Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹7.4 L+₹14,692.10 (2.02%)Rejected-AOC | L2 | Rejected-AOC Second lowest bidder |
Tender Value
₹7.3 L
EMD Value
₹18,163
Closing Date
13 Dec 2024, 6:00 pmClosed
Medical Officer, CHC Ambalappara
CHC Ambalappara
LAC-ADS-2020 -2021 - Ottappalam Constituency - Ambalappara CHC -SITC of 30KVA Diesel Generator
2024_LSGD_710879_1
1/T4/MO/CHC/24-25
Open Tender
Electrical Works
Item Rate
180 days
CHC Ambalappara
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,605
₹18,163
24 Jan 2025
3 Dec 2024
16 Dec 2024
3 Dec 2024
13 Dec 2024
3 Dec 2024
Amount
1. SITC of 30 KVA DG Set
OD191978/2024-2025:Supply and installation of 30KVA/24 KW, Three phase Diesel Generating Set with acoustic enclosure as per CPCB IV+ norms comprising of Greaves/TMTL (Eicher)/Kirloskar/Ashok Leyland/Escorts equivalent, Radiator Cooled Diesel engine 1500 RPM, complete with standard accessories Coupled to Stamford/LS/equivalent Alternator rated at 30 KVA/24 KW at 415Volts mounted on Channel Iron Base Frame complete with Anti Vibration Pads, Initial fill of Lube oil, Fuel Tank, filled with full tank diesel, Silencer, Standard manual Control System and Batteries, Battery Wires with automatic battery charger suitable for 30KVA DG set, Tools Kit. The DG set should have warranty of 3 years from the date of installation.
OD114887/2024-2025:Supply and providing following size M. S. pipe - 5 mm thickness complete with suitable size 12mm flange coupling with minimum 4/5mtr using allied packing with MS bolt with washer and rising the same on the wall/ parapet using chain pullies, scaffolding, supports with M.S angles/channels etc. including painting the pipe with one coat of zinchromate primer over a coat of high temperature resistance alu. paint etc. for extending the exhaust pipe of the newly erected D. G. set. 50mm dia or nearest size B class MS pipe.
OD114888/2024-2025:Supply and installation of COS in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts,fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. 63A 4 pole on-load COS AC 23A duty.
OD114889/2024-2025:Supply and fixing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour.
OD114890/2024-2025:Supply and fixing LED indicators for all voltage ranges - Blue Colour.
OD114891/2024-2025:Supply, installation, testing and commissioning of 2A SP MCB in the existing panel as required.
OD114892/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipment's including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50 sq mm single run with required sockets.
OD114893/2024-2025:Supply and fixing legend plate of Aluminium anodized Danger Notice Board of size 150 x 100 mm with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red color in the panel assembly.
OD114894/2024-2025:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 2.50 cm,4 cm or 5 cm height.
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.5.29:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 50 sq mm
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size
OD114895/2024-2025:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2 metre long etc. with charcoal/ coke as required.
OD114896/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using 25 x 3 mm GI strip of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate,test joint etc. as required.
OD114897/2024-2025:Providing and fixing 2x25mmx 3mm GI strip test joint for earthing system.
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.2.2:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
OD114898/2024-2025:Supply and providing 25 x 6 mm brass nut and bolt etc.as required.
OD114899/2024-2025:Supply and providing 2mm thick electrical grade chequied type rubber mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength in front of panels & Generators.
OD114900/2024-2025:Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD114901/2024-2025:Charges for preparing schematic drawings in A3 sheet as per electrical inspectorate standards
OD114902/2024-2025:Additional charges for taking copy of sheet
OD114903/2024-2025:Fees for getting sanction from Electrical inspectorate including all liaison work etc.(actual will be paid on production of relevant documents.)
2.Foundation.
2.7.1:Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
4.1.3:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
ARUN.C.S (BID ID -2017732)
Bidder Name
AYAPPA ELECTRICALS
ARUN.C.S
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1118601.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .