corporation, Danapith,Ahmedabad – 380 001, Gujarat (INDIA) and
technical tender shall be opened as prescribed date and time in the presence of tenderer who
may be present. The tenderer shall submit their tender before the last date & time mentioned
elsewhere. The tenderer shall take caution to submit their tender well in advance to avoid rush
in tender officer.
33 The tenders shall be received under Registered Post A D/ Speed post / in persons, should not be
adopted under the circumstances.
(i)Late tenders (i.e. tender received after the specified time of opening), delayed tenders(i.e. tenders
received before the time of opening but after due date and time of receipt of tenders) and post
tender offers shall not be opened and considered at all.
(ii) The tenders received (by registered post) after the time and the date specified in the tender
notice shall not be received by the concerned office from the postmen, for which, date and
time may be recorded on the cover of the tender as to when tender was refused by the concern
officer or Administrative Head or any other person in charge.
(iii)Necessary records should be maintained for refusal of such tenders in the registers for receiving
tenders and should be initialed by tender officer, Administrative Head or any other person in
34 On the occurrence of any accident on site while working, which results in death of workman,
employed by the contractor or any disability likely to be occurred, in respect of which
compensation may become payable under workmen's compensation Act has to be borne by
the Tenderer. AMC is not responsible for the same.During the work, if any damage is done to
the AMC property than it will be in the scope &responsibility of the contractor to overcome the
same at his own cost; failing which the amount will be recovered from the contractor’s bill.
Persons tendering are informed that no erasures or alterationsby them in the text of the
document sent herewith shall be allowed and any such erasures or alterations shall be
disregard. If there is any error in writing, no overwriting should be done, the wrong word or a
figure should be struck out and the correct one written above or near it in unambiguous way.
Each correction should be initialed.
36 All Corrections and additions or pasted slips must be initialed.
37 The Insurance Company’s bond will not be accepted against the security deposit.
38 TENDER SHALL BE LIABLE TO BE REJECTED
• Not more than one tender shall be submitted by contractor or by a firm of contractors. no two
or more concerns in which an individual is interest as a proprietor and /or a partner&/or
director shall submit tender for the execution of the same work/tender. If they do so all such
tender shall be liable to be rejected.
• DISQUALIFICATION:
-Even though the applicants meet the required criteria,they are subject to be disqualified if applicant
or any of its constituent partner/s,director/s have :-misleading or false representation in the
forms,statements and attachments submitted;or -been debarred or terminatedor blacklisted by
central govt.organization/state Govt.organization/AMC/Any municipal corporation/ULBs etc.
- If,any of the directors,partners of the proprietor has a criminal history or has been convicted by any
court of law of any of the offenses under any Indian laws.
- If,any criminal proceeding is pending in any court of law in India against any of the directors,partners
or a proprietor and if any such proceeding culminates into conviction.
39 Interpretation of Documents
Tenderer shall carefully examine the Tender Documents and fully inform themselves as to all the
conditions and matters which may in any way affect the work or the cost thereof. Should a tenderer
find discrepancies in or omission from the specification or other documents, or should be in doubt as
to their meaning, he/she should at once address a query to the Additional Chief Engineer (Electrical),
5th Floor,” C”-Block, Sardar Patel Bhavan,Danapith,Ahmedabad-380 001. Any resulting interpretation
of the Tender Documents shall be issued to all tenderers as an Addendum. Verbal clarification and /
or information given by the any employee/officer of AMC shall not be binding on the AMC.
40 It shall be incumbent on the successful tenderer to pay stamp duty on the contract and legal
cvcharges for preparation of the contract agreement.
41 Payment terms:-
For SITC of HVAC Work:
(a) On Delivery : 70% of the contract price shall be paid on receipt of satisfactory Goods and upon
submission of the documents from tenderer.
(b) On Installation : 20% of the contract price shall be paid on completion of mechanical Installation
(c) Successful Testing &Commissioning On Final Acceptance : The remaining 10% of the contract price
shall be paid to the Contractor against Testing &commissioning of the complete system after
satisfactory competition trial Run for 1 Month and handed over SITC work to AMC.
42 Secure HVAC equipment premises with preventing entry of unauthorized persons, fatal or non fatal
accident, and illegal and anti social activities. Tenderer will have to file FIR at nearest Police Station if
any HVAC related equipments are stolen from the Building. The copy of FIR should be submitted in
the department immediately. If any thefts occurred than said amount shall be deducted from the
assign bill and in that case Contractor shall be responsible for any police case, court case or any type
of compensation suit filed by any person, institute, or government.
43 Tenderer shall have to furnish a list of adequately qualified personnel with him & have well furnished
workshop. The full detail must be given with the tender.
44 Tenderer must provide PF and GST Registration certificates along with Tender. Copy of Latest GST
Return and latest PF Challan attached with Tender.
45 Award to Contract : The Contractor who has filled overall lowest price of BOQ items will be consider
46 Municipal Commissioner has reserves the right to reject all the tenders or the lowest or any other
tender in part or full without assigning any reason whatsoever or to split the tenders and award to
one or more than one tenderer in the interest of public. The tenderer shall have no cause of action or
47 If due to any reason, payment is delayed then tenderer is not eligible to claim/demand any
compensation for loss of interest there of.
48 To remove all debris accumulated at site from excavation & construction work or any kind of waste
material from site as per instruction of Engineer incharge without any extra cost.
49 The bidder is required to check the website https://tender.nprocure.com for Addendum if any
before 48 hours of last date and time of tender submission. The bidder who quotes the bid without
attaching the addendum shall be rejected.
Addendum is a part of tender and the tenderer who quotes the tender without attaching the
addendum will be rejected.
I/We hereby do certify that I /We have read above instruction 1 to
carefully and understood very well and taken into account while tendering and have
quoted our firm price accordingly.
Signature of the Tenderer Addl. Chief Engineer
Name : (Electrical)
Company’s seal AMC
ELIGIBILITY CRITERIA FOR TENDERER
Qualification shall be based on meeting all the following minimum pass/fail criteria
regarding the Supplier’s general and particular experience, personnel and financial
position, as demonstrated by the bidder’s responses in the forms attached. The AMC
reserves the right to waive minor deviations, if they do not materially affect the capability
of a bidder to perform the contract.
1. Tenderer must have to Pay Tender Fee of Rs.2400/- through Demand Draft only in
favour of “Municipal Commissioner, AMC” payable at Ahmedabad from banks
mentioned in Annexure-I only with their tender documents.
2. Tenderer must have to Pay EMD of Rs.1,00,000/- through Demand Draft OR Bank
Guarantee only in favour of “Municipal Commissioner, AMC” payable at Ahmedabad
from banks mentioned in Annexure-I only with their tender documents.
3. Tenderer should be original manufacturer or Authorized distributer/dealers for
Ductable & Cassette A.C. and having experience of such/similar type of work for the
same in various types of Erection and Commissioning at various Places.(Latest
authorization certificate must be attached along with tender).
4. Tenderer must have minimum experience of satisfactory work completion of one
year for such/similar type of work at various Places in any Central/State
Government/Semi Government/Municipal Corporation during last 7 years ending last
day of month previous to the one in which Tender are invited should be either of
Tenderer must have atleast
One similar type of work order completed of Rs.80.00 Lakh (80% of tender amount)
Two similar type of work orders completed of Rs.50.00 lakh (50 % of tender amount)
Three similar type of work orders completed of Rs.40.00 lakh (40 % of tender
amount) in any Central/State Government/Semi Government/Municipal Corporation.
(Private contracts like society, clubs etc. will not be considered).
• Similar work means S.I.T.C. of Ductable/Cassette/Package/VRV/Chiller A.C. Plant
contract work done by the contractor.
• Copy of work order along with satisfactory Work Completion Certificate must be
submitted by the Tenderer.
• All certificates / evidence must be duly certified & attached by the Tenderer. All work
/ experience details must be furnished with attested copies for evidence.
• Tenderer must have also experience of AHU with ducting installation work.
5. Tenderer must have sound financial capacity and having average annual financial
turnover in last three financial years shall not be less than Rs. 30.00 Lakh. (Note : The
CA certified turnover certificate & Audited balance sheets for the last three financial
years must be submitted.)
6. The Tenderer must submit a solvency certificate from a Nationalized Bank/scheduled
Bank of an Amount of Rs. 20.00 lakh (20 % of estimated cost of tender). Bank
Solvency shall not be older than one year period.
7. Litigation History:
he bidder should provide accurate information on any litigation history or arbitration
resulting from contracts completed or under execution by him over the last 10 years.
This should also include such cases, which are in process / progress. A consistent
history of awards against the bidder or any partner of a firm may result in failure of
the bid. In case the bidder has not provided such information and has come to the
notice of the authority, the bid shall be rejected at whatsoever stage and in such
case all the losses that will arise out of this issue will be recovered from the
bidder/contractor and he shall not have any claim for the same.
Signature of the Tenderer Add. Chief Engineer
Name : (Electrical)
Company’s seal AMC
GENERAL CONDITIONS OF CONTRACT
The Goods supplied under this Contract shall conform to the standards mentioned in the Technical
Specifications, and, when no applicable standard is mentioned, to the authoritative standard
appropriate to the Good’s country of origin and such standards shall be the latest issued by the
concerned institution.
2.0 INSPECTIONS AND TESTS
2.1 The Purchaser or its representative consultant shall have the right to inspect and / or to test the Goods
to confirm their conformity to the Contract. The special conditions of contract and / or the Technical
Specification shall specify what inspections and tests the Purchaser requires and where they are to be
conducted. The Purchaser shall notify the Tenderer in writing of the identity of any representatives
retained for these purposes.
2.2 The inspections and tests may be conducted on the premises of the Tenderer or its subcontractor(s),
at point of delivery and / or at the Good’s final destination. Where conducted on the premises of the
Tenderer or its subcontractor(s), all reasonable facilities and assistance (including access to drawings
and production data) shall be furnished to the inspectors at no charge to the Purchaser.
2.3 Should any inspected or tested Goods fail to conform to the Specifications, the Purchaser may reject
them and the Tenderer shall either replace the rejected Goods or make all alterations necessary to
meet specification requirements free of cost to the Purchaser.
2.4 The Purchaser’s right to inspect, test and, where necessary, reject the Gods after the Good’s arrival in
India shall in no way be limited or waived by reason of the Goods having previously been inspected,
tested and passed by the Purchaser or its representative prior to the Goods’ shipment from the country
2.5 Nothing in above clause shall in any way release the Tenderer from any warranty or other obligations
under this Contract.
3.1 The Tenderer shall provide such packing of the Goods as is required to prevent their damage or
deterioration during transit to their final destination as indicated in the Contract. The packing shall be
sufficient to withstand, without limitation, rough handling during transit and exposure to extreme
temperatures, salt and precipitation during transit and open storage. Packing case size and weights
shall take into consideration, where appropriate, the remoteness of the Good’s final destination and
the absence of heavy handling facilities at all points in transit.
3.2 The packing, marking and documentation within and outside the package shall comply strictly with
such special requirements as shall be expressly provided for in the Contract and, subject to Clause
in any subsequent instructions ordered by the Purchaser.
4.0 DELIVERY AND DOCUMENTS
The Supplier shall mail the following documents to the Purchaser :
(a) Copies of the Supplier invoice showing Goods description, quantity, unit price, total amount.
(a) Copies of the Supplier invoice showing Goods description, quantity, unit price, total amount.
(b) Delivery note / railway receipt / truck receipt;
(c) Manufacturer’s / Supplier’s guarantee certificate;
(d) Inspection Certificate issued by the nominated inspection agency and the Supplier’s
factory inspection report; and
(e) Certificate of origin.
The Goods supplied under the Contract shall be fully insured against loss or damage incidental to
manufacture or acquisition, transportation, storage and delivery in the manner specified in the Special
Conditions of Contract.
6.0 TRANSPORTATION
6.1 Where the Tenderer is required under the Contract to deliver the Goods, FOB, transport of the Goods,
up to and including the point of putting the Goods, up to and including the point of putting the Goods on
board the vessel at the specified port of loading, shall be arranged and paid for by the Tenderer, and
the cost thereof shall be included in the Contract Price.
6.2 Where the Tenderer is required to effect delivery under any other terms, for example, by post or to
another address in the source country, the Tenderer shall be required to meet all transport and storage
expenses until delivery.
7.1 The Tenderer warrants that the Goods supplied under the Contract are new, unused, of the most recent
or current models & incorporate all recent improvements in design & materials unless provided
otherwise in the Contractor. The Tenderer further warrants that the Goods supplied under this Contract
shall have no defect arising from design, materials or workmanship (except insofar as the design or
material is required by the Purchaser’s Specifications) or from any act or omission of the Tenderer, that
may develop under normal use of the supplied Goods in the conditions obtaining in India.
7.2 Defect Liability Period Entire work shall be12 months from date of completion of trial run for
1 months after date of satisfactorily completion and handed over SITC work
7.3 The Purchaser shall promptly notify the Tenderer in writing of any claims arising under this warranty.
7.4 Upon receipt of such notice, the Tenderer shall, with all reasonable speed, repair or replace the
defective Goods or parts thereof, without additional costs to the Purchaser other than, where
applicable, the cost of inland delivery of the repaired or replaced Goods or parts from the port of entry
to the final destination.
7.5 If the Tenderer, having been notified, fails to remedy the defect(s) within a reasonable period, the
Purchaser may proceed to take such remedial action as may be necessary, at the Tenderer's risk and
expense and without prejudice to any other rights which the Purchaser may have against the Tenderer
under the Contract.
In Warranty Maintenance :
(a) The contractor will give routine services for minimum 4 times in a year.
(b) The contractor will attend all the preventive and break down maintenance call without any labour or part
8.1 The method and conditions of payment to be made to the Tenderer under the Contract shall be done
after Satisfactory Work Completion & bill Submission by the Contractor of given Sub-order by Light
8.2 The currency in which payment is made to the Tenderer under this Contract shall be Indian Rupees.
Payment will be done to the party as soon as possible after bill Submission of S.I.T.C. Work of given
9.1 Prices charged by the Tenderer for Goods delivered and Services performed under the Contract shall
be fixed price without any price adjustment.
10.0 SUBCONTRACT
10.1 The Tenderer shall notify the Purchaser in writing of all subcontracts awarded under the Contract if not
already specified in his Tender. Such notification, in his original Tender or later, shall not relieve the
Tenderer from any liability or obligation under the Contract.
11.0 DELAYS IN THE TENDERER’S PERFORMANCE
11.1 Delivery of the Goods and performance of Services shall be made by the Tenderer in accordance with
the time schedule specified by the Purchaser.
11.2 An unexcused delay by the Tenderer in the performance of its delivery obligations shall render the
Tenderer liable to any or all of the following sanctions: forfeiture of its performance security, imposition
of liquidated damages, and / or termination of the Contract for default.
11.3 If at any time during performance of the Contract, the Tenderer or its subcontractor (s) should
encounter conditions impending timely delivery of the Goods and performance of Services, the
Tenderer shall promptly notify the Purchaser in writing of the fact of the delay, its likely duration and its
cause(s). As soon as practicable after receipt of the Tenderer’s notice, the Purchaser shall evaluate the
situation and may at its discretion extend the Tenderer’s time for performance, in which case the
extension shall be ratified by the parties by amendment of the Contract.
12.0 TERMINATION FOR DEFAULT
The Purchaser may, without prejudice to any other remedy for breach of contract, by written notice of
default sent to the Tenderer, terminate the Contract in whole or in part:
13.0 APPLICABLE LAW
The Contract shall be interpreted in accordance with the Indian laws.
14.1 Any notice given by one party to the other pursuant to the Contract shall be sent in writing (or by
telegram / telex / fax and confirmed in writing) to the address specified for that purpose in the Special
Conditions of Contract.
14.2 Any notice shall be effective when delivered or on the notice’s effective date, whichever is later.
15.0 TAXES AND DUTIES
The Price quoted for work must be of Site / Store delivery of Corporation with including applicable all
types of Govt. taxes. Prices must be firm. No any tax changes given to the contractor during contract
16.0 CHILD LABOUR ACT :
16.1 No Contractor shall employ any child heaving age 5 years to 14 years, as it is prohibited by the Child
Labour Prohibition and Regulation Act, 1986. The Hon. Supreme Court has given certain guidelines
and as per the guidelines, if employment of child labour is detected on the site work, the employer i.e.
the Contract shall have to deposit Rs. 20,000/- (Rupees Twenty Thousand only) in the Child Labour
welfare Fund. If the employer refuses to deposit, then action will be taken for contempt of Court of the
Supreme Court Judgment and also will be prosecuted by the concerned authority.
16.2 Because of the breach of any provision of the Child Labour Prohibition and Regulation Act, 1986, by
the Contractor and for that Municipal Corporation has to pay any amount, then the Municipal
Corporation shall recover the said amount from the Contractor.
17.0 BRAND NAMES
17.1 The make of equipments shall be as per attached list. If make of a particular item is not given in the
tender, then prior approval of AMC for that make must be required
17.2 Bidder must clearly mention make of AC,Ventilation Fans, Panels etc. and its catalogue no if any, name
and full address of the manufacturers must be submitted with the tender.
18.0 EQUIPMENT FOR EXECUTION
To expedite the execution work, the contractor has to submit a complete list of equipment he proposes
to deploy on this work along with the tender. Tenderer not complying with this requirement may be
considered non-responsive and his tender is liable to be rejected.
19.0 INSURANCE:
19.1 The Goods supplied under the Contract shall be fully insured against loss or damage incidental to
manufacture or acquisition, transportation, storage and delivery in the manner specified in the Special
Conditions of Contract.
19.2 This warranty shall remain valid for 12 months after the taking over of complete working AC System
fully or any portion thereof as the case may be, have been delivered, erected and commissioned to the
final destination indicated in the Contract, unless specified otherwise in the Special Conditions of
20.0 EXTRA ITEM OF WORK
20.1 The extra work beyond tender item, if required to be executed during course of execution of regular
work, that shall have to be carried out by the contractor as per the instructions and satisfaction of the
Engineer–in-charge. This will be paid separately as per detail rate analysis made by the department
based on market rate or prevalent SOR whichever is less.
20.2 If in the interest of the AMC it is necessary to change either any site or the design of the proposed work
the Contractor shall carry out the same at his quoted rates without charging any extra and he will be
paid at the rates quoted by him and no claim for extra amount for subsequent changes made will be
21.0 MEASURMENT OF WORK
21.1 The measurements of work will be taken according to the usual method in use in the Ahmedabad
Municipal Corporation and no proposals to adopt alternative methods will be accepted. The Concerned
Additional Chief Engineer’s decision as to what is ‘the usual method in use in the Ahmedabad
Municipal Corporation’ will be final.
21.2 The Contractor shall submit all the bills on the printed forms to be had on application at the office of the
Engineer-in-Charge. The charges to be made in the bills shall always be entered at the rates specified
in the agreement or at the part/reduced rates subject to the approval by the Engineer-in-Charge in the
case of items not completed/executed as per agreements or in the case of any extra work ordered in
pursuance of these conditions and not mentioned or provided for in the tender, at the rate hereinafter
provided for such work.
Quantity indicated in the Bill Of Quantity can be change as per Site Requirement and the same will be
considered on actual for making payments from the same.
22.0 NO CLAIM TO ANY PAYMENT OR FOR RESTRICTION OF WORK: .
22.1 In the case of such delay in the supply of materials, Ahmedabad Municipal Corporation shall grant such
extension of time for the completion of the works as shall appear to the Engineer-in-Charge to be
reasonable to accordance with the circumstances of the case. The decision of the Engineer-in-Charge
as the extension of time shall be accepted as final by the Contractors.
22.2 Action and compensation in case of bad work : If, at any time before the expiry of defects
Liability,period, it shall appear to the Engineer-in-charge or his sub-ordinate in charge of the work, that
any work has been executed with unsound, imperfect or unskilled workmanship or with materials or
inferior quality or that any materials or articles provided by him for the execution of the work are
unsound, or of a quality inferior to that contracted for or are otherwise not in accordance with the
contract, it shall be lawful for the Engineer-in-Charge to intimate this fact in writing to the Contractor and
then notwithstanding the fact that the work, materials or articles complained of, may have been passed,
certified and paid for, the Contractor shall be bound forthwith to rectify, or remove and reconstruct the
work so specified in whole or in part as the case may require, or if so required shall remove the
materials or articles so specified in whole or in part and provide other proper and suitable materials or
articles at his own charge and cost, and in the event of his failing to do so within a period to be specified
by the Engineer-in-charge in the written intimation aforesaid, the Contractor shall be liable to pay
compensation at the rate of one percent on the amount of the estimate of the rectification for every day
not exceeding ten days during which the failure so continues, and in the event of any such failure as
aforesaid continuing beyond ten days, the Engineer-in-charge may rectify or remove, and re-execute
the work or remove and replace the materials complained of, as the case may be at the risk and
expense in all respects of the Contractor should the Engineer-in-charge consider that any such inferior
work of materials as described above may be accepted or made use of, it shall be within his discretion
to accept the same at such reduced rates as he may fix therefore,
However, the contractor shall be responsible for normal maintenance of the work till the final bill for the
work is prepared by the corporation officer.
23.0 SETTING OUT THE WORKS
The Contractor shall be responsible for the true and proper setting out of the works in relation to original
points, lines and levels of reference given by the Engineer in writing or shown on the Drawings and for
correctness, subject as above mentioned in the position, levels, dimensions and alignment of all parts
of the works and for the provision of all necessary instruments, appliances and labour in connection
24.0 SAFETY MEASURES AND SERVICES
24.1 The Contractor shall be responsible for the safety of all workmen and other persons entering or in the
works and shall take all measures necessary to ensure their safety to the approval of the Engineer’s
Representative. Reference in these respects shall also be made to the Conditions of Contract and
safety provisions but in particular, such measures shall include the following :
(a) Provision of proper safety and emergency regulations’ fire, gas and electric shock precautions,
stretchers, first-aid box and fire extinguisher together with rescue facilities generally for each place of
(b) Provision of efficient safety helmets for all personnel including the Engineer’s Representative and each
of his staff and any authorized visitors to site;
(c) Safe control of water including provision of ample standby generating and pumping plant;
(d) Provision and maintenance of suitable lighting to provide adequate illumination of works with
appropriate spares and standby equipment;
(e) Provision and maintenance of safe, sound mechanical equipment, each item of plant having an up-to-
date testing certificates ;
(f) Provision and maintenance of safe, sound, ropes, slings, pulleys and other lifting tackle, each appliance
having an up-to-date testing certificate where appropriate;
(g) Provision of notices 1.25 m x 1.5 m size written in bold letters in English, Gujarati and Hindi to be
erected on existing footpaths and at points of access likely to be used by the pubic, which shall warn
the public of the Works. These notices shall be in addition to any statutory requirements demanded of
the Contractor.
24.2 Contractor shall provide and maintain at his own expenses all lights, guards, fencing and necessary
watchmen when and where necessary or ad required by Owner / Engineer for the protection of the
works or for the safety and convenience of those employed on the works and the public. Contractor
shall also provide at his cost traffic barricades, men for diverting and controlling traffic, necessary sign
boards for diversion of traffic. In the event of failure on the part of Contractor, Owner man with or
without notice to Contractor put up a fence or improve a fence already put up or provide and/or improve
the lighting or adopt such other measures as he may deem necessary, and all the cost of such work
and procedures as may be adopted by Owner / Engineer shall be borne by Contractor. Maintenance of
adequate warning and general lighting at nights a t place of work is essential.
24.3 Contractor shall take the necessary permission and clearance of all the authorities like department of
Roads, traffic, Water Supply and Drainage; Electricity Board, Telephone Company, etc. Wherever
necessary and observe the regulations regarding the execution of work in congested areas, heavy
traffic areas, etc.
25.0 LIABILITY OF ACCIDENTS TO PERSONS:
Responsibilities and liabilities of the contractor under Workmen’s Compensation Act.
(a) On the occurrence of an accident, which results in death of workmen employed by the contractor or
which is so serious as is likely to result in death of any such workmen, the Contractor, shall within
hours of happening of such accident(s) intimate, in writing, to the Engineer in charge the fact of such
(b) In the case of an accident, in respect of which compensation may become payable under Workmen’s
Compensation Act, It must be payable by the Contractor only.
(c) In any of such accident the contractor shall have sole responsibility of all the consequences like police
case, accident compensation to the work man, hospitalized expense of the work man and any other
implication may arise then after.
26.0 CLEARING SITE ON COMPLETION
26.1 On completion of the Works, the Contractor shall clear away and remove from the site all
Constructional Plant, surplus materials, rubbish, Temporary Works of every kind and leave the whole of
the site and the works clean and in a workmanlike condition to the satisfaction of the Engineer.
26.2 The Contractor shall comply with the above requirements before the start of the Defects Liability Period
and by the end of that period shall clear, regrade terrace, level topsoil and grass all his working areas
as instructed by the Engineer’s Representative. No separate payment shall be made on his account.
27.0 COMPLETION PERIOD :
Work Completion Period will be strictly 60 Days from the Date of Work Sub-Order given
Subject to Site Clearance.
29.0 Tenderer has to provide PF and GST Registration certificates along with Tender. Copy of
Latest GST Return and latest PF Challan attached with Tender.
30.0 PENALTY CLAUSE :
For SITC Work :
The Delayed Work of given S.I.T.C. will attract Penalty @ 0.1% per Day for remaining work up to
maximum of 10 % on the value of remaining S.I.T.C. work (Sub-order Work) that not completed in Time
Limit. Completion period for S.I.T.C. work in the tender will be 60 days subject to site clearance.
Signature of the Tenderer Addl. Chief Engineer
Name : (Electrical)
Company’s seal AMC
TECHNICAL SPECIFICATIONS
1.0 ECBC Compliance:
The proposed HVAC system design complies to following ECBC norms (Code 2009) which
shall be complied by bidder in their offered equipments:
a. Energy Efficient Variable Refrigerant Flow System offered is having minimum COP
b. All cooling equipment operations are regulated based on indoor temperatures.
c. All areas shall have independent control for operation and temperature settings.
d. Resistivity ( R ) of insulation material for pipes is more than 0.35.
e. Under deck insulation having U VALUE OF 0.12 BTU/HR./DEG C
2.0 SCOPE OF WORK AND BASIS OF DESIGN
2.1 BROAD SCOPE
The scope of this Tender covers Engineering , Design, Manufacturing / Fabrication, Shop
testing, Supply, Installation (including dismantling, lifting, shifting, assembling etc.), Site
testing, and Commissioning of the following system components (confirming to tender
specifications, relevant ASHRAE codes and in accordance with the requirements of Bill of
quantities and approved drawings) for HVAC SYSTEM proposed for Hospital Building.
The condensing unit shall be of Corrosion resistant Galvanized powder coated or equivalent
paint Sheet steel low vibration assembly installed on suitable vibration isolators and
comprising of energy efficient Scroll compressor with controls such as thermal protector,
HP/LP cut-outs, Pressure relief valve; the outdoor unit shall also comprise of finned tube air
cooled condenser and condenser fan unit; the units shall have integral refrigerant copper
piping within compressor and condenser and accessories such as refrigerant shutoff valves
at compressor / compressors and liquid refrigerant outlet if required & filter dryer; Cooling
fans shall have protective metal frame.
HVAC JOB Scope Covers:
SITC of Ductable & Cassette type Split Air Conditioning System Associated electrical work.
All quantities mentioned in the Bill of quantity are approximate and the contractor shall not
be eligible for any claim due to any variation in / or omission of any item.
Any extra item shall be calculated on the rate analysis basis on Market Rate or Old Tender Rate.
After completion of work 1 Year Guarantee Period / Defects Liability Period.
2.3 BASIS OF DESIGN & EQUIPMENTS
Proposed system / system components offered shall have:
Higher efficiency & Co-efficient of Performance.
Minimum power consumption, efficient parts load operation.
Ease of operation and maintenance.
Minimum vibration and noise level.
Reliability, Simplicity, Compactness, Modularity and Interchangeability.
Better Environmental protection and Indoor Air Quality.
Prevent frosting on coil & maintain cooling efficiency.
Reduce inrush current & energy efficient
SPECIFICATION OF OUTDOOR UNITS
Outdoor units of the system shall be compact air cooled type.
Outdoor Units Condenser must be made with Copper metal.
The outdoor units shall be suitable to operate in the higher Ambient requirement of Ahmedabad.
Noise level of outdoor units shall not exceed 70 dB (A) at a distance of 1.0 m from the unit.
Noise level of Indoor Unit shall not exceed 44 Db at a distance of 1.5m.
Outdoor units shall be complete with following safety devices:
High pressure / Low Pressure Protection
Fan driver overload protector Over
Inverter Overload Protector / Digital Protector Fusible Plug
Unit shall be supplied with
Installation manual Operation Manual Connection Pipes Clamps
Units will use R-410, R-407, R134, R32 like Refrigerant gas.
TECHNICAL SPECIFICATION OF PACKAGE AIR-CONDITIONING UNITS
Scope of Supply
The scope of supply shall include package air conditioning units shall be delivered for each power unit as per this
specification and standard.
Package Air Conditioning Unit shall be delivered with air cooled condenser. The scope of supply for package air
conditioning unit shall include all the items required for reliable, safe and unattended trouble free operation consisting of
a) Inner evaporator unit/air cooler unit with moisture separator.
b) An outer compressor and condenser unit.
c) Installation Manual for routing of the refrigerant piping.
d) Operation and Maintenance Manual from OEM.
e) Manufacturer’s certificate on the packaged air conditioner.
2.0 APPLICABLE CODES AND STANDARDS
Following codes & standards will be followed:
AMCA201 Fan & systems
AMCA210 Laboratory Method for testing of fans
IS8148 Package Air conditioner
ASHRAE37 Standard method for testing for rating
ANSI-B9-1/IS660 Safety code for mechanical refrigeration
AMCA2404 Drive arrangement for fans
BS2827 Specification for Copper & Copper alloy tubes
IS8148:2003 Packaged Air conditioner-Specification for performance
2.0 GENERAL FUNCTION AND DESCRIPTION
General Function
Package Air Conditioning Units are intended for heat removal from operating
equipment, cooling and air de-dusting in the rooms and the compartments of the
buildings of nuclear power plant.
An air conditioning unit utilizes the vapor compression refrigeration cycle to cool
refrigerant and reject the heat collected from the refrigerant plus the heat from the
compressor to ambient air.
Ozone-safe/ eco-friendly refrigerant is to be used in the Air Conditioning Units.
During operation the refrigerant is compressed in compressor from evaporation
pressure up to condensation pressure. Thereafter it comes into condenser, where it is
cooled and condensed by ambient air. Then liquefied refrigerant is further cooled by
throttling and comes into evaporator. In the evaporator the refrigerant gets heated
and evaporated owing to the heat, taken from the air-conditioned area.
Package AC is bigger version of common window/ split ac having higher cooling rates.
Units are intended for heat removal from operating equipment, cooling and air de-
dusting in the rooms and the compartments of the buildings of nuclear power plant.
Air cooled package air conditioner (PAC) units having scroll compressor are envisaged
to cater to the air conditioning load.
The packaged indoor evaporative units shall be kept in PAC room where as
condensing unit shall be kept outside the PAC Room /Passage area / Roof. Outlet of
all the package units shall be collected in a common plenum chamber through flexible
canvass connection & volume control dampers. The conditioned air is the n
distributed to various AC areas through duct along with diffuser(with volume control
damper) running above false ceiling. The return air from all these areas shall be
collected above false ceiling & shall be taken back to the PAC room.
The PACs shall consist of:-
i) Scroll compressors suitable for refrigerantR-410A /R 32/ R407C /R134 with drive
motor, air-cooled condenser with integrally groove copper tubes and propeller
fan, DIDW blower, cooling coil, filter, inter connecting refrigerant piping,
insulation, vibration isolator, inbuilt – microprocessor-based controller and
ii) Vibration isolation pads.
iii) First charge of refrigerant and oil.
Terminal points
• Packaged air-conditioner outlet flange connections
• Theterminalpointof380V.3phasepowersupplyforeachPAC’swillbeuptothe PAC’s
3) Control & Instrumentation
• Air conditioners in case of restoration of voltage after deenergization shall continue
operation without any repeat of activation by the operator.
• Following protective function shall be there for package airconditioners:-
Increaseofpump-inpressureorsuctionpressuredecreaseinthecompressor.
Decrease of pressure difference in the greasing system and in the compressor
Protective function of the fan with increase of a current of the electric motor of
Protection against an electro heater over heat (at temperature excess above95°С)
Pressure difference increase on the air filter of the conditioner
Protection at drainage failure
Protection at increase of a current of the electric motor of the compressor
Allows adjustment of temperature set points, range of control.
System Auto Restart-The auto restart feature will automatically restart the
system after power failure. Time delay is programmable.
Safety interlocks between condenser and compressor and time delay for restart
of compressors.
Control panel of the air conditioner the following signals for display on the
central control post should be provided:
i. Activated state of the conditioner
ii. The disconnected state of the conditioner
iii. Activation of ALT
iv. Mal function of the conditioner by the generalised signal
The scheme of automatics of conditioners should provide realization between
the standby conditioners and disconnection of conditioners in case of a fire in
the premise where they are installed with disabling of connection, including
disabling of connection of ALT(Automatic load transfer).
Alarm system on the central control post depending on the
connected/disconnected condition of the conditioner and the causes of its
emergency fail should be activated by the break-make contacts, integrated in
the directcurrentline24V/48Vwiththecurrentrunningthroughtheclosed contacts
from 1 to 400 mА.
REQUIREMENT FOR OPERATION
Air conditioning unit shall be manufactured, tested, operated by specialists duly
qualified as per appropriate qualification standards and permitted to do the job.
The design of the system must ensure the possibility of repair with replacement, if
necessary, of individual elements and parts during maintenance of the NPP
equipment under field conditions.
Air conditioning units shall be resistant to ambient conditions, as specified in this
All air conditioning units shall conform to energy efficiency norms with highest
energy rating and have minimum specific energy consumption. Blue fin can be
adopted by vendor for performance improvement of AC.
GENERAL DESIGN REQUIREMENTS
Design of Air Conditioning Unit shall be based on as per latest technology available in
the market. All possible upgrades shall be incorporated with prior approval. The
design of the system must ensure the following
• Maintaining the preset temperature conditions inside the premises.
• Alltheequipmentshallbecapableofwithstandingthestresses,whichmaybe experienced
during normal operation and test
• All the equipment shall be designed to permit inter-changeability of parts and ease
of access during inspection, maintenance, installation and repair of various parts.
• Refrigerant shall be environment friendly having ClassI/ClassII flammability as per
ISO 817 or other equivalent standard.For identification & detection of leak there
must be dedicated refrigerant leak detection system.
Allowed level of noise from Air Conditioning Unit shall not higher than 85 dB(A) of
total proportional value at the distance of 1 m from equipment.
All the surfaces of air conditioners shall be protected with corrosion-resistant
coating/epoxy coating. Life of corrosion-resistant coating shall be the entire life of
the conditioner.
The compressor shall be hermetic/semi-hermetic scroll type.The same shall be
suitable for R410A/ R32/ R407c refrigerant. The compressor shall be mounted on
anti- vibration spring/rubber pads and shall be positioned in such a way that it is
freely accessible with sufficient space all around for easy maintenance. Safety
controls like High and Low pressure cut-out overload and single phasing protection
for the motors shall be provided. A crankcase heater shall also be provided, if
considered necessary by the vendor.
Evaporator and Condenser
Air cooled condenser with adequate area shall be provided. The condensing unit
shall be complete with multi-pass heads and shall be fitted with the following:
Fan with drive motor, hot gas inlet and liquid outlet connection with shut off valve
for liquid , drain plug, air vent and test valve.
Air Handling Fan & filter
The air handling fan shall be of the centrifugal type and with forward curved blades.
This shall be driven by means of at Three phase induction motor through V belt drive.
The fan static pressure shall be selected for passing air through high efficiency filters.
The cooling coil shall be of direct expansion type and shall be made of heavy gauge
copper with aluminum fins/blue fins. The fins shall be bonded to the copper tubes
under hydraulic pressure.A distributor shall be provided for feeding the refrigerant to
different sections of the coil. Rows shall be staggered in the directions of airflow. The
velocity of air across coil shall not exceed 2.5 m/s.
Refrigerant Piping
The refrigerant piping shall be either heavy gauge copper .The piping shall be
completely factory assembled, pressure tested, dehydrated and initially charged with
refrigerant gas and compressor oil. The line accessories shall include liquid line
shutoff valve dehydrator, strainer, flow indicator and distributor etc.
All the equipment, except local control panel,mentioned above shall be provided
within a heavy gauge sheet metal cabinet, of floor/ wall mounted type. This shall be
given two coats of anti-corrosive and rust proof paint, finished with two coats of
final paint.Painting shall be as per manufacturers standard..The interior of the
cabinet shall be provided with thermal and acoustic insulation of minimum 25mm
thick. The insulating material shall be fire proof.
The front and back side of the cabinets shall be easily removable
providingmaintenance to all the interior parts.
All the electric wires within the cabinet shall run in flexible conduits and carry
identification tags.The bottom side of the panel shall be specially ribbed to take care
of the transportation.
Each packaged air conditioner shall be provided with required number of neoprene
rubber isolating pads. Suitable drain connection with drain pipe shall be provided
for removal of condensate collected in the tray under the cooling coil.
Cold Surface Insulation
Vendor to ensure that, outside surface temperature of the installed insulation shall
always be above the dew point temperature of the surrounding.Puff material
should not be used as insulation, vendor should ensure to use nitrile butadiene
rubber as insulator.
ELECTRICAL REQUIREMENT
Voltage of mains supply of Package air conditioners shall be380V,50Hz AC supply.
a) Deviations of voltage +/-10%.
b) Deviations of frequency+/-3%.
c) Combined frequency and voltage deviation not exceeding±10%.
d) Power shall be supplied via five-wirelines,depending on supply voltage ofair
conditioner (380 V).
Motors for Package air conditioners shall meet the following requirements:
Supplier shall describe actions and means assuring fire and electrical safety of the
article/equipment/system.
Either a terminal block or sealed terminal block shall be provided for connection of
Electrical insulation class of motor windings shall not be lower than with
temperature rise limited to class B.
Protection degree (IPClass)of the electrical equipment shall not be lowerthan IP55.
When supply voltage is restored after interruption, the Package air conditioner shall
be able to continue operation free of human action.
Inner control circuits and motors shall be protected in the Package air conditioner.
General performance test
Each PAC Package air conditioner shall be tested in the manufacturer’s works.
Performance test (except cooling capacity) of the PACs shall be as per applicable
standards and procedures approved by the Purchaser.
Inspection and testing at manufacturer’s works shall be carried out as covered
under this specification.
7.0 MARKING&IDENTIFICATION
Name plate shall be provided as per OEM standard.
Rating plate shall be provided as per OEM standard.
8.0 PACKING AND SHIPMENT
All equipment / material shall be protected for inland transport to Site and outdoor
storage during transit and at the Site, strictly according to the instructions give in
this Specification. The Vendor shall pack the Equipment and spares at his own cost
sufficiently and properly to ensure that they are free from loss or damage while in
transit to the ultimate destination. The Vendor shall be responsible for any damage
to the item during transit and storage in all climatic conditions due to improper and
inadequate packing.
Only packages constructed out of sound material and of dimensions ,proportional
to the size and weight of contents shall be used. Each package shall be limited to
the size and weight that are permissible under existing sea/rail/road transport
limitations as the case may be.
Bundled materials shall be strapped rigidly with steel band over the protective
covering. Loose materials, e.g. bolts, nuts, etc shall be packed in gunny bags sealed
in polythene bags with proper tagging.
All flanges and similar surfaces which are prone to scratching shall be provided with
either metal or wooden caps(to suit material of equipment) bolted in place .Metal
caps should have a minimum thickness of 3mm and woodencaps should be made
from two layers of wood, each of 10mm thickness, nailed together with the grain of
each layer located at right angles to the other.
All openings in the Equipment shall be tightly covered, plugged or capped to
prevent foreign material from entering.
In the case of large and bulky equipment, the Vendor shall be responsible for as
certaining transport limit ations and supply the Equipment in the minimum number
of components or sub-assemblies, within the frame work of transport limitations.
Wherever necessary, proper arrangement for attaching slings for lifting shall be
The contents of the packages (Packing slip) shall be sealed in thick polythene sheets
and all the inside walls of the packages shall be lined with water proof paper to
protect the Equipment from damage due to dust and moisture.
All machined and plated parts shall be protected with antirust grease.Precautions
shall be taken to protect shafts and journals where they rest on wooden or other
supports likely to contain moisture,at such points,wrappings impregnated with
antirust composition or vapour phase inhibitors shall beused.These shall have
Technical Specification of Ducted Split Units and D-X Condensing Units
SCOPE:The scope under this section shall cover the unitary refrigeration equipments such
as, Ducted Split Units and D-X Condensing Units.
The following standards shall be applicable
a) IS:4283 Hot air fans
b) IS:8272 Industrial cooling fans (man coolers)
c) IS:1391 Room Air conditioners
d) IS:8148 Packaged Airconditioners
e) IS:2997 Air circulator type electrical fan and regulator
f) IS:1169 Electrical pedestal type fans and regulators
g) IS:374 Electrical ceiling type fan and regulator
GENERAL REQUIREMENTS
The unitary air conditioners shall include Refrigeration compressor, Drive Motor, Air
cooled Condensing Unit, Evaporator, Refrigeration Piping, Automatic control system
The equipment assembly shall be well balanced to achieve minimum vibration and noise.
The condensing unit mounted outdoor shall be suitable for the climate and atmosphere
condition prevailing to avoid / minimize corrosion. Necessary anti corrosive treatments
shall be provided for the metallic components.
The equipments shall meet the requirements indicated in the equipment data and shall
meet the cooling load specified at the outdoor design data furnished and the distance /
static head between the outdoor and the indoor units.
ASSEMBELLED UNITS
The unitary Ductable air conditioning units shall be of factory assembled and tested
and of the following category as indicated on the drawing and bill of materials.
Ductable air conditioners having single unit to house compressor, condenser,
evaporator, refrigerant piping and control system.
a) Ductable airconditioners having compressor and control evaporated houses
in one unit and located indoor and condenser housed in another unit
located outdoor
b) The refrigerant 18G piping and power/control cabling inter connecting
condenser and the indoor unit laid externally.
The components for the various equipment assembly shall be as specified in the
following section.
The Compressor shall preferably be of hermetically sealed Scroll/Rotary/twin Rotary type
permanently lubricated . For Ductable systems compressor /shall be of either Digital
Scroll type OR Inverter type Rotary or Twin Rotary types.
The condenser shall be air cooled type consisting of copper tubes with Aluminium fins,
propeller fan with motor, sheet metal steel enclosure with air inlet and exhaust louvers
mounting frame, platform/ brackets etc. The condenser & all its components shall be
provided with suitable anticorrosive treatment. The enclosure shall be of GI / MS CRCA
duly powder coated.
The evaporators shall be ducted or non ducted concealed or exposed types as indicated in the
drawing and bill of quantities.The evaporators shall include coppertubes with aluminiumfins,
expansion valve, centrifugal fan with motor return air filter, supply and return air grilles and louvers,
automatic control panel with thermostat and enclosure. The enclosure for concealed unit shall be of
GI powder coated whereas that for exposed units shall be of ABS plastic The filters shall be anti
bacterial washable and shall be of minimum 10 micron filtration . The filters shall be easily
removable for cleaning / Washing.
The controls shall be with automatic digital electronic LCD display having the following
a) Automatic capacity control
b) Temperature and fan speed control with digital display
c) Timer control
d) Corded/cordless remote control wherever specified.
The control system features shall be as shown below:
Sr.No. Feature Standard Regular
1 Type of control Unit Mounted Remote Remote
2 Type of Remote Control Corded Corded
3 Temperature Setting Yes Yes
4 Fan Speed Selection Yes Yes
5 Timer Control Yes Yes
6 Digital Display Yes Yes
7 Delayed Starting Yes Yes
8 Filter Cleaning Indicator No Yes
9 Inbuilt–ON/OFF No No
10 Quick Cooling Machine No Yes
11 Auto reset No No
12 Auto fanspeed No No
13 Night set mode No Yes
14 Self Diagnosis No No
SUPPORTS & PIPING
Supports & Brackets
4.6.1. The equipment’s shall be properly supported with brackets, hangers, platforms, base
frame etc depending upon the type, location and capacity of the unit.
4.6.2 The supports shall be GI fabricated duly treated and painted for anti corrosion. The
outdoor condensing units shall be properly supported on MS frame work / platform
properly grouted to the RCC Slab / brick walls using bracket.
4.6.3. The Ducted AC unit shall be provided with base frame and pedestals with necessary anti
vibration pads. The ceiling suspended evaporator shall be support edusing anchor
fasteners and GI suspension rods. The wall-hung evaporators shall have GI tensiled back
plate for mounting the unit, grouted to the wall / beam using anchor fasteners.
REFRIGERANT PIPING
There refrigerant piping shall be of Soft/Hard copper RS 250 conforming to EN.1057Table
Y. The fittings shall be of shot end capillary brazing conforming to EN 1254.The pipes
shall be supplied in straight lengths and to be brazed to have required length to achieve
full length between the condenser and evaporator.
The fittings for connection to the condenser evaporator expansion valve etc shall be through
copper – brass composite fitting. The brazing / soldering material shall conform to EN.
4.7.3 There frigerant lines shall be insulated with 18mm thick black EPDM Rubber sleeves/tubing
faced with UV & Fire resistant Glass cloth coating and GI sheet cover to preven theat loss and
condensation .Refrigerant piping running along the partition wall shall be concealed in the
wall with necessary chasing in the wall and closing the same with sand cement plaster with
chicken wire mesh.
All joints in copper piping shall be sweat joints using low temperature brazing and / or silver
Before jointing any copper pipe or fittings, its interiors shall be thoroughly cleaned by passing
a clean cloth via wire or cable through its entire length. The piping shall be continuously kept
clean of dirt etc.
while constructing the joints. Subsequently, it shall be thoroughly blown out using carbon
dioxide / nitrogen. Refrigerant lines shall be sized to limit pressure drop between the
evaporator and condensing unit to less than 0.2 kg per sq.cm. After the refrigerant piping
installation has been completed, the refrigerant piping system shall be pressure tested using
Freon mixed with nitrogen / carbon dioxide at a pressure of 20 kg per sq. cm (high side) and
kg per sq. cm (low side). Pressure shall be maintained in the system for a minimum of
hours. The system shall then be evacuated to a minimum vacuum of 70 cm (500 microns) of
mercury and held for 24 hours. Vacuum shall be checked with a calibrated vacuum gage.
All refrigeration piping shall be installed strictly as per the instructions and recommendations of
air conditioning equipment manufacturer
The evaporator shall be piped to the nearest drain point / drain line using C-PVC
with 6 kg/cm2 pressure rating pipe conforming to 4985 Necessary water seal trap.
2.4 SPECIFICATIONS FOR INDOOR UNITS
HIGH STATIC DUCT TYPE UNITS
These units shall be floor mounted / ceiling suspended with suitable supports to take care of operating
weight of the unit, without causing any excessive vibration & noise. The cold air supplied by these units
will be supplied to the area to be air conditioned, through duct system specified in the tender.
The unit casing shall be Galvanized Steel Plate.
Unit must be insulated with sound absorbing thermal insulation material, Glass Fiber. The noise level
of unit at the highest operating level shall not exceed 44dB(A), at a vertical distance of 1.5 m below the
units with duct connected to the unit.
2.5 REFRIGERANT PIPING
a. All refrigerant pipes and fittings shall be hard drawn copper tubes and wrought copper / brass
fittings suitable for connection with silver solder / phos-copper.
b. All joints in copper piping shall be sweat joints using low temperature brazing and / or silver solder.
Before jointing any copper pipe or fittings, its interiors shall be thoroughly cleaned by passing a
clean cloth via wire or cable through its entire length. The piping shall be continuously kept clean of
dirt etc. while constructing the joints. Subsequently, it shall be thoroughly blown out using carbon
dioxide / nitrogen.
c. Refrigerant lines shall be sized to limit pressure drop between the evaporator and condensing unit
to less than 0.2 kg per sq.cm.
d. Sight glass with moisture indicator and removable type combination dryer cum filter with MS
housing and brass wire mesh / punched brass sheet shall be installed in liquid line of the
refrigeration system incorporating a three valve by pass. After ninety days of operation, liquid line
drier cartridges shall be replaced.
e. Heat exchanger shall be MS heavy duty pipe in pipe type and without any joint in the inner pipe.
f. Horizontal suction line shall be pitched towards the compressor and no reducers shall be provided
for proper oil return.
g. After the refrigerant piping installation has been completed, the refrigerant piping system shall be
pressure tested using Freon mixed with nitrogen / carbon dioxide at a pressure of 20 kg per sq. cm
(high side) and 10 kg per sq. cm (low side). Pressure shall be maintained in the system for a
minimum of 12 hours. The system shall then be evacuated to a minimum vacuum of 70 cm of
mercury and held for 24 hours. Vacuum shall be checked with a vacuum gage.
h. All refrigeration piping shall be installed strictly as per the instructions and recommendations of air
conditioning equipment manufacturer.
3.0 CODES AND STANDARDS
Ducts shall be made of either Galvanized sheets or Aluminum sheet & confirm to IS:
The Galvanized steel sheet shall confirm to IS: 277. Aluminum sheet shall confirm to IS: 737. The
duct construction shall be as follows:
3.1 RECTANGULAR G I DUCT CONSTRUCTION:
MAX. SIDE TYPE OF JOINT BRACING
Up to 750 24 22 flanges None
angle 22 20 angle 25 mm x 3 mm
MS 20 18 angle 40 mm x 3 mm at 1.25 m centers.
2251 & above 40 mm x 3 mm MS
MS 18 16 angle 40 mm x 3 mm at 1.25 m centers.
3.2 HANGERS FOR G I DUCT:
DUCT SIZE (MM) SPACING (M) SIZE OF ROD DIA. (MM)
4.0 G I DUCT INSTALLATION:
All ducts shall be fabricated and installed in workman like manner, generally confirming to IS: 655:
1963 updated. Round duct shall be die- formed for achieving perfect circle configuration.
Ducts shall be straight and smooth on the inside with neatly finished joints. All joints shall be made
All exposed ducts within conditioned spaces, shall have slip joints - no flanged joints. The internal
ends of slip joints shall be in the direction of air flow. Ducts and accessories within ceiling spaces,
visible from air-conditioned areas shall be provided with two coats of mat black finish paint.
Changes in the dimensions and shape of ducts shall be gradual. Air-turns shall be installed in all
vanes, arranged to permit the air to make the turn without appreciable turbulence.
Ducts shall be fabricated as per details shown on drawings. All ducts shall be rigid and adequately
supported where required standing seams, teas, or angles, of ample size to keep the ducts true to
shape and to prevent buckling, vibration or breathing.
All sheet metal connections, partitions and plenums required to confine the flow of air to and through
the filters and fans, shall be constructed of 18 G GSS / 16 G Aluminium, thoroughly stiffened with
25mmx25mmx3mm angle iron braces and fitted with all necessary inspection doors as required to
give access to all parts of the apparatus. Doors shall be not less than 45 cm x 45 cm in size.
Plenums shall be panel type and assembled at the site. Fixing of MS angle, iron flanges on duct
pieces shall be with rivets heads from inside and riveting shall be done from outside.
Rubber lining 6 mm thick shall be used between duct flanges instead of felt, in all clean room ducting
The contractor shall provide and neatly erect all sheet metal work as may be required to carry out the
intent of this specifications and drawings. The work shall meet with the approval of the engineer In-
charge at site in all it parts and details.
The contractor shall make all necessary provisions and allowances to avoid beams or other structural
work, plumbing or other pipes, and / or conduits, the ducts shall be transformed, divided or curved to
on a side, (the required area being maintained) all as per the site requirements.
If a duct can not be run as shown on the drawings, the contractor shall install the ducts between the
required points by any path available, in accordance with other services and as per approval of site
All ductwork shall be independently supported from building construction. All horizontal ducts shall be
rigidly and securely supported, in an approved manner, with trapeze hangers formed of MS rods and
Ducting over ceiling shall be supported from beams, after obtaining approval of site engineer. In no
case shall any duct be supported from false ceiling hangers or be permitted to rest on false ceiling.
Where metal ducts or sleeves terminate in woodwork, tight joints shall be made by means of closely
fitting heavy flanged collars. Where ducts pass through brick or masonry openings, wooden frame
work shall be provided within the opening and crossing of ducts provided with heavy flanged collars
on each side of the wooden frame work, so that duct crossing is made leak - proof.
All ducts shall be totally free from vibration under all conditions of operation. Wherever duct work is
connected to fans / air handling units or blower coil units that may cause vibrations in the ducts, ducts
shall be provided with two flexible connections, located close to the unit, in mutually perpendicular
directions, flexible heavy canvas sleeve at least 10 cm long securely bonded and bolted on both
sides. Sleeve shall be made smooth and the connecting ductwork rigidly held by independent
supports on both ends. The flexible connection shall be suitable for pressures at the point of
installation and shall be of approved make.
All dampers shall be louver dampers of robust construction and tight fitting. The design, method of
handling, and control shall be suitable for the location and the service required.
Dampers shall be provided with suitable links, levers, and quadrants as required for their proper
operation, control or setting devices shall be made robust, easily operable and accessible through
suitable access doors in the ducts. Every damper shall have an indicating device clearly showing the
damper position at all the times.
Dampers shall be placed in ducts at every branch supply or return air duct connection, whether or not
indicated on the drawings, for the proper volume control and balancing of the system.
6.0 SUPPLY AND RETURN AIR DIFFUSERS:
Supply and return air diffusers shall be of approved make as shown on the drawings and/or indicated
in the Bill of quantities.
Round or Rectangular Diffuser: Shall be anodized Aluminum section construction,
square,rectangular, or round diffusers with flush fixed pattern. Diffusers for different spaces shall be
selected in consultation with site engineer. Supply air diffusers may be equipped with fixed air
distribution grids, removable key operated volume control dampers, and anti-smudge rings as required
in specific applications, all as per requirements of Bill of quantities.
Linear Diffuser: Shall be anodized Aluminum section construction, one or two-way blow
lineardiffusers. Supply air diffusers shall be provided with volume control / balancing dampers within
the supply air collar. Diffusers for different spaces shall be selected in consultation with site engineer
and provided as per requirement of Bill of quantities. All linear / square / round diffusers shall have
volume control dampers of MS construction.
7.0 METHOD OF MEASUREMENTS FOR AIR DISTRIBUTION SYSTEM
Sheet Metal work:
Duct Length shall be measured along the centre line from flange face to face unless otherwise stated.
Ductwork shall be measured on the basis of external surface area (length as measured above,
multiply by duct perimeter) of ducts including the joints for each duct section. Duct measurement shall
be taken before application of the insulation. For taper section average perimeter shall be used for
measurement. For special pieces like bends, reducers, branches, and collars, mode of measurement
shall be identical to as described above using the length along the centre line. The quoted unit rate for
external surface of ducts shall include all wastage allowances, flanges and gaskets for joints, nuts and
bolts, hangers and angles, and angles/flats with double nuts for supports, felt strip between duct and
support, vibration isolation, inspection chamber / access panel, splitter damper with quadrant and lever
for position indication, turning vanes, straightening vanes, and all other accessories required to
complete the duct installation as per the specifications. These accessories shall not be separately
measured nor paid for.
Duct Accessories: Shall be measured by the cross section area perpendicular to air flow.
Grilles and diffusers:
Width multiplied by height, excluding flanges, volume control dampers shall form part of the unit rate
for registers and shall not be separately accounted.
Diffusers: Cross-section area for airflow at discharge/capture area, excluding flanges. Volume control
dampers shall form part of unit rate for supply air diffusers and shall not be separately accounted.
Linear Diffusers: Shall be measured by linear measurements only not by cross sectional areas, and
shall exclude flanges for mounting of linear diffusers. The supply air plenum for linear diffusers shall be
measured with ducting as described earlier.
Fire Damper: Shall be measured by their cross sectional area perpendicular to the direction of airflow.
Quoted rates shall include the necessary collars, and flanges for mounting, inspection pieces with
access door, solenoid valves etc. No special allowances shall be payable for extension of cross
section outside the air stream.
Flexible connection: Shall be measured by their cross sectional area perpendicular to the direction of
airflow. Quoted rates shall include the necessary mounting arrangement, flanges, nuts and bolts and
treated-for-fire requisite length of canvas cloth.
8.0 TESTING & BALANCING:
After the installation of the entire air distribution system is completed in all respects, all ducts shall be
tested for air leaks by visual inspection.
The entire air distribution system shall be balanced using anemometer. Measured air quantities at fan
discharge and at various outlets shall be identical to or less than 5 % in excess of those specified and
quoted. Branch duct adjustments shall be permanently marked after air balancing is completed so that
these can be restored to their correct position if disturbed at any time. Complete air balance report
shall be submitted for scrutiny and approval, and four copies of the approved balance report shall be
submitted along with the completion documents.
9.0 INSULATION:
The scope of this section comprises the supply and fixing of insulation conforming to these
specifications and in accordance with requirement of Bill of quantities.
Insulation material shall be EPDM – Class I
EPDM Insulation material shall have anti-microbial product, which is EPA approved, as an integral part
of insulation that cannot be washed off or worn off, which does not allow the microbes to function, grow
and reproduce. Microbiological growth on insulation surface should confirm to following standards:
Mould Growth – UL 181; Fungi Resistance – ASTM G21/C1 338 and Bacterial resistance – ASTM G
22. Density of Material shall be between 40 to 60 Kg/m3.
Thermal conductivity of Elastomeric EPDM shall not exceed 0.033 W/m K at an average temperature
of 0 C. The insulation shall have fire performance such that it passes Class 1 as per BS476 Part 7 for
surface spread of flame as per BS 476 and also pass Fire Propagation requirement as per BS476 Part
6 to meet the Class ‘I’ Fire category as per 1991 Building Regulations (England & Wales) and the
Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 1.74 x
10 Kg/m.s.Pa, i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum
Thickness of insulation shall be as specified for particular application or as specified in Bill of
quantities. Samples of insulation material shall be submitted for approval and shall be tested for
thermal conductivity values. Adhesive used for setting insulation shall be cold setting compound non-
flammable, vapor proof adhesive, shalimar CPRX compound or equivalent approved make.
DUCT INSULATION:
Duct acoustic lining:
Internal Acoustic lining for ducting is proposed (discharge duct) with 19 mm ( Or Specified Thickness )
thick Arma sound material.
Acoustic duct lining shall be applied inside the duct for a minimum distance of 3 meter or as shown in
the drawing from the outlet of air handling units or as specified in drawings or as indicated in Bill of
quantities. Acoustical duct lining shall be applied as follows:
(i) The inside surface of the duct shall be cleaned and covered with cold setting adhesive
(ii) Depending on size of duct fit min. 2 or more rows of insulation fixing pins to each face of duct at
every 300 mm center distance. Pins shall be self-adhesive, bond on type.
Carefully position insulation over the pins, pressing firmly so that pins penetrate through the
insulation. Fit spring clip or lock washer over pins pushing them down until they are tight against
insulation. Snip off any excess shank from pin. Seal all joints and openings with self adhesive
(iii) Depending on size of duct fit min. 2 or more rows of Mechanical fasteners (G.I Bolts) of sufficient
length to each face of duct at every 300 mm center distance. Pins can be self adhesive type,
Carefully position insulation over the bolts, pressing firmly so that bolts penetrate through the
insulation. Fit G.I nut over the bolts pushing them down until they are tight against insulation.
Snip off any excess shank from bolt. seal all joints and openings with self adhesive tape.
UNDER DECK INSULATION:
Thickness & specs with 19 mm Nitrile Rubber Silver White Finish flexible cladding Condition.
(a) Insulation Material TechnicalSpecification–Class O Nitrile:
• Insulation material shall be Closed Cell Elastomeric Nitrile Rubber
• Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.035W/(m.K)at an average
temperature of 0°C
• The insulation shall have fire performance such that it passes Class 1 as per BS476
• Part7 for surface spread of flame, also pass Fire Propagation requirement as per BS476Part6 to
meet the Class‘O’ Fire category requirement as per 1991 Building Regulations (England & Wales)
and the Building Standards (Scotland) Regulations
• Material shall be FM (FactoryMutual),USA approved.
• Unlike other generic materials it should be self extinguishing, does not dripand does not spread
• Moisture Diffusion Resistance Factor or‘µ’value shall be minimum7,000 for the insulation material
without any outcovering.
(b) Technical Details for composite film of metallic appearance with Silver White finish for outer covering:
It shall be a multilayer laminate of aluminum with coating for UV protection and polymer backing. It
should provide mechanical resistance with excellent aesthetic looks. It should be Class“1”rated with
surface spread of flame tested according to BS476Part7 and Class“O”rated as per the Fire
Propagation tested according to BS476Part6.
Application: On outdoor applications, joints along them at erial length shall be installed facing
downward. The joints shall be secured with plastic rivet sintheover lap area, installed every 200mm
along them at erial length. Manufacturer recommended adhesive can be used for flat sheets, or
where restricted access prevents use of rivets. All joints and overlaps must be finished with
manufacturer recommended Tapes.
• Temperature Range:-25°Cto+75°C
• Color and Finish:Silver, Bright Metallic Finish
• Resistance to mechanical impact:>200N as per ASTMD4833-07
• UV Resistance:Excellent as per ASTMG26A, ISO4892-2 and JISK7350-2
• Tensile Strength:>50MPa as per ENISO527-1,ENISO527-3
• Puncture Resistance: >200N as per ASTMD4833-07
Tenderer : Addl. Chief Eng. ( Electrical)
Name : Ahmedabad Municipal Corporation
Company’s seal :
APPROVED MAKE LIST
DETAILS OF MATERIAL /
SR. APPROVED MANUFACTURERS NAME
O-GENERAL / MITSUBISHI ELECTRIC(Akabishi)/
1 Ductable A.C. UNIT MITSUBISHI HEAVY DUTY.
O-GENERAL / MITSUBISHI ELECTRIC/ MITSUBISHI
2 Split A.C. HEAVY DUTY.
O-GENERAL / MITSUBISHI ELECTRIC/ MITSUBISHI
3 Cassette/Tower A.C. UNIT HEAVY DUTY.
O-GENERAL / MITSUBISHI ELECTRIC/ MITSUBISHI
4 Package A.C HEAVY DUTY Or Equivalent.
5 GI DUCTING SAIL / TATA / JINDAL
GRILLES / DIFFUSERS /
6 DAMPERS CARRYAIRE / DYNACRAFT / RAVISTAR
7 COPPER PIPE RAJCO / MANDEV / TOTALINE
8 EXPANDED POLYSTYRENE LLOYDS INSULATION/COOLINE/BEARDSELL
EXTRUDED POLY STYRENE
9 BOARD OWENS CRONING / SUPREME INSUBOARD
10 FIBERGLASS OWENS CRONING / TWIGA
11 CROSS LINKED POLYMER PERAMOUNT / TROSSLIN / SUPREME
12 NITRILE RUBBER AEROFLEX / K FLEX / ARMAFLEX
13 EPDM RUBBER ARMACELL/ AROFLEX / ARMAFLEX
STARBOND CANVASS
14 COATING PARAMOUNT
15 DRAIN PIPE / PVC PIPE FINOLEX / SUPREME / ASTRAL
16 CABLES FINOLEX / RR CABLE / HEAVELLS / KEI / TORRENT
17 GI PIPE TATA/ JINDAL
18 JET NOZZLE SYSTEM AIR/ DYNACRAFT
19 MCB/MCCB L & T / SCHNEIDER / SIEMENS/LEGRAND/ABB
Aluminium Composite Panel ALEX/TIMEX/PRASO
NOTE:- IF ANY ITEMS NOT IN APPROVED MAKE LIST,VENDER MUST HAVE
AUTHORISED BY CONSULTANT/AMC OFFICIALS.
Signature of Tenderer : Addl. Chief Engineer (Electrical)
Company’s seal : Ahmedabad Municipal Corporation:
EARNEST MONEY DEPOSIT / SECURITY DEPOSIT
In consideration of the Ahmedabad Municipal Corporation of the city of Ahmedabad
(hereinafter to as the corporation) having agreed to exempt
______________________________________ (hereinafter referred to as "the said Contract")
from the demand of earnest money / security deposit in cash for the due fulfillment of the
terms and conditions of the agreement made between the AMC- and the said tenderer on
(hereinafter referred to us "the said agreement") on production of Bank Guarantee for
(hereinafter referred to as "Bank") do hereby undertake to pay to the AMC as a amount not
exceeding Rs. _____________________________ Rupees
the demand from AMC.
Any such demand on the bank shall be conclusive as regards as amount due and payable by the
bank under this guarantee. However, liability of the bank under this agreement shall restrict to
as amount not exceeding Rs. ___________________________ Rupees
We the bank further agree that the guarantee herein contain shall remain in full force and
effect during the period that would be mentioned in the tender and that it shall continue to be
enforceable till all the dues of the Corporation under or virtue of the said agreement have
been paid and its claim satisfied or discharged and till a certificate to the effect has been
received by the bank from the Corporation. However, unless the demand of claim under the
guarantee is made to the bank in writing on or before the _____________________ (specify
the date) the bank shall be discharged from all liabilities under this guarantee.
With the bank further with AMC shall have fullest liberty, without the concert of the bank
without effecting in any manner it obligations herein under to vary any of the terms and
conditions of the said agreement or extend time for validity by the said tender from time to
time or to postpone for any time or from time to time any of the powers exercisable by the
AMC /AMC-MET against the said Contractor and to forebear to enforced any of the terms and
conditions relating to the said agreement and the bank shall not be relieved from liability by
reason of any such variation, or extension granted to the contractor for any forbearance, at
Contractor or by any such matter or thing whatsoever which under the law relating to sureties
would, but this provision, have the effect of so relieving the Bank.
undertake not to revoke the Guarantee during currency except with the previous concert of
the AMC in writing.