Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.3 LAccepted-AOC | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹43.6 L+₹1.3 L (3.13%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹47.4 L+₹5.2 L (12.2%)Rejected-Finance SHREE NIVAS LIMDA LANE JAMNAGAR GUJARAT PIN 361001 | JAMNAGAR | GUJARAT | 361001 | L3 | Rejected-Finance Not lowest | |
| 4 | L4₹59.7 L+₹17.5 L (41.3%)Rejected-Finance 141 SHANTI NAGAR MODEL TOWN MODEL TOWN PANIPAT HARYANA 132103 | PANIPAT | HARYANA | 132103 | L4 | Rejected-Finance Not lowest |
Tender Value
₹38.9 L
EMD Value
₹77,800
Closing Date
9 Apr 2024, 6:00 pmClosed
GE AF BARODA
GE AF BARODA DARJIPURA POST VAODARA
SR / REPLACEMENT OF LT DISTRIBUTION / PANEL / APFC PANEL / LT CABLE / STREET LIGHT / SOLAR STREET LIGHT AND ASSOCIATED WORK AT AFS VADODARA
2023_MES_632874_3
8860/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF BARODA
AS PER TENDER DOCUMENTS AND NIT
4 documents required · 4 mandatory
₹500
GE AF BARODA
₹77,800
Yes
7 Jun 2024
21 Mar 2024
11 Apr 2024
21 Mar 2024
9 Apr 2024
28 Mar 2024
Amount
Supply, installation, testing and commissioning factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door typesize not less then 2000 W x 1500H x 500 D platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Amps meter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos each Suitable long welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC 1:2:4 B2 of Suitable size the ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising of following complete all as specified and directed :- (Location KV school,247,230 )
Incomer:- (a) MCCB FP 400A 36 kA with Electronic/Microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release with Short circuit Zone of adjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 no (b) 4 Nos Aluminium Bus bars of Aluminium strips (50X12mm) having 600 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator complete with nut bolt fixing arrangement complete - 01 set Outgoing:- (c) MCCB FP 200A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -05Nos (d) MCCB FP 160 A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 Nos
Supply, installation, commissioning and testing factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door typesize not less then 2000 W x 1500H x 500 D platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Amps meter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos each Suitable long welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC 1:2:4 B2 of Suitable size the ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising of following complete all as specified and directed :- (Location MES Pump house)
Incomer:- (a) MCCB FP 500 A 50 kA with Electronic/Microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release with Short circuit Zone of adjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 no (b) 4 Nos Aluminium Bus bars of Aluminium strips (50X12mm) having 600 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator complete with nut bolt fixing arrangement complete - 01 set Outgoing:- (c) MCCB FP 125 A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -06 Nos (d) MCCB FP 160 A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 Nos
Supply, installation, testing and comminsioning of outdoor type, Self standing, made out of MS sheet thickness 3.15mm duly powder coated double door, front and back openable, APFC panel fabricated (CPRI approved manufacturer) compartmental type with APFC relay 9 stage with heavy duty MPP capacitor bank 70 KVAR (1 KVAR + 2 x 2 KVAR + 1x 5 KVAr+3x 10 KVAr + 2 x 20KVAr with power contactor and MCCB TP of 16 KA of 1.5 time of rating currect of capacitor suitable for each capacitor control and MCCB TPN 160 Amp 16 KA as incomer including control CT & control wiring complete dust and vermin proof double door made out of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Amps meter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos each Suitable long welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC 1:2:4 B2 of Suitable size the ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys having following assessories including control wiring with HR FRLS copper wire complete all as specified and directed
(KV School sub station, at Pump house sub station and Near Mashjid) (i) Compact modular bolted design, removable side and back panels with option of top and bottom cable entry (ii) Capacitor installed in removable assemblies for ease of operation and maintenance (iii) Incoming of APFC panel of MCCB TPN 160 Amps, 16 KA breaking capacity with high electrolytic grade Aluminium bus bar iof suitable rating. (iv) 70 KVAR (1 KVAR + 2 x 2 KVAR + 1x 5 KVAr+2x 10 KVAr + 2 x 20KVAr) with power contactor and MCCB TP of 16 KA of 1.5 time of rating current of each capacitor suitable for each control . (each capacitor bank equipped with discharge resister) (v) High performance microprocessor based 3 phase APFC relay 9 stage with Auto/Manual Option. (vi) In built 3 phase power analyzer , Amp meter, volt meter and PF meter (each have 1 No) (vii) With power contactor modules with high thermal current carrying capacity and early make contacts to reduce inrush current for enhancing life of capacitors (viii) Induced air system provided with axial flow fan/ centrifugal fan. (ix) Bottom cable entry system available with front glass for viewing controller and analyzer from front
Supply, installation, testing and commissioning of factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door typesize not less then size 1500 W x 1500H x 500 D platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Amps meter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos each Suitable long welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC 1:2:4 B2 of Suitable size the ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising of following complete all as specified and directed :- (Location :- Near Qtrs No 269 , 280 , 240, 246, 293, 288, 260 and 263
Incomer:- (a) MCCB FP 200 A 36 kA with Electronic microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release with Short circuit Zone of adjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 no (b) 4 Nos Aluminium Bus bars of 400 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator complete with nut bolt fixing arrangement complete - 01 set Outgoing:- (c) MCCB FP 100 A 16 kA with Adjustable Thermal release for over load 0.7 to 1.0 and Adjustable magnetic release (10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -04 Nos
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in soft / loose soil complete all as specified and directed.
Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Supplying and filling unwashed dry river sand for sand cushioning and covering of LT cable in trenches complete all as specified and directed. Note: Thickness of sand shall be measured after punning.
M&L well burnt bricks sub class 'B' as in protection of cable laid dry, flat abutting each other width wise complete all as specified and directed.
Taking down / dismantling of unsv LT cable complete all as specified and directed
Taking out existing U/S panel from existing site including disconnecting of existing cable complete all as specified and directed
Supplying, testing, laying and commissioning of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of the following sizes including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and covers shall be measured and paid separately.
3.5 Core X 240 Sqmm complete all as specified and directed
4 Core X 25 Sqmm complete all as specified and directed
4 Core X 35 Sqmm complete all as specified and directed
Supply, fixing, testing and commissioning of feeder pillar box made out of CRCA sheet not less than 3.15mm thick duly powder coated, CPRI approved 300 Amp rating Aluminium Busbar box size not less than 1 Mtr x1 mtr x .4Mtr suitable for arrengement of following complete all as specified and directed:- (a) Incommer :MCCB 100 16 KA 4 pole - 2 Nos (loop in /Loop Out) (b) Out going: MCB SPN 32 Amp - 6 Nos (c) 15 Amp switch socket combination 6 Nos
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft / loose soil complete all as specified and as directed.
M & L for stones aggregate of gauge 40 mm graded including spreading at various location of substation complete all as specified and directed
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32x6mm main earthing lead by means of galvanized bolts, nuts and washers with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed
Supply and fixing of solar street light driver /controller of capacity Power = 30W-50wtt Input voltage: 12 volt Automatic ON OFF complete all as specified and directed.
Supply and fixing of 100AH Tubular lead acid battery , maintenance free suiatbel for solar street light complete all as specified and directed.
Supply and fixing LED street light 40W, 12 V suiablle for solar street light complete all as specified and directed.
Supply and fixing LED 10W bollard gardon light pressure diacast Powder coated PDC Aluminium body with Opal diffuser./ PC diffuser efficent high output with IP 65 protection including PCC foundation of 1:2:4 20mm graded C2 complete all as specified and directed.
Supply and fixing of HDPE pipe 25 mm dia suitable for cable laying for Garden lights complete Including excavation up to depth 15 cm complete all as specified and directed.
Supply and fixing PVC insulated PVC sheathed 3 core copper conductor size 1.5 sqmm complete all as specified and directed.
M/s SK Traders
M/s super construction
Chanda Construction Co.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .