| 1.00HVAC WORKS | ||||
| 1.01 | Dismantling & Shifting of existing Machines 8.5 TR ducted split AC Out
door unit kit to Basement parking area and reinstallation of ODU
channel/frame | 1 | Lot | 15,000 ₹17,700 |
| 1.02 | Supply and installation of new 8.5 Tr ducted split AC ODU kit | 1 | Nos | 53,820 ₹63,507.60 |
| 1.03 | Supply and installation of new 8.5 Tr compressor. Model: ZR108KFTFD.522 copeland scroll | 1 | Nos | 48,000 ₹56,640 |
| 1.04 | Brazing , pressure testing vaccumisation of new compressor with labour
charge | 1 | Lot | 15,000 ₹17,700 |
| 1.05 | Commissioning of the system with R-22 refrigerant gas after necessary
pressure holding of nitrogen at 500psi for 24hrs, vacuuming of the system
to 600 microns and positive charging | 9 | Kg | 9,000 ₹10,620 |
| 1.06 | Communication cable wiring with electrical conduit | 7 | Rmt | 1,750 ₹2,065 |
| 1.07 | Copper refrigerant pipe of size with necessary 19 mm thick nitrile sleeve
insulation for suction and 13mm thick for discharge for connecting indoor
and outdoor units of suitable sizes 1 1/8 and 5/8 | 8 | Rmt | 14,400 ₹16,992 |
Tender Value
₹1.8 L
EMD Value
₹3,916
Closing Date
21 Jan 2026, 3:00 pmClosed
Managing Director
Managing Director,KSFDC,Chalachithra Kalabhavan,Vazhuthacaud,Tvm -14
E-TENDER FOR SITC OF NEW 8.5 TR DUCTED SPLIT AC ODU AND DISMANTILING OF EXISTING 8.5 TR HVAC ODU AT KAIRALI SREE THEATRE, OPP. KSRTC BUS TERMINAL,POLPAYAMANA,TAZHEKKOD, KOZHIKODE ,KERALA 673004
2026_KSFDC_827295_1
6578/T4/25/KSFDC - RE -E-Tender for SITC OF NEW 8.5 TR DUCTED SPLIT AC ODU AT KAIRALI THEATRE,KKD
Open Tender
Electrical Works
KAIRALI SREE THEATRE
Please refer Tender documents.
7 documents required · 7 mandatory
₹590
₹3,916
5 Mar 2026
13 Jan 2026
22 Jan 2026
13 Jan 2026
21 Jan 2026
13 Jan 2026
HVAC WORKS
Dismantling & Shifting of existing Machines 8.5 TR ducted split AC Out door unit kit to Basement parking area and reinstallation of ODU channel/frame
Supply and installation of new 8.5 Tr ducted split AC ODU kit
Supply and installation of new 8.5 Tr compressor. Model: ZR108KFTFD.522 copeland scroll
Brazing , pressure testing vaccumisation of new compressor with labour charge
Commissioning of the system with R-22 refrigerant gas after necessary pressure holding of nitrogen at 500psi for 24hrs, vacuuming of the system to 600 microns and positive charging
Communication cable wiring with electrical conduit
Copper refrigerant pipe of size with necessary 19 mm thick nitrile sleeve insulation for suction and 13mm thick for discharge for connecting indoor and outdoor units of suitable sizes 1 1/8 and 5/8
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.11 MB
NIT.pdf
Tender Documents • 0.10 MB
BOQ_1388322.xls
BOQ • 0.27 MB
SBD.pdf
Tender Documents • 0.49 MB
Download all tender documents and submit your bid