DY.CITY ENGINEER (SOUTH ZONE)
Annual Rate Contract for Suppy, installation, Testing and commissioning of New Fire Fighting System in Various A.M.C. Buildings in Vatva Ward, South Zone
311748
Tender notice no 02, tender no.188
Open
Civil Works - Others
Ahmedabad
5 documents required · 5 mandatory
₹2,400
municipal commissioner
₹53,721
5 Jun 2026
5 Jun 2026
5 Jun 2026
16 Jun 2026
5 Jun 2026
Name of Work : Annual Rate Contract for Supply, installation, Testing and commissioning of New Fire
Fighting System in Various A.M.C. Buildings in Vatva Ward, South Zone, Ahmedabad
Bill of Quantities
SR. No. Qty Items Unit Rate Per
A Part-A - Fire Hydrant System
Supply, Installation, Testing &
Commissioning of Fire Hydrant & Sprinkler
System as per the Technical Specifications
& tender Drawings .The work shall be
Completed in all respect as per the
Instruction of Engineer Incharge.The system
shall be Integrated with BMS (Refer the
Technical Specifications of BMS Specified in
Electrical Tender Document).The Auto Glow
Signage applicable for the respective
system shall be scope of Vendor.The
Vendor shall Prepare and submit 06 Sets of
detailed shop Drawings as per Tender
Specifications/Tender Drawings, Vendor
also shall Submit 06 Sets of As Built
Drawings and 03 Sets of Soft Copy (in the
form of CD in Editable Format alongwith
applicable Test Certificates,Data
Sheets,Operation & Maintenance Manual)
Supplying, Installation, Testing and
Commissioning of electric driven main
1.1 3.00 Hydrant fire pump suitable for automatic 350000.00 SET
operation and consisting of following:
complete in all respect as required.
a) Back pull out ,Horizontal type, single
stage, centrifugal, end suction pump of cast
iron body & bronze impeller with stainless
steel shaft, mechanical seal to ensure a
minimum pressure of 3.5 kg/sq. cm. at
highest and farthest outlet at specified flow
of 137 m3/Hr (2280 lpm )2900 rpm at
Mtr. head conforming to IS 1520.with
suitable size of footvalve confirming to IS
4038, Pressure rating PN2 , preventing
entry of foreign body to pump through
suction pipe, perfectly flat seating surfaces
for good sealing.
b) Suitable HP Squirrel cage induction
energy efficient motor, TEFC, suitable for
opertion on 415 volts, 3 phase 50 Hz. AC
with IP 55 class protection for enclosure,
horizontal foot mounted type with Class -
'F' insulation, conforming to IS-325.
c) M.S. fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
d) Suitable cement concrete foundation
duly plastered with anti vibration pads.
The pump shall be capable of giving not less
than 150% discharge at ahead not less than
65% of the rated head.
Supplying, installing, testing, &
commissioning of Electric Motor driven
1.2 1.00 Pump suitable for automatic operation 75000.00 SET
consisting of the following ( as per
specification ).- (Terrace Pump)
Back Pull out ,centrifugal end suction type
pump complete for delivery of 900 LPM
against a total head of 30 metres with
bronze impeller complete with Gland
Packing with Complete accessories like Base
Frame,Anti vibration Pads,Coupling etc to
make the system functional in all respect.
Squirrel cage induction , 3 phase ,415 Volt,
50 Hz, Energy Efficient Motor suitable for
above pump. (As per the Specifications of
Motors specified in the Electrical tender
Document) & Supply, Installation, testing &
commissioning of cubical type floor
mounted Electrical panel.The panel shall be
designed as per IS standard & Refer General
Specifications of LT Panels defined in
Electrical Tender Document including the
list approved makes.The Panel shall have
facility to Operate in Auto/Manual Mode of
Terrace Pump. The Pressure Switch ,Flow
switch and control Cabling in between for
the Individual Terrace Pump shall be part of
Vendor's Scope.
Supply, installation, testing, &
commissioning of electric driven automatic
pressurisation pump set consisting of the
Vertical in line ,multistage Jockey pump
complete for delivery of 10.8 m3/hr against
a total head of 70 metres with bronze
impeller complete with Gland Packing with
Complete accessories like Base Frame,Anti
vibration Pads,Coupling etc to make the
system functional in all respect.
Squirrel cage induction , 3 phase ,415 Volt,
50 Hz, Energy Efficient Motor suitable for
above pump. (As per the Specifications of
Motors specified in the Electrical tender
Supplying, Installation, Testing and
Commissioning of diesel engine driven main
1.4 2.00 fire pump suitable for automatic operation 625000.00 SET
and consisting of following: complete in all
respect as required
b) Suitable HP, 1500 /1800 RPM water
cooled with radiator, diesel engine
conforming to relevant BS & IS standard
complete with auto starting mechanism
with Battery,Charging system,Cables, Panel
(As per General Specifications in electrical
Tender), 12/24 volts electric starting
equipment, 180 AH lead acid battery with
battery stand, exhaust pipe extended upto
6 m. outside pump house duly insulated
with 50 mm thick glass wool with 1.0 mm.
thick aluminium sheet cladding, residential
silencer, instruments and protection as per
specification, stop solenoid for auto stop in
the event of fault with audio indications,
painted with post office red colour etc. as
c) One 200 Ltr capacity day oil storage tank
fabricated from 3 mm thick M.S. plates.
Tank shall be provided with inlet, outlet,
overflow, air vent, drain connections, filling
connection & level indicator. Tank shall be
mounted on a suitable steel structure
(Painted with 2 coats of red oxide paint).
Tank shall be provided with two or more
coats of synthetic enamel paint outside
over two coats of red oxide primer.
d) M.S. Fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
e) Suitable cement concrete foundation
duly plastered with anti vibration pads.
a) Back pull out,Horizontal type, single
stage, centrifugal, end suction pump
complete for delivery of 137 m3/hr (2280
LPM) 2150 rpm against a total head of
metres of cast iron body and bronze
impeller with stainless steel shaft,
mechanical seal to ensure a minimum
pressure of 3.5 kg/sq. cm at highest and
farthest outlet at specified flow to make the
system functional in all respect.
FIRE CONTROL PANEL FOR Main Hydrant
2.1 1.00 pump,Sprinkler Pump and Jockey pump and 341210.00 No
Diesel Engine pump.
Fabrication, Supplying, Installation, Testing
& Commissioning of electrical control panel
of cubical construction, floor mounted type,
fabricated out of 2mm thick CRCA sheet,
compartmentalised with hinged lockable
doors, dust and vermin proof, powder
coated of approved shade after 7 tank
treatement process, cable alley, inter-
connection, having switchgears and
accessories mounting and internal wiring,
earth terminals, numbering etc. complete
in all respect, suitable for main fire pump,
pressurisation pump complete as per
CPWD specification with following in
coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac Supply
with enclosure protection class IP 42 as
required :suitable for operation on 415 V,
phase, 50 HZ, AC supply with enclosure
protection class IP 42 as required.
A. Incoming Feeder:-
(i) 1 No of 200 A,35KA, 415V,FP MCCB with
Thermalmagnetic Based Releases having
O/C, S/C ,E/F protection, Digital ELR
96x96mm with CBCT, FP Spreader
Terminals 1 set= 8 Pcs, Extended Rotory
Handle for MCCB, 240V AC Shunt Trip coil
(ii) LED type indicating Lamp with suitable
rating 2 Amp SP MCB:- 1 Set (each set
comprise of R,Y,B)
(iii) Digital type 3 phase Multi function
Meter with suitable rating of MCB & 3 Nos.
of single core epoxy resin cast type CTs of
200/5 Amps, 10 VA, CL 1.0 ratings -1 Set.
415 V, 200 Amps, FP Aluminium Busbars
with Heat shrinkable color code insulation
OUTGOINGS:-( All outgoing feeders for
pumps should have digital Ammeter with
selector switches and LED type ON,OFF,Trip
indicating Lamps )
1 sets - 125 A, 25kA TPN MCCB, Ics=100%
Icu, with fully automatic Star/Delta starter
suitable for 50 HP pump with overload
protection, current sensing type single
phase preventor complete with all
acceessories and internal wiring required
for automatic operation,selector switch for
local/remote, auto/manual/OFF operation.
1 sets - 125 A, 25kA TPN MCCB, Ics=100%
Icu, with fully automatic Star/Delta starter
suitable for 50 HP pump with overload
protection, current sensing type single
phase preventor complete with all
acceessories and internal wiring required
for automatic operation,selector switch for
local/remote, auto/manual/OFF operation.
1 no.63A,16KA MCCB Ics=100%,Extended
Rotry handle with TM release having O/C &
S/C protection with 10 HP fully automatic
star/ delta starter , current sensing type,
Single Phase Preventer, ON/OFF Push
Button & LED type Indicating lamps
complete with all accessories and internal
wiring required for automatic operation,
selector switch, for local/remote,
auto/manual operation
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch & 3 attempt
starting device, timers and relays as
required, push buttons, start/stop in
ii) LED type Indication lamp for High/Low
Lub. Oil pressure, High Water Temp and
Engine ON indication.
iii) Battery charger suitable for 12 V/24 V
DC with boost and trickle selector switch, 0-
30 V DC volt meter, 0-20 Amp DC
iv) All standard relays, accessories for
automatic operation of diesel engine,
wiring with 1.5 sq mm PVC insulated copper
wire between various sensors and system
controller / starter, suitable size cable for
battery charging etc. as required.
System Controller
Designing, Supply, Installation, Testing and
Commissioning of system controller to
control operation of Main Electric Fire
Pump, Diesel Pump, Pressurisation Pump,
Terrace Pump in sequence as per
specification consisting of relays, timers,
sensors, annunciation window for fault
indication, control wiring complete as
3 NOS. 25A DP MCB " C " Curve
FIRE CONTROL PANEL FOR Main Hydrant
2.2 1.00 pump and Jockey pump and Diesel Engine 258883.00 No
Fabrication, Supplying, Installation, Testing
& Commissioning of electrical control panel
of cubical construction, floor mounted type,
fabricated out of 2mm thick CRCA sheet,
compartmentalised with hinged lockable
doors, dust and vermin proof, powder
coated of approved shade after 7 tank
treatement process, cable alley, inter-
connection, having switchgears and
accessories mounting and internal wiring,
earth terminals, numbering etc. complete
in all respect, suitable for main fire pump,
pressurisation pump complete as per
CPWD specification with following in
coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac Supply
with enclosure protection class IP 42 as
required :suitable for operation on 415 V,
phase, 50 HZ, AC supply with enclosure
protection class IP 42 as required.
A. Incoming Feeder:-
(i) 1 No of 125 A,25KA, 415V,FP MCCB with
Thermalmagnetic Based Releases having
O/C, S/C ,E/F protection, Digital ELR
96x96mm with CBCT, FP Spreader
Terminals 1 set= 8 Pcs, Extended Rotory
Handle for MCCB, 240V AC Shunt Trip coil
(ii) LED type indicating Lamp with suitable
rating 2 Amp SP MCB:- 1 Set (each set
comprise of R,Y,B)
(iii) Digital type 3 phase Multi function
Meter with suitable rating of MCB & 3 Nos.
of single core epoxy resin cast type CTs of
125/5 Amps, 10 VA, CL 1.0 ratings -1 Set.
415 V, 125 Amps, FP Aluminium Busbars
with Heat shrinkable color code insulation
OUTGOINGS:-( All outgoing feeders for
pumps should have digital Ammeter with
selector switches and LED type ON,OFF,Trip
indicating Lamps )
1 sets - 80 A, 25kA TPN MCCB, Ics=100%
Icu, with fully automatic Star/Delta starter
suitable for 60 HP pump with overload
protection, current sensing type single
phase preventor complete with all
acceessories and internal wiring required
for automatic operation,selector switch for
local/remote, auto/manual/OFF operation.
1 no.40A,10KA MCB Ics=100%,Extended
Rotry handle with TM release having O/C &
S/C protection with 10 HP fully automatic
star/ delta starter , current sensing type,
Single Phase Preventer, ON/OFF Push
Button & LED type Indicating lamps
complete with all accessories and internal
wiring required for automatic operation,
selector switch, for local/remote,
auto/manual operation
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch & 3 attempt
starting device, timers and relays as
required, push buttons, start/stop in
ii) LED type Indication lamp for High/Low
Lub. Oil pressure, High Water Temp and
Engine ON indication.
iii) Battery charger suitable for 12 V/24 V
DC with boost and trickle selector switch, 0-
30 V DC volt meter, 0-20 Amp DC
iv) All standard relays, accessories for
automatic operation of diesel engine,
wiring with 1.5 sq mm PVC insulated copper
wire between various sensors and system
controller / starter, suitable size cable for
battery charging etc. as required.
System Controller
Designing, Supply, Installation, Testing and
Commissioning of system controller to
control operation of Main Electric Fire
Pump, Diesel Pump, Pressurisation Pump,
Terrace Pump in sequence as per
specification consisting of relays, timers,
sensors, annunciation window for fault
indication, control wiring complete as
3 NOS. 25A DP MCB " C " Curve
S.I.T.C of Pressure gauges - Glycerine Filled
SS 304 with all accessories like needle-
valve, Syphon etc. Range 0-16 Kg/cm2 , Dial
- 150 mm, Size - 1/2 " BSP
Supply,Installation, testing &
commissioning of Diaphragm Type Pressure
switch, housing shall be die cast aluminum
with SS 316 moving parts like pressure
element and socket. the range 0 to
Supply ,Fabrication,Erection and Painting
of Steel Structure with one coat of Red
5 300.00 Oxide and Two Coat of Synthetic Enamel 120.00 Kgs
Paint for Support complete in all respect
with the anchoring etc.
Supply ,Installation, testing &
commissioning air vessel of Min 450 mm
dia. (8 mm thick) 1.5 meter long made from
M.S with 25mm-dia spring-loaded air
release valve, safety valve and gunmetal full
way valve. The Vessel shall be Painted with
one Coat of Red Oxide and Two Coats of
Synthetic Enamel Paint . The Vessel shall be
Fixed and Mounted by Vendor including
anchoring etc. Two Numbers Extra Air vents
with Isolation Ball valves to be Provided in
the Piping at the Highest Point.
Providing, laying, testing & commissioning
of 'C' class heavy duty MS Pipe conforming
to IS 1239 i/c fittings like elbows, tees,
flanges, tapers, nuts bolts, gaskets etc., in
ground including excavation and providing
cement concrete blocks as support,
anticorrosive treatment with
coaltar/asphalt tape as per IS
refilling the trench etc. of following sizes
complete as required .( For HYDRANT )
Providing, laying, testing & commissioning
of 'C' class heavy duty MS pipe conforming
to IS 3589/IS 1239 including Welding,
fittings like elbows, tees, flanges,tapers,
8 nuts bolts, gaskets etc. and fixing the pipe
on the wall/ceiling with suitable
clamp/support frame and painting with two
or more coats of synthetic enamel paint of
required shade complete as required :
8.1 10.00 200 NB (6 mm Thickness) 3500.00 Mtrs
Supply, Installation, testing &
commissioning cast iron double flanged
,including mating Flanges,type IS marked
9 sluice valve of the following size complete
with bolts, nuts, washers and inserted
rubber gaskets as required: As defined in
Technical Specification
Supply, Installation, testing &
commissioning ISI marked C.I (SS304 Disc)
Butterfly valve of P.N 1.6 Rating as per
10 Technical Specification ,the mating flange
and additional Pair of Flanges shall be
considered to Fix the distance piece with
Butterfly Valve.
10.1 3.00 200 NB (Gear Operated) 24000.00 Nos.
Supply, Installation, testing &
commissioning of single headed SS 304, ISI
mark oblique pattern hydrant valve with
11 2.00 80mm diameter flanged inlet & 63 mm 7500.00 Nos.
instantaneous type female out let with pvc
cap- chain spring release type lug and
accessories as per IS: 5290- 1983 (Type ‘A’)
Supply,Installation, testing &
commissioning first aid hose reel, full
swinging with 30 mtr long, 25mm dia
rubber lined, with ss 304 shut off nozzle of
6 mm dia. confirming to IS: 884,
including 25mm dia pipe connection from
riser to hose reel with complete
Supply & Installation of outdoor type hose
cabinet fabricated from 16g M.S sheet with
full front glass door and locking
arrangement suitable to accommodate ,
no of 15 meter long hose pipe and one
13 2.00 branch pipe. It should be painted with one 4500.00 Nos.
coat of primer and two coat of synthetic
enamel paint. Complete in all respect with
Fixing Supports of Steel Members Duly
Painted in same color and Clamping
Supply & Installation of outdoor type hose
cabinet fabricated from weather proof FRP
sheet with full front glass door and locking
arrangement suitable to accommodate ,
no of 15 meter long hose pipe and one
14 2.00 branch pipe. It should be painted with one 5500.00 Nos.
coat of primer and two coat of synthetic
enamel paint. Complete in all respect with
Fixing Supports of Steel Members Duly
Painted in same color and Clamping
Providing ISI marked RRL (IS : 636, type‐A)
fire hose pipe 15 meter long and 63 mm dia
with ISI marked (IS : 903) Stainless steel
male and female coupling bound and
rivetted to hose pipes with copper rivets
and copper wire complete as required.
Providing Stainless steel ISI marked 63 mm.
dia. male Instantaneous pattern short
branch pipes with 20 mm dia. Nozzle as per
IS : 903, suitable for 10 Kg/sqcm operating
pressure and suitable for interconnections
to hose pipe coupling as required.
Supplying and fixing of fire brigade
connection of cast iron body with gun metal
male instantaneous inlet couplings
complete with cap and chain as reqd. for
suitable dia MS pipe connection conforming
17.1 1.00 2 way - 100 mm dia M.S. Pipe 6500.00 Nos.
17.2 1.00 4 way - 150 mm dia M.S. Pipe 12500.00 Nos.
Supply,installation ,testing &
commissioning of Ball Valves 3 Piece Design
18 ,Body - Forged or Cast Carbon Steel ,Trim
and Ball SS410 , Seat SS410 Threaded End
as per Technical Specification
Providing and fixing Orifice plates, S.S.
12 mm thick, bore and construction as per
TAC's Sprinklers manual / IS:15105, for all
horizontal tapping for hydrant system for
reduction of pressure in the range of 3.5-
7.00 Kg/cm2 including one pair of Slip-on-
Flange, nuts, bolts, gasket and complete as
Supply,Installation, testing &
commissioning ISI marked C.I double
flanged dual plate type Non- Return valves
(SS 304 disc) Complete with Mating
Flanges,Nuts,Bolts and Gaskets, As per
Technical Specification
Supply, installation, testing and
commissioning of "Y" type Flanged
Strainer with SS 410 mesh of at least
21 times pipe area with flanged inlet and
outlet complete Complete with Mating
Flanges,Nuts,Bolts and Gaskets, As per
Technical Specification.
Wrapping and Coating of Under Ground
22 1.00 Piping with 4 MM Pypkot anti Corosive tape 550.00 SQMTR
, As per Technical Specification
Supplying and erecting Flexible PVC
insulated multistrand multicore 1.1 kv
grade ISI marked copper wires of following
size to be erected as directed.
10.00 f) 1.50 Sq.mm 4 core round PVC sheathed 67.00 Mtrs
SITC of fire pump start stop push buttons in
SITC of 2 Zone standalone Fire Alarm
control Panel, 16X2 Character LCD
Display, provision for zone wise contact and
25 1.00 sounder. Panel does not have provision to 7500.00 Nos.
connect Repeater Panel. Make: Ravel
Approval: CE Mark. (Including Five year
free maintenance with guarantee)
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or ceiling
26 erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in
approved manner as directed
Supply, Installation, Testing and
Commissioning of Single action Manual Pull
Station.Shock and Vibration Resistant, pull
Down Lever Remains Down Until Reset.
27 1.00 Shall be Polarity Insensitive (with all 350.00 Nos.
mounting accessories , complete with
Junction Box for mooting on Surface, Cable
lugs at Ends, cable compression glands,
cable tags and ferruling.
Supply, Installation, Testing and
Commissioning of Conventional Sounder
cum strobe having tone settings with range
of 95dbA and field selectable 15/30/75/110
28 1.00 candelas.(with all mounting accessories , 950.00 No
complete with Junction Box for mooting on
surface, cable lugs at ends, cable
compression glands, cable tags and
29 2.00 S.I.T.C of Conventional Smoke detectors 1350.00 Nos.
30 2.00 S.I.T.C of of Conventional Heat detectors 1550.00 Nos.
S.I.T.C of of Fire retadent Paint 2 Hour
Sprinkler K-5.6, 57 Deg.C, Standard
Response, Standard Coverage. Maximum
Working Pressure: 175 psi (12 bar),Thread
size: 1/2” (15 mm) NPT,Sprinkler Body:
Brass Casting,Body Cap: Stainless
Steel,Deflector: Copper,Deflector Pins:
Stainless Steel,Compression Screw:
32 Brass,Fusible Link Assembly: Beryllium
Nickel and Eutectic Solder,Fusible Link
Levers: Stainless Steel,Lever Bar: Copper
Alloy,Belleville Spring Sealing Assembly:
Nickel Alloy, coated on both sides with
Teflon Tape and Escutcheon Plate: Brass &
Sprinkler Finish- Chrome Finished.Sprinkler
Heads Shall be UL Listed Approved
32.1 1.00 Upright Type Sprinkler Heads 450.00 Nos.
32.2 70.00 Pendent Type Sprinkler Heads 450.00 Nos.
32.3 1.00 Side Wall Sprinkler 550.00 Nos.
32.4 1.00 Side Wall Extended Throw Sprinkler 650.00 Nos.
S.I.T.C of Air release valve with Body Brass,
33 Internal Parts & Float HDPE complete with
all accessories.
1.00 25MM Size 2500.00 Nos.
S.I.T.C of Flexible Dropper Unit - Complete
with Braided SS Hose, Support Bracket,
Inlet/Outlet Connectors and Square Bar -
Mild Steel, zinc plated, Nipples, Reducer
and other accessories. Size - 1 X 1/2" or
3/4" with 750 / 1000mm / 1500mm length
34.1 60.00 750mm length 1000.00 Nos.
34.2 1.00 1000mm length 1400.00 Nos.
34.3 1.00 1500mm length 1800.00 Nos.
S.I.T.C of Inspector's Test Connection with
Orifice and Isolation Gun Metal Ball valves
with screwed ends lever operated ASTM A
35 1.00 105,TRIM 13% Cr. 800# Including 25NB dia. 7500.00 Nos.
pipes, fittings, Open Sprinkler, Coupling,
pressure gauge, Sight glass & Wall mounted
MS Box for better operations.
Supply Installation testing & Commissioning
of Flow switch for the maximum working
temperature of 250°C with flameproof
protection. Sensing Element of SS 316. The
Flow switch shall hooked up with the Fire
Alarm system the Provision is the part of
Vendor's Scope. The Flow Switch shall be
UL Listed/FM Approved.
Supply, Installation, testing and
Commissioning of Sprinkler Alarm Valve
with Trim and Water Motor Gong Bell,
Working press 175 PSI, Hydraulic Testing
Pressure 350 PSI, Body High Tensile C.I.
Seat Ring & Clapper - Bronze, Cover Bolts
Steel,Clapper Disc -EPDM & other
accessories as UL Listed/FM approved
Specification. The Mechanical Gong
Diameter 205 MM, UL Listed/FM Approved.
S.I.T.C of 2 core x 1 sq. mm flexible wire
38 10.00 with pvc conduit & accessories for alarm 70.00 Mtrs
Centrifugal,Electrical Operated,Vertical,
Mono Block, Motor above & Pump
Below,Dewatering Pump for Pump Room
Complete with Electrical Panel,Level control
& Cable etc. For auto operation, Capacity -
270 LPM, Head -15 Meters, The Pump shall
be suitable to Pump Dust,Dirt and
39 4.00 Suspended solids of same nature, Complete 45000.00 SET
with Aluminium Body,SS 304 Impeller,SS
Fasteners,SS 410 Shaft. The Power supply
shall be 3 Phase,415 Volt and the Cable in
between from Panel to Pump shall be
vendor's scope. Refer the Secifications &
Approved makes of General Specification of
Electrical Tender.
Obtaining approval on entire Fire
Protection and detection system from Local
Fire Brigade authority / Insurance co. or
from any other statutory body with all
respect the Statutory Approval Charges
40 1.00 paid to the Statutory authorities will be re 100000.00 Lot
imburshed by HAL on reciept of written
approval from Statutory authority and
against submission of Payment reciepts
from Statutory Authorities.(Legal Fess shall
be paid Be Extra.)
Providing, fixing, testing and commissioning
of below Auto Glow Signages.
41.2 2.00 Fire Equipment: 4" X 12" 514.97 Nos.
In case of Fire, do not use lift, use staircase:
41.4 2.00 Fire Lift 4"X12" 514.97 Nos.
41.5 2.00 Fire Extinguishers 8"x 4" 480.00 Nos.
41.6 2.00 Floor Sign": 4" X 12" 514.97 Nos.
41.7 2.00 Fire Hydrant 4” X 12” 514.97 Nos.
41.8 2.00 Fire Hose Reel.4” X 12” 514.97 Nos.
41.9 2.00 DCP Extinguisher 8"x 4" 480.00 Nos.
41.1 2.00 CO2 Extinguisher 8"X 4" 480.00 Nos.
SUB-TOTAL OF PART-A FIRE HYDRANT
PART-B FIRE EXTINGUISERS AND
LIGHTNING ARRESTOR
Supply & Installation of 6 Kg ABC
Extinguisher of stored pressure type with
mono ammonium phosphate discharge
tube and pressure gauge complete.
Tenderer shall give 3 years guarantee on
cylinder with gas and powder. Quantity &
Quality shall be as Latest Code -15683/BIS
Supply & Installation of CO2 Fire
Extinguisher of 4.5 Kg capacity fitted with
screw down type high pressure control
valve with 1.0 M long rubber braided
discharge hose with horn. The Body shall be
CCE approved with IS:2878 marking and
supplied with initial charge of CO2 gas. The
valve shall conform to IS:3224.Quantity &
Quality shall be as Latest Code -15683/BIS
Supply & Installation of 2 Kg ABC
Extinguisher of stored pressure type with
mono ammonium phosphate discharge
tube and pressure gauge complete.
Tenderer shall give 5 years guarantee on
cylinder with gas and powder.Quantity &
Quality shall be as Latest Code -15683/BIS
SITC of Vertical Air Termination Solid
aluminium with Base- 10 mm dia and
mm long. Air Termination Base tested for
conditioning, Ageing Test & Lightning
45 2.00 impulse current withstand test: 100 kA of 9323.00 No
10/350µs waveform in an accredited Third
party laboratory as per 6.3 & 6.4 of IEC
62561-1 2017 protocol with MAST 34mm
dia 3000 mm long- Cold Galvanized
SITC of 8 mm dia solid Aluminium
Conductor for roof top mesh grid and
tested as per IEC 62561- 2 conducted in the
46 2.00 Govt. accredited thirty party laboratory to 297.00 Mtr
meet the requirement of IS/IEC 62305 with
Required Accessories - Aluminium Holding
clamp at every 1 mtr distance,
Aluminium/SS cross splicer at every
crossing of Alu. conductor, Expansion piece
with connectors at every 20 mtr distance,
Aluminium straight Splicer to connect
conductors. All Accessories should be
tested as per IEC 62561-1 2018 Cl. 6.3 for
conditioning & Ageing Test & 6.4 for
Lightning impulse current withstand test:
100 kA of 10/350µs waveform(Ageing &
Electrical test ) conducted in a sequence
manner & tested in the Govt. accredited
Third party laboratory to meet the
requirements of IS/IEC
SITC of Galvanized Steel Flat 25x6 mm
thickness from earth electrode directly in
ground as required. Zinc coating: 500 g/m
47 2.00 square (Approx:70 micron coating) tested 153.00 Mtr
and used exclusively for lightning
protection earthing system and ring
equipotential bonding.
SITC of 14.2 mm dia 3 mtr long Earth
electrode of High tensile steel electrode
with 250 micron copper bonding & 1 bag of
Carbon fill Based environment friendly
backfill tested as per IEC 62561-7 in NABL
48 2.00 accredited Laboratory and suitable stainless 5933.00 No
Steel double sided clamp. Eco Friendly rust
proof heavy duty weather proof
Polyethylene Earth Pit Chamber with
following dimensions :254 mm dia (top),
330 mm dia (bottom) & 260 mm (height).
SUB-TOTAL OF PART-B FIRE EXTINGUISERS
AND LIGHTNING ARRESTOR
PART-C ELECTRICAL
Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having normal current rating 125A. with
49 Fixed thermal & magnetic release suitable
to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing.
3.00 ICS=100% of ICU only 8773.60 Nos.
Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
Microprocessr release having Overcurrent
Range 40-160A suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
1.00 ICS=100% of ICU only 23288.45 Nos.
Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. and above
at 415 V . having normal current rating
250A. with Microprocessr release having
overcurrent range 100-250A suitable to
work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
2.00 ICS=100% of ICU only 30071.55 Nos.
Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 50 KA and above
at 415 V having Normal current rating
400A. with Microprocessor release having
overcurrent range 100-400A suitable to
work on A.C.supply 50 c/s. With all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1.00 ICS=100% of ICU only 36219.55 Nos.
Providing and erecting Approved make Four
pole moulded case circuit breaker having
breaking capacity ICU of 50 K.A. and above
at 415 V having normal current rating up to
630A. with Microprocessor release suitable
to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing . Overload release range
158-630A. confirms to IS/IEC 60947-2.
1.00 ICS=100% of ICU only 40447.75 Nos.
Providing and erecting Approved make
Earth fault Relay suitable to mount with
inter connection suitable to following size
of moulded case circuit breaker having CT
ratio & MCCB rating as following along with
shunt trip 220V AC. with all internal
connections & complete erected in existing
FABRICATION AND BUSBARS CHAMBER
Providing and erecting busbar chamber
confirming to IS-375 fabricated from
G.M.S. sheet, dust & vermin proof having
hinged door with rubber gasket and
necessary busbar supports with COPPER
busbar having current density not more
than 1.6 Amp. / sq.mm (Rated current /
cross section area) duly wrapped with
colour insulation tape for phase sequence,
three phase & neutral each suitable for
following current capacity with necessary
painting mounted on wall or pedestal frame
of required size with necessary
55.1 1.00 (B) Suitable for 200 Amp. Capacity 5675.00 Rn.Mtr
55.2 1.00 (C) Suitable for 300 Amp. capacity 8455.00 Rn.Mtr
55.3 1.00 (D) Suitable for 400 Amp. capacity 10239.00 Rn.Mtr
Supplying and erecting triple pole & neutral
440V / 500V panel mounting Copper
Busbars with four equal Nos. of electrolyte
bus having current density not more than
1.6 Amp. / sq.mm (Rated current / cross
section area) duly wrapped with colour
insulating tape for phase sequence of
following current carrying capacity, erected
with necessary bus bar supports /insulators,
main cable socket to each bar, erected in
existing cubical panel with necessary
1.50 (E) Suitable for 630 Amp. capacity 10455.00 Rnmtr
Providing & erecting weather proof, dust &
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per approval
from engineer incharge made from 14 SWG
thick CRC M.S. sheet for outer body &
doors, 16 SWG thick CRC M.S.sheet for
internal partitions with necessary
accesories , supporting angles/ flats channel
including cutting, bending, drilling, welding,
riveting with internal partitions & cable
alley as per requirements & instruction of
engineer-in-charge with erection of
supplied switch gears, BUSBARS, suitable
size of inter connecting PVC copper wire /
copper-aluminium strips, rubber grommets,
rib, bakelite control fuses/MCB for
measuring instruments, earth bus & earth
bolts, foundation flange - bolts-base Plates,
sufficient nos. of hinged doors, handles
with locking arrangement and rubber
gasket,heavy duty end terminal
connection,danger notice board,necessary
ventilation,earthing strip complete. The
Panel shall be painted with epoxy powder
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding
base beams) The panel shall be supplied
with following approved manufacturers
with following size.
(B) The standard companies switch gear
shall be used and only manufacturers at
CPRI approved factory
0.50 (i) with 350mm depth 14755.00 Sqmtr
CABLE AND TERMINATIONS
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Aluminium
58 conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe of following size of cables
(C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm
(D) 3 1/2 core 70 Sq. mm ( 35 Sq. mm 1/2
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2
(G) 3 1/2 core 150 Sq. mm ( 70 Sq. mm
(H) 3 1/2 core 185 Sq. mm ( 95 Sq. mm
Providing and, fixing heavy duty flange type
brass double compression type cable gland
with rubber ring for PVC insulated
armoured cable complete with out going
tails, insulating tape etc for following size of
Solder less crimping type Aluminium lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
providing and erecting Mains with ISI
marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor with
heat resistant PVC insulated conforms to IS
61 694, IEC - 227 erected in existing pipe of
following size (Specifically for control panel,
relays, power switchgears, motor starters &
control wiring) with required size of copper
lugs, nuts and bolts if required.
61.1 5.00 (h) One wire 25.00 sq. mm 234.00 Mtr
61.2 5.00 (i) One wire 35.00 sq. mm 298.00 Mtr
61.3 20.00 (j) One wire 50.00 sq. mm 466.00 Mtr
61.4 30.00 (k) One wire 70.00 sq. mm 663.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
Providing and, fixing heavy duty flange type
brass cable gland with rubber ring for PVC
63 insulated armoured cable complete with
out going tails, insulating tape etc for
following size of cables.
63.1 4.00 (B) 2 to 4 core 6 Sq. mm 38.00 Nos.
63.2 1.00 (C) 2 to 4 core 10 Sq. mm 38.00 Nos.
63.3 4.00 (D) 2 to 4 core 16 Sq. mm 47.00 Nos.
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
SUB-TOTAL OF PART-C ELECTRICAL
Signature of contractor Additional City Engineer ( SOUTH ZONE)
Seal Ahmedabad Municipal Corporation
AHMEDABAD MUNICIPAL CORPORATION
ENGINEERING DEPARTMENT- SOUTH ZONE
NAME OF WORK:- Annual Rate Contract for Supply, installation, Testing and commissioning of New
Fire Fighting System in Various A.M.C. Buildings in Vatva Ward, South Zone, Ahmedabad.
FINANCIAL BID ( To Be Submitted Online Only )
Sr. No. Description Amount
1 Amount For SITC of Fire Fighting Work Rs.
I/We am/are willing to carry out work at ______ % Above / Below (should be written in figures
and words) The Estimated Cost Mentioned Above.
Estimated cost put to tender: Rs.53,72,100.59 Estimated cost put to tender: Rs.
Add_____% above : Rs ___________ Deduct_____% below : Rs __________
In words : Rupees _______________________ In words : Rupees_____________________
Signature of contractor Additional City Engineer (SOUTH ZONE)
Seal Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
T.No.188 Final Price Bid Vol.-II.pdf
T.No.188 Vol-1 part A Tender Document VATVA WARD SOUTH ZONE (1).pdf
T.No.188 _Vol-1 part-B Fire Fighting Specification.pdf
T.No.188 _Vol-1 part-C Electrical Specification.pdf
Download all tender documents and submit your bid