Chief Engineer 31 Zone
HQ Chief Engineer 31 Zone C/O 56 APO PIN 914631
COMPLETION OF INCOMPLETE AND BALANCE WORK FOR PROVISION OF ADM BLOCK AND GARRAGES FOR HQ INF DIV AT BARAMULLA
2020_MES_314987_2
CESZ / 2019-20 COMPLETION OF INCOMPLETE AND BA
Open Tender
Civil Works
Lump-sum
500 days
Baramulla
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,000
Garrison Engineer 969 EWS
₹5.5 L
12 Sept 2020
26 Jun 2020
5 Aug 2020
26 Jun 2020
3 Aug 2020
16 Jul 2020
26 Jun 2020 - 16 Jul 2020
Amount
Notes: (i) Please refer Schedule 'A' Notes given on serial page No. 23 to29 of tender documents. (ii) Sch ‘A’ Part-I (Sec-I), Part-I (Sec-II), Part-II (Sec-II), Part-III (Sec-II), Part-IX (Sec-II), Part-XI, Part-XII and Part-XIII is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
SCHEDULE 'A' PART-I (SEC-I): LIST OF WORKS FOR BUILDING WORKS
Construction of Incinerator (built in brick masonry) complete all as specified and shown on drawings.
SCHEDULE 'A' PART-I (SEC-II): LIST OF WORKS FOR BUILDING WORKS
Completion of incomplete works of Construction of Block of office and Adm Block (D/S) RCC framed structure, M-25 (Design mix) brick masonry, including porch, ramp, platforms, flower beds, steps, landscaped courts, hard standings etc complete all as specfified and shown on drawings.
Completion of incomplete works of Construction of Block of sentry post /Elevated sentry post, load bearing structure, brick masonry, including stair case etc complete all as specified and shown on drawings.
Completion of incomplete works of Construction of Block of Plant Room (S/S) RCC framed structure, M-25 (Design mix), brick masonry, including ramps etc complete all as specified and shown on drawings.
Completion of incomplete works of Construction of Block DG Set Room (S/S) RCC framed structure, M-25 (Design mix) brick masonry, including ramps, platform etc complete all as specified and shown on drawings.
Completion of incomplete works of Construction of Block of Sub Station building (S/S) RCC framed structure, M-25 (Design mix), brick masonry, including ramps and platforms etc complete all as specified and shown on drawings
LUMPSUM PRE-PRICED SCHEDULES OF WORKS
Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-II (SEC-I) brought forward from serial page No. 30
Lump sum price worked out by the contractor for INTERNAL ELECTRIC SUPPLY WORKS as listed in Schedule 'A' Part-III (SEC-I) brought forward from serial page No. 34
Lump sum price worked out by the contractor for ROAD, PATH, CULVERT WORKS listed in Schedule 'A' Part-IV brought forward from serial page No. 37
Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule 'A' Part-V brought forward from serial page No. 39.
Lump sum price worked out by the contractor for SECUTITY FENCING, COMPOUND WALL AND GATE WORKSas listed in Schedule 'A' Part-VI brought forward from serial page No. 41
Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS as listed in Schedule 'A' Part-VII brought forward from serial page No. 43
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-VIII brought forward from serial page No. 44
Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS as listed in Schedule 'A' Part-IX (SEC-I) brought forward from serial page No. 47
Lump sum price worked out by the contractor for SITE CLEARANCE WORKS as listed in Schedule 'A' Part-X brought forward from serial page No. 48
SCH 'A' PART-II(SEC-II) INTERNAL WATER SUPPLY WORKS FOR SPECIALISED ITEMS
Supply and fixing 15mm bore health faucet CP brass screwed down high pressure, with 100 to 150cm long PVC connection pipe including rubber ring gaskets etc complete all as specified and directed.
Supply and fixing Aquisense sensor faucet for wash basin with 200mm long spout (wall mounted model) complete with plastic installation box with 02 Nos. control cocks for Hot & Cold water supply screwed down to 15mm bore dia GI pipe complete all as specified and directed. (Make : 15 Jaquar, Cat Part No. SNR 51071)
Supply and fixing soft touch dual flow concealed type flushing valve set for western type commode with auto shut off (complete with installation box) screwed down to 15mm bore dia iron pipes, complete all as specified and directed. (Make : Jaquar, Cat Pat No. SFT 085)
Supplying and fixing auto closing concealed urinal flush valve with wall flange screwed down to 15 mm bore dia iron pipe, complete all as specified and directed. (Make : Jaquar, Cat Pat No PRS-073)
Supply and fixing concealed 4-way divertor set with Hot & Cold concealed stop cock with built in non-return valves (composite on piece body) complete screwed down to 15mm bore dia iron pipes, complete all as specified and directed. (Make : Jaquar, Cat Pat No. FUS 29427)
SCH 'A' PART-III (SEC-II) INTERNAL ELECTRIFICATION WORKS
Supply and fixing fluorescent tube light fittings T-5, 1x28 watt, 230 V, surface/pendant mounted type, epoxy powder coated CRCA sheet housing complete with tube -01 No, lamp holders with electronic ballast having PF not less than 0.9, connector block etc, Complete with all accessories prewired and including connecting up with three core twisted flexible copper conductor cable with suitable size, complete all as specified and directed. Make: Surya SDB 128T-EB-1/P401 or Havells LHIT 01128 or Philips TMS 122ML x TLS-28 EBT
Supply and fixing CFL light fitting 1x15 Watt, 230 Volts, 50Hz wall mounting decorative polycorbonate fitting with retrofit 1x15 Watt CFL having PF not less than 0.9 complete with all accessories prewired and including connecting up with three core x 23/0.0076 size twisted flexible copper conductor cable complete all as specified and directed.
Supply and fixing retrofit type 1x18 watt CFL having PF not less than 0.9 with all accessories complete all as specified and directed.
Supplying and fixing Telephone socket with top connector with suitable size of module for fixing arrangement, complete all as specified and directed.
Supply and fixing TV Socket outlet single with suitable module, complete all as specififed and directed.
Supply and fixing MCB TPN 415 volts, 50 Hz, 10 KA 'C' curve of rating (50-63Amp), complete all as specified and directed.
Supply and fixing MCB SPN 240 volts, 50 Hz, 10 KA 'C' curve of rating (6-32A), complete all as specified and directed.
Supply and fixing isolator TP 415 V, 50 HZ 10 KA of rating (125A), complete all as specified and directed.
Supply and fixing isolator FP 415 Volts, 50 HZ 10 KA of rating (100Amp), complete all as specified and directed.
Supply and fixing isolator FP 415 Volts, 50 HZ 10 KA of rating (63A), complete all as specified and directed.
Supply and fixing MCB isolator TP 415V, 50Hz, 10KA 'C' curve of rating (100A), complete all as specified and directed.
Supply and fixing MCB SP 240V, 50HZ 10 KA 'C' curve of rating (0.5-5A), complete all as specified and directed.
Supply and fixing MCB SP 240V, 50HZ 10 KA 'C' curve of rating (6-32A), complete all as specified and directed.
Supply and fixing 1x85 watt street light fitting epoxy black powder coated sheet steel housing with epoxy white powder coated CRCA sheet steel gear tray, clear acrylic cover aluminium reflector including 1x85 W CFL PF not less than 0.9 mounted on wall with GI pipe light grade 40mm dia of 1.2 mtr length bend to shape with 2 Nos FI clamp 50x6mm with suitable size nuts, bolts and making the connection from ceiling rose to fitting, complete with all acessories all as specified and directed.
Supply and fixing CFL light fitting 4x14 W, 230 V, 50Hz wall/surface mounted decorative polycarbonate fitting with retrofit including 4x14 Watt CFL having PF not less than 0.9 prewired with all accessories complete all as specified and directed.
Supply and fixing MCCB four pole 415V, 50 HZ, 10KA with adjustable thermal setting of rating (200A), complete all as specified and directed. B58
Supply and fixing MCCB four pole 415V, 50 HZ, 35KA with adjustable thermal setting of rating (400A), complete all as specified and directed.
Supply, installation, commissioning and testing of distribution board indoor type 2mm thick MS sheet factory made CRCA sheet dust and vermin proof and angle iron of size 50x50x6mm frame complete with double door infront having packing arrangement and coiled fixed type shelter at rear out door type incl spray painting with one coat of red oxide and two coats of synthetic enamel paint over it in and incl copper bus bar chamber 450 Amps comprising of the following :- (a) MCCB 4 pole, 315 Amps, 415 volts 3 phase, 35 KA with adjustable thermal setting -01 No (Incoming) (b) MCCB 3 pole, 125 Amps, 415 volts 3 phase, 16 KA with adjustable thermal setting -02 Nos (Outgoing) (c) MCCB 3 pole, 100 Amps, 415 volts 3 phase, 16 KA with adjustable thermal setting -01 No (Outgoing) (d) MCCB 3 pole, 63 Amps, 415 volts 3 phase, 16 KA with adjustable thermal setting -01 No (Outgoing)
Supply, installation, commissioning and testing of distribution board indoor type 2mm thick MS sheet factory made CRCA sheet dust and vermin proof and angle iron of size 50x50x6mm frame complete with double door infront having packing arrangement and coiled fixed type shelter at rear out door type incl spray painting with one coat of red oxide and two coats of synthetic enamel paint over it in and incl copper bus bar chamber 300 Amps comprising of the following :- (a) MCCB 4 pole, 200 Amps, 415 volts 3 phase, 25 KA with adjustable thermal setting -01 No (Incoming) (b) MCCB 3 pole, 100 Amps, 415 volts 3 phase, 16 KA with adjustable thermal setting -02 Nos (Outgoing) (c) MCCB 3 pole, 63 Amps, 415 volts 3 phase, 16 KA with adjustable thermal setting -01 No (Outgoing)
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x6 mm thick burried directly in gound (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connecting to galvanised iron earth lead 4mm dia by means of bolts, nuts check nuts and washers of galvanised iron and 4 mm dia GI earth wire protected by provn of GI medium grade pipe 15mm bore upto 7.5 mtr including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (Weight not less than 4kg/Sqm) and frame of angle iron 25x 25x3mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard/dense soil, returing filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 of SSR Part -I and connecting to earth test point all as specified or indicated including testing on completion, complete all as specified and directed. Note : The quoted rate of earthing shall be deemed to include cost of 7.5 m long galvanised wire 4 mm dia and protection pipe 15 mm bore medium grade GI light grade 20 mm bore watering pipe. Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted rates.
Supply & fixing only exhaust fan ventilating type of plastic body of size 250mm sweep complete with all accessories like louver shutter etc including provision of PCC grouting and duly connecting up with 3 core flexible copper conductor cable of suitable size from ceiling rose to fan, complete all as specified and directed.
SCH 'A' PART-IX (SEC-II) EXTERNAL ELECTRIFICATION WORKS
Earthing complete with GI earth plate electrode 60cm x60cmx6mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level) with top edge of plate not less than 1.5 mtrs below ground level, connetcting with GI earth strip of size 32mm x 6mm by means of bolts , nuts , check nuts and washers of bronze and provisioning of GI tubing medium grade (ISI marked) of size 40mm bore for protection of earth strip including PCC with 1:2:4 type B1 (using 20mm graded crushed stone aggregates) CI frame and cover of angle iron 40x40x6mm with lug 02Nos and handle 6mm dia MS bar made to shape GI light grade 20mm bore pipe of watering perforated at bottom 1.75m long placed on top edge of earth plate, charcoal and common salt filling , test point made out of Bronze/Gun metal of size 75x75x20mm with fixing arrangement funnel wire mesh including excavation and earth work in soft/loose soil , returning filling in and removal of surplus surplus soil to a distance n.exc 50m all as per electrical plate No 03 of SSR Pt-I to earth test point including testing on completion all as specified and directed. NOTE: The quoted rate of Earthing shall be deemed to included cost of 7.5 M long GI earth strip 32x6 mm and protection pipe of 40mm bore medium grade 20mm bore light grade watering pipe . Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted rates.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x6mm thick burried directly in ground( Earth pit not less than 2.25 mtrs deep below normal ground level) with top edge of plate not less than 1.5 mtrs below ground level connecting to galvanised iron earth wire 4mm dia by means of bolts , nuts , check nuts and washers of galvanised iron and provision of GI tubing medium grade (ISI Marked) of size 20 mm bore for protection of GI earth wire 4mm dia including PCC with 1:2:4 type B1 using 20mm graded crushed stone aggregates CI frame and cover of angle iron 40x40x6mm with lugs 02 Nos and handle 6mm dia MS Bar made to shape GI light grade 20mm bore pipe for watering perforated at bottom 1.75M long placed on top edge of earth plate, charcoal and common salt filling , test point made out of Bronze/Gun metal of size 75x75x20mm with fixing arrangement funnel wire mesh including excavation and earth work in soft /loose soil , returning filling in and removal of surplus soil to a distane n.exc 50m all as per per Electric plate No 03 of SSR Pt-I to earth test point all as specified and directed. Note:- The quoted rate of rathing shall be deemed to included cost of 7.5m long galvanised wire 4mm dia and protection pipe of 40 mm bore medium grade , 20mm bore light grade watering pipe, any variation in length shall be adjusted through deviation order to be based on SSR rates adjusted with quoted rates.
Laying only cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 Volts grade ISI marked as per IS-7098-I laid in trenches ducts or fixing or passing through GI pipe across the road /Path/drains/alongwith wall/floor equivalant etc cross sectional area of cable 400 Sqmm 3.5 core.
Laying only cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 Volts grade ISI marked as per IS-7098-I laid in trenches ducts or fixing or passing through GI pipe across the road /Path/drains/alongwith wall/floor equivalant etc cross sectional area of cable 150 Sqmm 3.5 core.
Laying only cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 Volts grade ISI marked as per IS-7098-I laid in trenches ducts or fixing or passing through GI pipe across the road /Path/drains/alongwith wall/floor equivalant etc cross sectional area of cable 50 Sqmm 3.5 core.
Laying only cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 Volts grade ISI marked as per IS-7098-I laid in trenches ducts or fixing or passing through GI pipe across the road /Path/drains/alongwith wall/floor equivalant etc cross sectional area of cable 25 Sqmm 4 core.
Laying only cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 Volts grade ISI marked as per IS-7098-I laid in trenches ducts or fixing or passing through GI pipe across the road /Path/drains/alongwith wall/floor equivalant etc cross sectional area of cable 10 Sqmm 2 core. Note for srl item No 7.03 to 7.07: (a) Excavation , earth work, sand cushioning, brick cable covers, protection pipe shall be measured and paid seperately. (b) Cables shall be issued under Sch 'B' stores.
Supply, installation, testing and commissioning of Diesel Engine driven generating set water cooled capacity 350KVA (280 KW) , 415 volts , 0.8 PF at NTP, mounted on common base platform with flexible coupling , 1500 RPM , alongwith sound proof enclosures (Acoustic Enclosures) designed for reducuing the sound level less than 75d BA at 1.00 m of (average) IS 10001/.10002 Part -10 as per approved CPCB norms and as per GSR 371 (E) dated 17.05.2002 with silencer pipe and silencer muffler covered with asbestos rope 25mm thick independently supported from Engine to outside of power house upto 1.00 mtr cold start kit, Battery start with suitable size cables for connecting from DG sets to DG set panel board DG Set shall be capable of operating in temperature range off (-15°C to +35°C ) and PCC foundation as recommended with and including the following:-
(A) PRIME MOVER :- Vertical diesel engine of suitable capacity as per manufacturer recommendation water cooled,(Radiator mounted) closed circuit as per IS-10001/10002 or ISO -3046 direct injection type with turbo charged. The diesel engine shall be capable of running 24 hrs contiunously with 10% overloading for one hour in every 12 hours as per BS-5514/BS-649. Engine shall be equipped with all standard fitting as per manufacturer's recommendations and mounted on common base plateform through flexible coupling with following acessories- (a) RPM cum hour meter. (b) Battery charging Ammeter. (c) Ignition key and starting with push button switch. (d) Lubricating oil pressure gauge. (e) Electronic governor controlling (f) Toggle switch for idle running
(g) Oil temprature gauge (h) Water temperature guage (I) Safety controlled trip for the following :- (i) High water temp. (ii) Low lubricating oil pressure,. (iii) Over speed. (k) Lubricant oil heater to avoid freezing. (j) 24 Volts starting equipment comprising of the followings:- (i) 02 No. 12 volts 180 AH battery.(Maintenance free type) Make : Exide type 25xnN 21 or equivalent as recommended by manufacturer. (ii) Battery Charging alternator with inbuilt regulator. (iii) Self starter motor of suitable capacity. (iv) Battery leads (copper stranded cable) of suitable size with brass thimbles and terminals.
(B) ALTERNATOR:- Alternator of capacity 350 KVA (280KW), 3 phase, 50 cycles 415 volts, 4 wire supply at NTP 0.8 PF running @ 1500 RPM self excited, self regulated, mounted on common base frame mounted on a permanent foundation screen protected with self excited field brush rotating fixed designed to be coupled with above engine through flexible coupling. The alternator shall be conforming to BS-2613 or IS-4722.
(D) OTHER FITTNGS :- (a) Battery Charger :- Battery Charger having electric circuit consisitng of triodes rectifiers, capacitors and resistance etc. The battery charger should be able to charge 2 No's of 12 volts 180 AH battery with suitable battery charging Ammeter with two Nos of lead for charging with clips , mounted on suitable angle iron frame duly painted -01 Nos (b) Integral Fuel tank of suitable capacity as per manufacturer's recommendations with all connected pipes and fittings upto fuel pump and over flow pipe from engine to tank including level indicating guage duly marked and drain valve and air vent plug etc.
E) Maintenance spares:- (i) Fuel filter element-02 Nos. (ii) Oil filter element-03 Nos. (iii) Element air cleaner outer-06 Nos(iv) Element air cleaner inner-06 Nos (v) 'V'Belt -02 Nos (vi) Filter lubricant oil bypass-02 Nos. (F) DG Set shall be supplied alongwith acoustic enclosure of the manufacturer suitable for 350 KVA DG set as per CPCB Norms. Notes:- (i) Complete DG Set shall be mounted on foundation as per design of manufacturer with in overall cost quoted. (ii) Precommissioning test shall be carried out by rep of Accepting Officer within overall cost qouted . POL shall be arranged by the contractor .(iii) Contractor shall produce a copy of approved certificate to authenticate the above from the OEM/DE (iv) Higher capacity DG set can be offered by contractor with in overall cost quoted.
Supply, installation, testing and commissioning of HT panel having following specifications:- (A) Indoor vaccum circuit breaker panel suitable for 11 KV , 400 Amps , 25 KA for 3 Sec for incommer cum outgoing conforming to IEC 62271-200 , class front accessed having following specifications:- Each comprising of following items:- (a) 400 amps continous rated electrolytic copper bus bar, droppers and bus bars should be insulated with full system voltage sleeves of Reychem or equivalant Make. (b) Trolly mounted vaccum circuit breaker as per IEC 62271-100. Vaccum circuit breaker should have three no resin encapsulated vaccum bottles. (c) Motorized spring charging mechnism with integral spring charging handle for manual spring charge. (d) Cast resin current transformer 11KV, 50-25/5-5A, Core 1 class 1.0 15 VA, Core 2: SP10, 15VA. (e) Cast resin potential transformer 11KV/V3/110V/V3/110V/3 50VA, CI 1.0, CI 3P and HT fuse at the primary end 04 pole MCB at the secondary end of the PT. (f) Acessories like local remote switch , breaker control switch (T-N-C) space heater with thermostate,DC & AC control circuit through, MCB , indicating lamps for RYB spring charge , DC supply healthy , breaker ON/OFF , breaker in SERVICE /TEST as per manufacturer. (g) Multifunction meter with RS 485 port model No EM6400 of CONSERV make or equivalant in L&T make. (h) Digital Ammeter and digital Voltmeter. (j) Master trip relay.
(k) Comperhensive numrical protection relay as per IEC 61850 compatible for directional and non directional O/C , E/F, U/V, O/V protection . Make SIEMESN/L&T/ALSTOM/AREVA/ABB 1. Trip ckt supervision. 2. Disturbance recorder. 3. Event log with date and time. 4. Measurement and control features (i) Panel should also have additional facility like:- (a) Intermittant rated closing and tripping coil. (b) Fully internal arc type tested (25KA for 1 Sec) (c) Vaccum bottles should be epoxy encapsulated (d) Racking in/out , manual closing /tripping compartment door closed. 5. Breaker shall be provided with following contacts. 5(a) Auxillary switch with 06 Nos +6NC Mounted on the draw out portion of the switch gear. 5(b) Position switches with 03 Nos +1NC for each position in SERVICE and TEST. 6. Panel height should not exceed 2300 mm. 7. Electrical & mechnical interlcking between two Nos incommers. 8. Type test reports for internal arc test to be submitted alongwith submission of drawings.
COMMON NOTES:- (a) Drawings for panel shall be got approved from GE before placement of order by contractor. (b) CT Ratio is given is tentative and is subject final approval of GE. (c) Precommissioning test of panel shall be carried out by EI from HQ CENC or Rep of AO within overall cost of quoted by contractor. (d) Any modification required to match the system with existing system is deemed to be included in overall cost quoted by contractor. (e) Power pack duly fitted by firm supplying VCBs shall be supplied with in overall cost quoted. (f) Make of HT Panel : ABB /Siemen/L&T/AREVA/C&S/Schnider
Supply and installation , commissioning and testing of transformer , copper wound with tertiary winding step down indoor type complete withh all standard fitting of capaciy 315 KVA, AC phase, 3 wire primary , 4 wire secondary 50C/S. 11/0.433KV, oil immersed naturally cooled with external cooling tube and having off load top changing gear hand operating with tapping for voltage (±)2.5% , (±) 5% (±) 7.5% and (±) 10% of rated voltage , with and incl first filling of transformer oil including standard acessories as per IS-2026 and making connection on HT & LT complete as specified and directed. NOTES:- (I) Foundation for out door transformer cattle fencing around transformer is incl in the above rates. (ii) Precommissioning of transformer shall be carried out by Electrical Inspector from HQ CENC or Rep of Accepting Officer with in overall cost quoted.
Supply and installation , commissioning and testing of distribution board (KIOSK Type) factory made dust and vermin proof , fabricated out of 3.15mm thick MS sheet and angle iron of size 50x50x6mm frame complete with openable shelters in front having proper locking arrangement and bolted fixed type shelters at rear out door type including painting with spray painting internally and externally with two coats of hammer tone over a coat of primer with and including 600 Amps copper bus bar mounted on porcelin insulators in totally enclosed chamber for inspection of three phases 440 volts 50 Hz AC supply including wiring to panel with suitable size PVC insulated and sheathed copper cable duly mounted on angle iron frame of size 50x50x6mm in PCC block complete in all respect for following:- (a) MCCB 4 pole 415Volts 500 Amps 35 KA with adjustable thermal setting (Incomming) -01 No. (b) On load change over switch , 415 volts , four pole 400 Amps -01 No. (c) MCCB 4 pole, 415 Volts 315 Amps 25 KA with adjustable thermal setting (outgoing) (one standby)-02 Nos. (d) MCCB 4 pole, 415 Volts 100 Amps 25 KA with adjustable thermal setting (outgoing) -02 Nos. (e) MCB 32 Amps TPN 10 KA 'C' curve -01 No. (f) Digital Ammeter as well as Voltmeter each of size 4"x4": -01 No. (g) Indication lamps RYB -01 Nos
SCH 'A' PART-XI AIR CONDITIONING WORKS
Supply , testing and installation splits unit indoor/outdoor complete with cordless remote control unit and with cooling and heating function of capacity 2 Ton complete with fixing arangements on wall and acessories , complete all as specified.. Note : The unit should be functional between minus 15° to + 45°.
Supply and fixing voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170V to 250 V with output voltage stabilized at 230 volts with accuracy of ± 2.5% and of capacity 5.0 KVA complete all as specified and directed.
SCH 'A' PART-XII CENTRAL HEATING SYSTEM WORKS
OIL FIRED BOILER:-Supply, installation, testing and commissioning of oil fired glycol based hot water generator using HSD oil complete with combustion chamber and equipment automatic monoblock burner assembly tubes , control panel with sequence controller, photo cell for flame failure, HT transfer electrodes, blower assembly, electric panel, mounting frame, pressure gauges, at inlet and out let , suitable for operation on 50 Hz, 3 phase 415 volts AC supply and all as specified. Hot water inlet temp = 65° C Hot water outlet temp = 75° C Capacity - 3,00,000 K Cal/hr at MSL Note :- (a) Higher capacity generator can be offered by contractor within overall cost quoted. (b) Pre-dispatch inspection can be carried out by rep of Accepting Officer within overall cost quoted. Decision of Accepting officer shall be final and binding in this regard.
GLYCOL CIRCULATION CENTRIFUGAL PUMP:- Supply, installation, testing and commissioning of monoblock centrifugal pump, driven by suitable capacity electric motor for ethylene glycol of 500 LPM 25 metre head complete with accessories and including plain cement concrete foundation etc complete , all as specified & directed.
GLYCOL MAKE UP CENTRIFUGAL PUMPS :- Supply, installation, testing and commissioning of monoblock centrifugal pump with Bronze impeller, driven by suitable capacity electric motor for glycol fluid make up and mixing with flow rate of 5 LPM and 5 metre head with acessories including cement concrete foundation etc complete , all as specified & directed.
FUEL GAS CHIMNEY:-Supply and installation of mild steel flue gas chimney made out of 3mm thick mild steel sheet, minimum 1.20 metre above the highest point of the plant room including connection from boiler to main chimney fabricated from 3mm mild steel sheet all as specified. Notes:- (i) The item shall be complete with the mounting/fixing arrangement. (ii) The each boiler shall be connected to an indepent chimney. (iii) The portion of the chimney inside the building shall be insulated with fibre glass insulation wool 24 Kg/Cum,50mm thick and insulated portion covered with 28 SWG aluminium cladding.The item shall be complete with mounting/fixing arrangement,complete all as specified and directed.
EXPANSION TANK: Supply and installation of overhead expansion tank of size 1000ltrs PVC tank complete covered with 13mm closed cell electrometric insulation complete with removable lid, in,out,drain, over flow system, including mounting arrangement making connections etc complete all as specified and directed.
GLYCOL FLUID TANK : Supply and installation of 1000 Litre capacity HDPE tank with removable lid, in,out,drain, over flow connection system, mounting arrangement etc complete connection.
BULK OIL STORAGE TANK :- Supply, installation, testing and connecting with the system and commissioning of Horizontal Cylindrical oil storage tank made out of mild steel design temprature (-) 30°C and design pressure atmosphere (+) static head of liquid. (i) Storage capacity (Nominal) : 10 KL (ii) Gross Capacity (not exceeding 10.2 KL) (iii) Shell thickness : 5mm (iv) End plate thickness : 6mm Note :- Tank shall be complete with all nozzles, manhole, lifting lugs,earthing lugs, vent pipe dip stick suitable dia inlet,outlet connections and return pipes with flanges as per specifications including civil works for installation and staging.
DAY OIL STORAGE TANK : Supply , installation, testing and commissioning of kerosene /HSD oil day service tank rectangular mild steel construction with capacity 990 litres complete with inlet, outlet , drain out pipe. Tank shall be made out of 3mm thick mild steel and will be provided with supports made out of minimum 50mm NB class 'B' pipe to keep tank base at minimum (1000 mm) above finished floor level complete, All as specified and directed.
TRANSFER GEAR OIL PUMP K OIL (SELF PRIMING):- Supply, installation, testing and commissioning of Rotary gear transfer pumps for capacity 15 LPM, 10 mtr head, for Kerosene Oil complete with base frame, foundation bolts, coupling and coupling guard and TEFC flame proof motor (2 HP), and other accessories required for commissioning complete , all as specified.
HSD OIL PIPING :- Supply, installation, testing and commissioning of mild steel heavy duty 'C' class, pipe including bends, reducers, flanges, nuts, bolts etc, complete in all respect size of 40 mm bore pipe all as specified and directed.
HSD OIL PIPING :- Supply, installation, testing and commissioning of mild steel heavy duty class 'C', pipe including bends, reducers, flanges, nuts, bolts etc, complete in all of 25 mm bore pipe all as specified and directed.
HSD OIL PIPING :- Supply, installation, testing and commissioning of ball valve of size 25 mm dia complete all as specified and directed.
HSD OIL PIPING :- Supply, installation, testing and commissioning of Non return valve of size 25 mm dia complete all as specified and directed.
HSD OIL PIPING :- Supply, installation, testing and commissioning of Y-oil strainer of size 25mm bore complete all as specified and directed.
HSD OIL PIPING :- Supply, installation, testing and commissioning of ball valve of size 40 mm dia complete all as specified and directed.
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 150 mm dia pipe with 25 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 100 mm dia pipe with 25 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 80 mm dia pipe with 25 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 65 mm dia pipe with 19 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 50 mm dia pipe with 19 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 40 mm dia pipe with 19 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING :Supply and laying, connecting and testing of mild steel ERW, class 'C' piping complete with fittings duly insulated of thickness mentioned there in with closed cell elastomeric insulation 30 to 40 Kg/m3 density covered with shrink wrap polythene sheet for 32 mm dia pipe with 19 mm thick nitrile insulation of Hot Glycol fluid pipes. Note :- The pipes exposed to atmosphere or buried under ground will be insulated with, 25mm thick insulation and along the walls inside the building with 19mm thick insulation
HOT GLYCOL FLUID PIPING Supply, laying, connecting, and testing of 3 layer poly propylene random copolymer pipes or composite pipes conforming to PN-16 complete with fittings duly insulated with 13 mm thick closed cell elastomeric insulation 30 to 40 Kg/m3 density for 25 mm dia OD pipe with 13 mm thick nitrile insulation of Hot Glycol fluid pipes.
HOT GLYCOL FLUID PIPING Supply and laying, connecting, fixing and testing of 3 layer poly propylene random copolymer pipes or composite pipes conforming to PN-16 complete with fittings duly insulated with 13 mm thick closed cell elastomeric insulation 30 to 40 Kg/m3 density for 20 mm bore OD pipe with 13 mm thick nitrile insulation of Hot Glycol fluid pipes.
Supply, fixing and testing of Butter fly valves 100mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Dual plate Non Return valves 100mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Balancing valves 100 mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Balancing valves 80 mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Balancing valves 50 mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Butter fly valves 80mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Butter fly valves 50mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Ball valves 25mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Inlet, outlet valve for FCU 15mm dia for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of pressure guage with cocks and syphon for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Water flow switches for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of Automatic air purgers valves for HOT GLYCOL FLUID PIPING complete all as specified and directed.
Supply, fixing and testing of 12mm dia Polyurethene pipe for connections to FCUs for HOT GLYCOL FLUID PIPING complete all as specified and directed.
GLYCOL CHARGE:- Supply , mixing and filling of mono ethylene glycol concertrate alongwith the necessary addictiuve and inbabitor in congnition and supplied in barrels. The mixing freezing temperatureshall be minus 16° C all as specified. However the mode of payment and operations involved for this item shall as under:- Note :- (a) Mono ethylene glycol in concertrate form shall only be measured and paid under this item. (b) Material and labour for mixing, filling prepration of glycol charge to get total quantity of mixture including first filling required for operation of CHS plant and network having 70% quantity of treated water availabble at site and 30% of monoethylene glycol supplied under item 9.38 to attain the freezing temp of mixture as minus 16°C the quoted rates shall be deemed to include the above activity ./work. (c) The water for prepration of mixture will be supplied by MES without any extra charges for these items only. The water shall be supplied at a point decided by GE and quoted rates shall deemed to be included for transportaion of same from take off point. (d) Any other additives and inhabitors as per the requirement laid down in relevant IS shall also deemed to include in quoted rate. (e) Empty barrels shall be property of contractor.
FAN COIL UNITS:- Supply , installation , testing and commissioning of wall/floor mounted fan coil units complete with top grill High impact moulded polymers 3 Speed motor , wall mounting brackets inlet outlet manfold etc complete of capacity 6000 kcal/hr complete all as specified and directed.
FAN COIL UNITS:- Supply , installation , testing and commissioning of wall/floor mounted fan coil units complete with top grill EBS (Pastic ) casing , 3 Speed motor , wall mounting brackets inlet outlet manfold etc complete of capacity 4500 kcal/hr complete all as specified and directed.
FAN COIL UNITS:- Supply , installation , testing and commissioning of wall/floor mounted fan coil units complete with top grill EBS (Pastic ) casing , 3 Speed motor , wall mounting brackets inlet outlet manfold etc complete of capacity 3000 kcal/hr complete all as specified and directed.
FAN COIL UNITS:- Supply , installation , testing and commissioning of Towel Radiator wall mounted 600x910 mm size complete all as specified and directed.
CABLE TRAYS:- Supplying , fabricating and installing perforated mild steel cable tray of size 150mm width x 50mm depth including horizantal and verticl bends reducers , tees, cross members and other acessories as required and duly suspended from the ceiling with mild steel suspenders and incluing painting with two coats of synthetic enamels paint over a coat zinc chrome primer, all as specified and directed (For cabling work in plant room)
CABLES : Supply , laying and testing of PVC insulated and usheathed (ISI marked) multistrand conductor , armoured cable of 1.1KV grade conforming to IS 1554 of size 3x 6 Sqmm (aluminium conductor) all as specified.
CABLES : Supply , laying and testing of PVC insulated and usheathed (ISI marked) multistrand conductor , armoured cable of 1.1KV grade conforming to IS 1554 of size 3x 4 Sqmm (aluminium conductor) all as specified.
CABLES : Supply , laying and testing of PVC insulated and usheathed (ISI marked) multistrand conductor , armoured cable of 1.1KV grade conforming to IS 1554 of size 2x 4 Sqmm (aluminium conductor) all as specified.
ELECTRICAL ACESSORIES:- Providing and fixing 6 SWG dia GI Wire on surface or in recess for loop earthing interconnecting the main panel and other electrical equipments.
Danger notice plate of 200mm x150mm made of mild steel atleast 2mm thick and viterous enamels white on both sides painted with letters , figures and conventional skull and bones in signal red colour onfront side as required , including fixing with MS clamps , bolts and nuts of approved size all as specified.
Providing "NO SMOKING" and "FLAMABLE' sign board as per requirement of Pertrollium rules and CCOE Nagpur.
Earthing complete with galvanised steel earth plate electrode 60cm x60cmx6mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level) with top edge of plate not less than 1.5 mtrs below ground level, connecting with galvanised Iron earth lead strip of size 32mm x 6mm by means of bolts , nuts , check nuts and washers of GI and earth wire protected by provision of GI Pipe medium grade 40mm bore including provn of concrete pit in PCC 1:2:4 type B1 (using 20mm graded crushed stone aggregates with 40 mm thick cover RCC 1:2:4 reinforced with XPM (weight not less than 4kg/Sqm) and frame of angle iron 40x40x6mm with lug 02Nos and handle 6mm dia MS bar handle made to shape GI light grade 20mm bore pipe for watering perforated at bottom 1.75m long placed on top edge of earth plate, charcoal and common salt and charcoal filling , test point made out of phopsphorus /Bronze with fixing arrangement funnel wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus surplus soil to a distance n.exc 50m all as per electrical plate No 03 of SSR 2009 Pt-I to and connection to earth test point all as specified and testing on completion. NOTE:- Item of earthing included cost of 7.5M long Galvanised iron earth lead 32x6 mm size and protection pipe of 40mm bore GI medium grade and 20 mm bore light grade watering pipe. Any variation in length shall be adjusted through deviation order.
Excavation in trenchees not exceeding 1.50 m wide and not exceeding 1.50 m in depth for foundation , laying of pipes etc and not exc 10 Sqm on plan for manholes etc and n exc 1.5m in depth and getting out in hard/dense soil complete all as specified and directed.
Returning filling in with approved excavated soil including spreading levelling , watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed.
Removing excavated material (Soil) not exceeding 50m and depositing where directed at level not exceeding 1.50 m above the starting point , complete all as specified and directed.
Notice board (Display Board) of ize 1200mm x900mm as shown on drawing NO CESZ/TD-175/94 Sheet 1/1 for displaying the duty roaster description and including resuscitation chart in three languages for electric shock and burn injury complete as specified and directed.
Supply and fixing MCB SPN 240 V, 50 Hz ,10 KA 'C' curve of rating (6-32 A) complete all as specified and directed.
Supply and fixing MCB SPN 240 V, 50 Hz ,10 KA 'C' curve of rating (6-32 A) complete all as specified and directed.
SCH 'A' PART-XIII SOLAR WATER HEATER WORKS
Supply installation testing and commissioning of solar water heating system with ETC TECHNOLOGY with electrical back up as per manufacturer specification suitable for single phase 220V AC supply complete with ETC type collector Hot water tank stands etc as per the following specifications (A) Collector : Collector 300 LPD ETC type with 30 Nos of vertical evacuated tubes duly installed on angle iron frame transmittance of cover glass tubes 85% reflectances of glass tubes more then 85% absorbance of glass tubes 92% type of coating (Cu/AI/SS) and reflectance of coating as recommended by manufacturer having wind resistance up to 100 Km with freezing resistance minus 20°C and heating up co-efficient 240°C having average thermal efficiency 58.76% and maximum rise in temp 53.04°C (in 24 hours) without night losses fixed at angle of incliation from horizontal as per recommendation of manufaturer. (B) Hot water tank : Hot water tank of 300 ltr capacity with 6KW electrical backup made out of stainless steel sheet not less than 0.5mm thick duly insulated with puff insulation 50mm thick having density not less than 36Kg having thermal conducitivity 0.29 m/k duly covered with PPGI cladding fixed with temperature gauge inlet and outlet valves of suitable size duly installed on staging fabricated out of MS angle of apporpriate size as recommended by manufacturer duly fixed properly and painted with two coats of anti corrosive paint over a coat of red oxide primer. Note:- (a) 5 Nos of spare ETC glass tubes with each system are to be supplied by the contractor with in overall cost quoted. (b) Any other item required for successful operation of system is deemed to included in overall cost quoted. (c) System shall be installed and commissioned by authorised rep of firm supplying the solar water heating system. (d) Stands for mounting of collector and hot water tank are included in overall cost quoted.
mirco builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .