Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹1.1 Cr | L1 | Accepted-AOC Reasonable rate |
| 2 | L2₹1.1 Cr+₹4.7 L (4.43%)Rejected-Finance HENGRABAI LICHUBAGAN BYE LANE 2 HOUSE NO 2 GUWAHATI 781036 ASSAM | KAMRUP METRO | ASSAM | 781036 | ₹1.1 Cr+₹4.7 L (4.43%) | L2 | Rejected-Finance Quoted amount higher than L1 |
| 3 | L3₹1.4 Cr+₹30.2 L (28.4%)Rejected-Finance | ₹1.4 Cr+₹30.2 L (28.4%) | L3 | Rejected-Finance Quoted amount higher than L1 |
| 4 | Rejected-Technical KHASRA NO 145 GROUND FLOOR NEAR JAIN MOHALLA JATO KI CHOPAL VILLAGE KHERA KALAN NEW DELHI 110082 | NORTH | DELHI | 110082 | - | - | Rejected-Technical Having appropriate category of b (ii) but two class below, Value of wk in hand is more than 05 time tendering limit. Does not have b(iii) category. Hence Rejected |
| Sl No | Description | Qty | Unit | PURBANCHAL BUILDERS L1 | S and B Electricals L2 | SPAAN Infratech L3 |
|---|---|---|---|---|---|---|
| 1.00 | Supply & Installation & Testing and Commissioning of 11KV H.T. IN SUBSTATION (2 INCOMER 1 BUSCOUPLER AND SIX OUTGOING). 11KV Indoor Floor mounted, Metal Clad 11 KV, VCB Panel with Al-zinc / GI enclosure with 1Nos VCBs, totally enclosed & Fully interlocked horizontal draw-out, vertical / horizontal isolation type breaker, dust and vermin proof, free standing, having capacities as mentioned below, single break, trip free mechanism, motorised charged and auto-cum-manual closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C supply with short circuit fault level of 500 MVA, complete with self-contained, fully interlocked , rack in rack out mechanism, air insulated but PVC sleeved copper bus bars of 800 A capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO + 4 NC and equipped with following switch gears and accessories etc. and suitable for connecting 3 core 240 Sq.mm XLPE 11 KV cable heat shrinkable end termination (Cable entry from top) etc. as required including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage included in the quoted rate.. | 1 | Each Set | 70,69,999 ₹70,69,999 | 70,00,000 ₹70,00,000 Lowest | 92,25,000 ₹92,25,000 |
| 1.01Note:- BER 11 KV OCB / New VCB Transportation charges , handling charges , tools and plants charges are deemed to be included in the quoted rate. Incomer- 2 Nos. VCB Panels each having the following (a) 1 No. 630A,18.4KA, 11KV, 3 phase, 50 Hz VCB "(b)1 No 3 phase 11 KV/110 Volts PT, class 0.5 accuracy and 100 VA burden with 1 No Voltmeter (0-15 KV), Digital type, selector switch for voltmeter and protection fuses for HT metering upto 12kV on incomer (Voltmeter shall have communication features for monitoring by BMS)" "(c)1 set of dual core 3 CTs 100/1+1A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection." (d) 1 No – multi function meter suitable for operation on 110V a.c supply with RS-485 (e) 1 No - Digital Tri Vector Meter (Trivector meter shall have communication features) "(f) 1 No. Microprocessor based numerical relay for OC and Earth fault protection and 1no surge protector of suitable rating." (g) 1 set of phase indicating lamps with HRC fuses "(h) 1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, 01 | ||||||
| 1.02SPRING CHARGED, TRIP CIRCUIT HEALTHY" (i)1000Amps copper busbar-2 set (common) (j)Test terminal block (k)Trip/Neutral/close switch (l) 1 set of copper bus bar for earthing (common) (m) 1 set of master trip relay & trip circuit healthy supervision relay. (n) Provision for padlocking the incomer VCBs in 'OFF' position. BUSCOUPLER: 1 Nos. of Bus-coupler & Bus-riser provision without metering protection. OUTGOING: 6Nos. VCB Panels each having the following (a) 1 No. 630A,18.4KA, 11KV, 3 phase, 50 Hz VCB "(b)1 No 3 phase 11 KV/110 Volts PT, class 0.5 accuracy and 100 VA burden with 1 No Voltmeter (0-15 KV), Digital type, selector switch for voltmeter and protection fuses for HT metering upto 12 KV on incomer (Voltmeter shall have communication features for monitoring by BMS)" "(c)1 set of dual core 3 CTs 60/1A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection." (d) 1 No – multi function meter suitable for operation on 110V a.c supply with RS-485 (e) 1 No - Digital Tri Vector Meter (Trivector meter shall have communication features) | ||||||
| 1.03"(f) 1 No. Microprocessor based numerical relay for Over current and Earth fault protection and 1 no surge protector of suitable rating." (g) 1 set of phase indicating lamps with HRC fuses "(h) 1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT HEALTHY" (i)1000Amps copper busbar-2 set (common) (j)Test terminal block (k)Trip/Neutral/close switch (l) 1 set of copper bus bar for earthing (common) (m) 1 set of master trip relay & trip circuit healthy supervision relay. (n) Provision for padlocking the incomer VCBs in 'OFF' position. Model: JVACE Nomenclature: 2IC+1BC+6OG --9PNB | ||||||
| 2.00 | Supply & installation & testing and commissioning of 1250 A 33KV 25KA 3 pole outdoor type porcelain clad Vacuum circuit breaker for OH line protection control with CT, mounting MS Structure with necessary hardware (Location: switchyard). Breaker operation shall be with 110 V DC and spring charging shall be 230 V AC. PCVCB shall be suitable for electrical operation and manual operation including spring charging, (MAKE CG POWER) Model: 36PV25A. including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage.
Note:- Transportation charges , handling charges , tools and plants charges are deemed to be included in the quoted rate. | 2 | No. | 4,09,999 ₹8,19,998 | 4,00,000 ₹8,00,000 Lowest | 4,08,760 ₹8,17,520 |
| 3.00 | Design, supply, installation, testing and commissioning of relay panel for outdoor pole mounted PC VCB. Relay shall be with 3 Over current and 1 Earth Fault numeric relay. Relay shall be programmable. Relay panel shall be with alarm annunciator, MFM and indication lamps, suitable ammeter and voltmeter with selector switch.) Make: CGPISL brand including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage.
Note:- Transportation charges , handling charges , tools and plants charges are deemed to be included in the quoted rate. | 2 | No. | 3,69,999 ₹7,39,998 Lowest | 4,20,000 ₹8,40,000 | 4,67,400 ₹9,34,800 |
| 4.00 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 100/1-1A | 3 | No. | 1,19,999 ₹3,59,997 Lowest | 1,50,000 ₹4,50,000 | 1,38,990 ₹4,16,970 |
| 5.00 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 30/1A | 6 | No. | 1,19,999 ₹7,19,994 Lowest | 1,25,000 ₹7,50,000 | 1,35,300 ₹8,11,800 |
| 6.00 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 60/1-1A | 3 | No. | 1,19,999 ₹3,59,997 Lowest | 1,20,000 ₹3,60,000 | 1,35,300 ₹4,05,900 |
| 7.00 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, Hermetically sealed, Outdoor Inductive Voltage Transformer (Hollow Bushing type) | 3 | No. | 1,19,999 ₹3,59,997 | 1,00,000 ₹3,00,000 Lowest | 1,35,300 ₹4,05,900 |
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
31 Jan 2026, 6:55 pmClosed
COL AMIT CHAUBEY
HQ 137 Wks Engr PIN 914137 c/o 99 APO
SPECIAL REPAIR/ REPLACEMENT OF 11 KVA HT VCB AND 2 INCOMER /BUS COUPLER AND SIX OUTGOING 33 KV CT, PT, VCB, CTR AGAINST BERAT MILITARY STATION AGARTALA
2025_MES_719733_3
8043/E8
Open Tender
Civil Works
Item Rate
180 days
Agartala
As per tender documents
6 documents required · 6 mandatory
₹1,000
AGE (I) Agartala
₹2.2 L
Yes
18 Mar 2026
17 Jan 2026
7 Feb 2026
17 Jan 2026
31 Jan 2026
24 Jan 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply & Installation & Testing and Commissioning of 11KV H.T. IN SUBSTATION (2 INCOMER 1 BUSCOUPLER AND SIX OUTGOING). 11KV Indoor Floor mounted, Metal Clad 11 KV, VCB Panel with Al-zinc / GI enclosure with 1Nos VCBs, totally enclosed & Fully interlocked horizontal draw-out, vertical / horizontal isolation type breaker, dust and vermin proof, free standing, having capacities as mentioned below, single break, trip free mechanism, motorised charged and auto-cum-manual closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C supply with short circuit fault level of 500 MVA, complete with self-contained, fully interlocked , rack in rack out mechanism, air insulated but PVC sleeved copper bus bars of 800 A capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO + 4 NC and equipped with following switch gears and accessories etc. and suitable for connecting 3 core 240 Sq.mm XLPE 11 KV cable heat shrinkable end termination (Cable entry from top) etc. as required including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage included in the quoted rate.. | 1 | Each Set | - | - |
| 1.02 | SPRING CHARGED, TRIP CIRCUIT HEALTHY" (i)1000Amps copper busbar-2 set (common) (j)Test terminal block (k)Trip/Neutral/close switch (l) 1 set of copper bus bar for earthing (common) (m) 1 set of master trip relay & trip circuit healthy supervision relay. (n) Provision for padlocking the incomer VCBs in 'OFF' position.
BUSCOUPLER: 1 Nos. of Bus-coupler & Bus-riser provision without metering protection.
OUTGOING: 6Nos. VCB Panels each having the following (a) 1 No. 630A,18.4KA, 11KV, 3 phase, 50 Hz VCB "(b)1 No 3 phase 11 KV/110 Volts PT, class 0.5 accuracy and 100 VA burden with 1 No Voltmeter (0-15 KV), Digital type, selector switch for voltmeter and protection fuses for HT metering upto 12 KV on incomer (Voltmeter shall have communication features for monitoring by BMS)" "(c)1 set of dual core 3 CTs 60/1A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection." (d) 1 No – multi function meter suitable for operation on 110V a.c supply with RS-485 (e) 1 No - Digital Tri Vector Meter (Trivector meter shall have communication features) | - | - | - | - |
| 1.03 | "(f) 1 No. Microprocessor based numerical relay for Over current and Earth fault protection and 1 no surge protector of suitable rating." (g) 1 set of phase indicating lamps with HRC fuses "(h) 1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT HEALTHY" (i)1000Amps copper busbar-2 set (common) (j)Test terminal block (k)Trip/Neutral/close switch (l) 1 set of copper bus bar for earthing (common) (m) 1 set of master trip relay & trip circuit healthy supervision relay. (n) Provision for padlocking the incomer VCBs in 'OFF' position. Model: JVACE Nomenclature: 2IC+1BC+6OG --9PNB | - | - | - | - |
| 2 | Supply & installation & testing and commissioning of 1250 A 33KV 25KA 3 pole outdoor type porcelain clad Vacuum circuit breaker for OH line protection control with CT, mounting MS Structure with necessary hardware (Location: switchyard). Breaker operation shall be with 110 V DC and spring charging shall be 230 V AC. PCVCB shall be suitable for electrical operation and manual operation including spring charging, (MAKE CG POWER) Model: 36PV25A. including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage.
Note:- Transportation charges , handling charges , tools and plants charges are deemed to be included in the quoted rate. | 2 | No. | - | - |
| 3 | Design, supply, installation, testing and commissioning of relay panel for outdoor pole mounted PC VCB. Relay shall be with 3 Over current and 1 Earth Fault numeric relay. Relay shall be programmable. Relay panel shall be with alarm annunciator, MFM and indication lamps, suitable ammeter and voltmeter with selector switch.) Make: CGPISL brand including disconnecting electric supply and dismounting old BER 11 KV OCBs alongwith conecting terminals and deposit to MES E/M store yard by tranporting without damage.
Note:- Transportation charges , handling charges , tools and plants charges are deemed to be included in the quoted rate. | 2 | No. | - | - |
| 4 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 100/1-1A | 3 | No. | - | - |
| 5 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 30/1A | 6 | No. | - | - |
| 6 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, hermetically sealed, Outdoor Current Transformer (LIVE Tank Type) CTR: 60/1-1A | 3 | No. | - | - |
| 7 | Supply & Installation & Testing and Commissioning of 33/ 36 kV, 50Hz, 1ф, Oil Impregnated, Hermetically sealed, Outdoor Inductive Voltage Transformer (Hollow Bushing type) | 3 | No. | - | - |
| 8 | Supply and fixing and (end) termination of outdoor type 33 KV screen conductors suitable for 33 KV XLPE cable upto 3 x 120 -185 Sqmm as per recommended make of 36 KV Sf6 insulated SWG supplier . Screen conductors should be terminated in 36 KV CGS by "Certified jointer " only duly certified by SWG complete all as specified and as directed. | 2 | Each | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
retenderdox3.pdf
Tender Documents • 1.37 MB
BOQ_838826.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .