Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.2 LAccepted-AOC 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹11.8 L+₹56,160 (5.02%)Rejected-Finance 362 SUBHASH NAGAR PO CLEMENT TOWN DEHRADUN UTTARAKHAND | L2 | Rejected-Finance Being 2nd lowest | |
| 3 | L3₹12.6 L+₹1.4 L (12.9%)Rejected-Finance | L3 | Rejected-Finance Being 3rd lowest | |
| 4 | L4₹13.7 L+₹2.5 L (22.2%)Rejected-Finance 67 NIRANJANPUR SAHARANPUR ROAD PO MAJRA DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L4 | Rejected-Finance being 4rth lowest | |
| 5 | L5₹13.9 L+₹2.7 L (24.4%)Rejected-Finance 11 GURU NANAK MARKET AMBALA ROAD SAHARANPUR 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | L5 | Rejected-Finance Being 5th lowest |
Tender Value
Refer Docs
EMD Value
₹32,800
Closing Date
26 Sept 2020, 6:00 pmClosed
SHRI B K SREEKUMAR EE GE (AF) SARSAWA
Garrison Engineer (AF) Sarsawa, Distt. Saharanpur (U.P)
PROVISIONING OF 12 ALL WEATHER AIR CONDITIONERS IN P-6 BUILDING IN GT AREA AND ROAD FURNITURE AT 1 AFSB DEHRADUN
2020_MES_372808_1
8120/SAR-31/E8 PROVISIONING OF 12 ALL WEATHER AIR
Open Tender
Civil Works
Item Rate
273 days
GE(AF) SARSAWA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(AF) SARSAWA
₹32,800
Yes
3 Oct 2020
28 Aug 2020
28 Sept 2020
28 Aug 2020
26 Sept 2020
12 Sept 2020
28 Aug 2020 - 12 Sept 2020
Amount
Supply install testing and commissioning of split type air conditioner 5 star BEE rated all weather "Hot and Cold " of capacity of 1.5 TR, consisting of indoor and outdoor units(Evaporative and condensive units including manufactures recommended size/type copper tubing duly insulated for connecting the units both indoor and out door along with PVC insulated copper conductor for electric power supply including all connected item for fixing complete all as specifid and directed. make - Blue star,voltas or equivalent
Supply and fixing voltage stabilizer for automatic operation/single phase Ac supply 230 volt 50 HZ time delay relay naturally air cooled indoor type designed for input variation between 170 volt to 250 volt with out put voltage stabilizer at 230 V with accuracy of +2.50% and capacity 4 KVA complete all as specified. Make - v-guard,or equivalent
S&F submain wiring with two single core FRLS cable of size 4 sqmm 1100 volts grade drawn in concealed conduit including 2.5 sqmm copper multi-stranded conductor PVC insulated FRLS earth wire connected to main board complete all as specified and directed.(Two Number of cable and one number earth wire shall measured together as unit length)
S&F rigid non metalic conduit medium grade 25 mm external dia ISI marked with accessories such as tees,bends,junction box,bell mouth tube ends,including fixing accessories locks as couplers,lock-nuts,pipe hook etc in walls ceiling etc complete all as specified.
Supply and fixing including connecting 20 Amps SPN with AC Box complete all as specified and directed by Engr-in-charge.
M&L for Excavation in trenches in soft/loose soil n.exc 1.5mtr deep and n excl 1.5 mtr wide for laying of HT cable ,pole, etc and gettting out including of dressing / trimming sides and levelling, grading and ramming of bottom excavation complete all as specified and as directed.
Returning filling in including spreading, leveling watering and well ramming in layers not exc 25 cm thick each layer in soft/loose soil complete all as specified and as directed.
Removing excavated materials (soils) not exc. 50 m and depositing where directed at a level not exc.1.5 mtr above the starting point complete all as specified and as directed.
M & L for fine dry sand cushioning for underground cable by providing a layers of sand 8 cm deep before laying and 15 cm deep after laying the cable including streching the cable complete all as specified and as directed.
M & L forlaying of bricks sub class 'B' old size laid flat perpendicular to the direction of cables for protection complete all as specified and as directed.
Taking down old unserviceable GI tubes any size complete all as specified and as directed.
Supply & lay G I tubing light grade in protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified and directed for following sizes :- . Make : jindal/ TATA/prakash. (a) 40 mm dia bore complete all as specified and as directed.
-ditto- but 50 mm dia bore complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5core complete all as specified and as directed.
S& F TP & N Vertical load line 6 way Double door suitable for 125A incomer impact test IK 09. DB should be provided with insulated vertical phase bus-bars, neutral bars with shroud, earth bars, sticking saddles, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identificationlabels. Make L&T,Havells equivalent complete all as specified and as directed.
Supply and fix 4 Pole MCCB 125 to 160 Amp,50 Hz, 415 V with rupturing capacity 50 KA complete all as specified and as directed.
S&F MCB 20A, 10kA, SP, C Curve with mechanical short circuit flag indication, Line-Load Reversibility, Vibration resistance 3g in frequency 10-55 Hz 20 cycle, shock resistance 20g, 3 shock with short duration of 10ms, pollution degree 3. or equivalent complete all as specified and as directed.
Earthing complete with copper earth plate electrode 60×60cm.× 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than1.5 metres below normal ground level, connected to copper strip 20x3 mm as earth lead by means of brazing, all as shown in electricalplate No. 5 connected to earthing test point all as specified or indicated including testing on completion ® complete all as specified and as directed.
M&L for heavy duty mild steel road delinators, 50mm dia and 40 inches height, colour coated with 3 bands of reflective tape of different colour including fixing to road side complete all as specified and directed by Engineer in charge.
Supply and fix solar road struds, flashing type, bl-directional with LEDS (Light emitting Diods) on each sides red colour with reflector strip & aluminium cast housing with & incl fixing arrangement as per manufacturer instruction complete all as specified. (Make: AKTION AK 970/. TATA BP/DARK EYE)
S&F ABS Engineering plastic road cat eye dinamically designed having impact reflector both side size-110x128x29.5mm wt 248 grm all as specified and directed. (Make: AKTION AK 970/. TATA BP/DARK EYE)
S & F convex mirror 900mm dia made of PC material provided with suitable MS pipe post, duly powered coated as per site requirement, unbreakable a stronger than glass.It is meant for road turning , intersections ,curves , T junction ,Hospitals , parking lots etc. It is also idea for surveillance. It should have clear & define mirror image having 130 degree of viewing angle complete all as specified and as directed.
KAPOOR ELECTRICALS
SHRI RAM ENTERPRISES
Bedi Refrigeration Works
RAJAN TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .