| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance CHANDRA VILASAM VAZHUTHOOR NEYYATTINKARA THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | KERALA | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹25.9 L
EMD Value
₹50,000
Closing Date
25 Mar 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Chief Engineer, Sports Kerala Foundation
Jimmy George Indoor Stadium, Vellayambalam, Thiruvananthapuram
Renovation and Upgradation to the Administrative Building at G.V. Raja Sports School Mylom, Thiruvananthapuram -Electrification Works-Retender
2024_SKF_667687_2
249/SKF/CE/2023-24
Open Tender
Electrical Works
Item Rate
180 days
Thiruvananthapuram
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,950
₹50,000
27 Mar 2024
16 Mar 2024
27 Mar 2024
16 Mar 2024
25 Mar 2024
16 Mar 2024
Amount
Electrification works at Administrative Building
1.10.1 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.6 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)
1.28.2 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.6 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.12 Module
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.28.3 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module
1.28.4 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
od250585/2023_2024 : SKFOD6W_Supply,Installation, testing and commissioning of pre-wired, 6W Surface/recess mounting round LED down light fittings complete with all accessories directly on ceiling/ wall, including connection with PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.24.6 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
1.34 : Supplying and fixing brass batten/ angle holder including connection etc. as required.
1.53.1 : Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
od250420/2023_2024 : Supply and fixing of following 4 pole 63amps. (415 Volts),100mA sensitivity rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep -5star rated ceiling fan complete with 300mm down rod , canopies, shackles and blades working on 230V/240V single phase A/C
od39111/2023_2024 : Servicing of 400mm wall mounted fan including disconnecting the pull switch nylon cord and re-installation of wall fan without speed control as instructed in Engineer-in charge
od39112/2023_2024 : Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2018 with ISI mark.
1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required.
2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
od250308/2023_2024 : SKFDSROD: Supply and installation of pre-wired 20W LED batten fitting complete with all accessories and tube etc directly on ceiling/wall, including connection with PVC insulated,copper conductor single core cable and earthing etc as required.<br>(Make: Phillips, Crompton greaves, Bajaj, Lucker or Approved by engineering in charge)
90.15.4.6 : Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
od250302/2023_2024 : SKF-OD Supply,Installation, testing and commissioning of pre-wired, 9W Surface mounting round LED down light fittings complete with all accessories directly on ceiling/ wall, including connection with PVC insulated, copper conductor, single core cable and earthing etc. as required
od250303/2023_2024 : SKFOD15W_Supply, Installation, testing and commissioning of pre-wired, 15W recess mounting round LED down light fitting complete with all accessories directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.<br>Make : Phillips, Crompton Greaves, Bajaj, Lucker or approved by engineer in charge
od250307/2023_2024 : Supply and fixing of LED strip light fixture of 5Watts/ 5mtr including all accessories like drive etc having provision to connect with 1.5 sqmm wires as required
1.59 : Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins reinstalling the same as required.
od252277/2023_2024 : Supply, installation, testing and commissioning of Inverter type ceiling-mounted four-way cassette type Split AC unit complete with the indoor unit and outdoor units. Indoor unit with DX cooling coil, filter, fan-motor<br>assembly and inbuilt drain pump. Air-cooled condensing unit complete with Scroll/Rotary and compressor condenser fans condenser coil. The unit should operate on R22/R410A/R32<br>refrigerant Rates shall include cordless remote controller Make Bluestar/Carrer/LG/Equivalent" 2.0TR Cassette unit<br>
od252353/2023_2024 : Supply and Laying of the copper pipe for the 4ton Cassette AC units including the insulated sleeves with all accessories as required
Lightning Protection
od39103/2023_2024 : Supply and installation vertical run - Round wires - , 8 mm / 50 mm², AlMgSi, semi-rigid Round wire according to DIN EN 62561-2 (VDE 0185 Part 202) for use as air-termination system or down conductor in lightning protection systems.Diameter Ø conductor: 8 mm Cross-section: 50 mm2 Material: AlMgSi Materi. with Conductor holder for Metal Roof with all accessories
od39174/2023_2024 : Supply and Installation for sub panel Rewired complete unit consisting of a base part and plug-in protection modules ,High discharge capacity due to heavy-duty zinc oxide varistors / spark gaps ,High reliability due to "Thermo Dynamic Control" SPD monitoring device.SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II Nominal voltage (a.c.) (UN) 230 / 400 V (50 / 60 Hz) Max. continuous operating voltage (a.c.) [L-N] (UC) 320 V (50 / 60 Hz) Max. continuous operating voltage (a.c.) [N-PE] (UC) 255 V (50 / 60 Hz) Nominal discharge current (8/20 µs) (In) 20 kA Max. discharge current (8/20 µs) (Imax) 40 kA Lightning impulse current (10/350 µs) [N-PE] (Iimp) 12 kA with all accessories
od39175/2023_2024 : Supply and Installation - For 3 phase power supply system Prewired combined lightning current and surge arrester, energy-coordinated with power supply systems for cell sites ,Encapsulated spark gap technology with a width of only 1 module / pole allows compact and space-saving design for easy installation within the power supply cabinets/SPD according to EN 61643-11 / ... IEC 61643-11 type 1 + type 2 / class I + class II Energy coordination with terminal equipment (≤ 10 m) type 1 + type 2 + type 3 Nominal voltage (a.c.) (UN) 230 / 400 V (50 / 60 Hz) Max. continuous operating voltage (a.c.)[L-N]/[N-PE] (UC) 255 V (50 / 60 Hz) Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) 25 / 100 kA Specific energy [L-N]/[N-PE] (W/R) 156.25 kJ/ohms / 2.50 MJ/ohms Nominal discharge current (8/20µs) (In) 25 / 100 kA.
od39104/2023_2024 : Supply of HORIZONTAL RUN - Round wires wire, 8 mm / 50 mm², AlMgSi, semi-rigid Round wire according to DIN EN 62561-2 (VDE 0185 Part 202) for useas air-termination system or down conductor in lightning protection systems.Diameter Ø conductor: 8 mm Cross-section: 50 mm2 Material: AlMgSi Material with Conductor holder for Metal Roof with all accessories
od39105/2023_2024 : Supply and Installation of Universal connector For cross-connections, T connections and parallel connections Material of clamp: StSt Clamping range Rd: 8-10 mm Screw: M10 x 35 mm Standard: EN 62561-1 with all accessories
od39106/2023_2024 : Supply and installation of Earthing: C-Bar 3/4''; dia, UL listed, 3000 mm long + 22.6 Kg GC+ and clamp for termination with all accessories
od39107/2023_2024 : Providing and fixing of test joint with enclosure suitable for 10mm dia copper bonded solid steel round conductor with 100 microns of copper bonding (if pure copper conductor 25x3 mm solid tape also can be used) and 8mm dia solid round aluminum conductor made of stainless steel SS 304 grade. Conforms to the requirements according to (IS/IEC 62305).with an outdoor glass-fibre reinforced poly carbonate enclosure having minimum inner dimension of 75mm x 75 mm x 50 mm.
od39108/2023_2024 : Supply, Installation, Testing & Commissioning of Early Streamer Emission<br>(ESE) type lightning Air terminal.Supporting Mast The mounting pole used to support the lightning air terminal shall be minimum length of 05 Mtr. , non corrosive and made up of medium class GI / SS pipe of 1.5′′ diameter having base plate at bottom for securely fixing the mast on roof top. The mounting pole and supports shall be securely fixed with the<br>brackets and PVC insulated metallic guy wires to withstand the maximum wind velocity ofthat area.Protection Radius :- TYpe II Make :- ABB / STROMKING / POWER TRAC/AXIS All the work should be carried out as per the specified specifications and instruction of the Engineer-in-Charge.
od39109/2023_2024 : Supply, Installation, Testing & Commissioning of non-electronic & non-<br>resettable (Not require any external power supply) type lightning strike Digital counter to count the lightning stroke having display with IP-67 enclosure including all accessories and connection..(Digital 2 Digits) Make :- ABB / STROMKING / POWER TRAC/AXIS All the work should be carried out as per the specified specifications and instruction of the Engineer-in-Charge.
90.15.4.11 : Supply Conveyance, installation, testing and commissioning of 200W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
Conventional Fire Alarm System
od39197/2023_2024 : Supply, installation, testing, and commissioning of Addressable/Conventional type Multi-Detector (photoelectric cum rate of rising temperature type) complete with all accessories like base. base box, etc. to be installed under/above the false ceiling, roof, and concealed space, etc. interconnecting to loop cable complete as required. Shall be UL listed and FM Approved, complete as required as per the technical specification.
od39198/2023_2024 : Supply, installation, testing and commissioning of conventional type wall sounder cum strobe for both audio and visual indication complete with all fixing<br>accessories, base box etc. under false ceiling, roof, wall, etc, as required as per the technical specification. The product shall be EN/UL/FM/LPCB approved/listed.
od39199/2023_2024 : Supplying, installation, testing & commissioning of conventional type beam<br>detector with addressable module complete with emitter and receiver including all fixing accessories etc complete as required. The product must be UL listed,<br>complete in all respect as per technical specification.
od39200/2023_2024 : Supply, installation, testing and commissioning of addressable type or conventional with addressable module wall sounder cum strobe for both audio and visual indication complete with all fixing accessories, base box etc. under false ceiling, roof, wall, etc, as required as per the technical specification. The product shall be EN/UL/FM/LPCB approved/ listed.
od39203/2023_2024 : Supply, installation, testing, and commissioning of Manual Call Point with break glass, hammer, and chain, complete as per Tech. Spec. Make:Win Fire /Ravel or equivalent
od39276/2023_2024 : Supply and laying of 2x 1.5sq.mm armored Copper FRLS cable ISI marked with proper clamping, supports, and terminations appropriately above ground as per technical specification
Bidder Name
SREEJITH S G
stage.html
html • 0.02 MB
finance_1044056.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .