Bill of Quantities
Unit Rate Amount
I. No. Qty Items Per
FIRE FIGHTING SYSTEM
Design,Drawing, Supply,installing,testing and
commissioning of FIRE HYDRANT WORKS
1.1 1 Supplying, Installation, Testing and Commissioning of 143626.00 SET
electric driven main Hydrant fire pump and Sprinkler
pump suitable for automatic operation and consisting of
following: complete in all respect as required.
a) Horizontal type, single stage, centrifugal, end suction
pump of cast iron body & bronze impeller with stainless
steel shaft, mechanical seal to ensure a minimum pressure
of 3.5 kg/sq. cm. at highest and farthest outlet at specified
flow of 1620 lpm at 56 Mtr. head conforming to IS
1520.with suitable size of footvalve confirming to IS
Pressure rating PN2 , preventing entry of foreign body to
pump through suction pipe, perfectly flat seating surfaces
for good sealing.
b) Suitable HP Squirrel cage induction motor, TEFC,
suitable for opertion on 415 volts, 3 phase 50 Hz. AC with
IP 55 class protection for enclosure, horizontal foot mounted
type with Class - 'F' insulation, conforming to IS-325.
c) M.S. fabricated Common base plate, coupling, coupling
guard, foundation bolts etc. as required.
d) Suitable cement concrete foundation duly plastered with
anti vibration pads.
The pump shall be capable of giving not less than 150%
discharge at ahead not less than 65% of the rated head.
1.2 1 Supplying, Installation, Testing and Commissioning of 61717.00 SET
electric driven pressurisation pump suitable for
automatic operation and consisting of following: complete in
all respect as required
b) Suitable HP Squirrel cage induction motor TEFC type
suitable for operation on 415 volts, 3 phase 50 Hz. AC with
IP 55 Class of protection for enclosure, horizontal foot
mounted type with Class F' insulation, conforming to IS :
c) M.S. fabricated Common base plate, flexible rubber
coupling, coupling guard, foundtion bolts etc. as required.
a) Horizontal type, single stage, centrifugal, end suction
pump of cast iron body and bronze impeller with stainless
steel shaft, mechanical seal at specified flow of
180 lpm at 70 m. head conforming to IS:
1.3 Supplying, Installation, Testing and Commissioning of
diesel engine driven main fire pump suitable for
automatic operation and consisting of following: complete in
all respect as required
b) Suitable HP, 1500 /1800 RPM water cooled with
radiator, diesel engine conforming to relevant BS & IS
standard complete with auto starting mechanism, 12/24
volts electric starting equipment, 180 AH lead acid battery
with battery stand, exhaust pipe extended upto 6 m.
outside pump house duly insulated with 50 mm thick glass
wool with 1.0 mm. thick aluminium sheet cladding,
residential silencer, instruments and protection as per
specification, stop solenoid for auto stop in the event of fault
with audio indications, painted with post office red colour
etc. as required.
c) One 200 Ltr capacity day oil storage tank fabricated from
3 mm thick M.S. plates. Tank shall be provided with inlet,
outlet, overflow, air vent, drain connections, filling
connection & level indicator. Tank shall be mounted on a
suitable steel structure (Painted with 2 coats of red oxide
paint). Tank shall be provided with two or more coats of
synthetic enamel paint outside over two coats of red oxide
d) M.S. Fabricated Common base plate, coupling, coupling
guard, foundation bolts etc. as required.
e) Suitable cement concrete foundation duly plastered with
anti vibration pads.
a) Horizontal type, single stage, centrifugal, end suction
pump of cast iron body and bronze impeller with stainless
steel shaft, mechanical seal to ensure a minimum pressure
of 3.5 kg/sq. cm at highest and farthest outlet at specified
1 1620 lpm at 70 mtr. head conforming to IS 1520. 482265.00 SET
2 1 FIRE CONTROL PANEL FOR Main Hydrant pump and 258883.00 No
Jockey pump and Diesel Engine pump.
Fabrication, Supplying, Installation, Testing &
Commissioning of electrical control panel of cubical
construction, floor mounted type, fabricated out of 2mm
thick CRCA sheet, compartmentalised with hinged lockable
doors, dust and vermin proof, powder coated of approved
shade after 7 tank treatement process, cable alley, inter-
connection, having switchgears and accessories mounting
and internal wiring, earth terminals, numbering etc.
complete in all respect, suitable for main fire pump,
pressurisation pump complete as per CPWD specification
with following in coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac Supply with enclosure
protection class IP 42 as required :suitable for operation on
415 V, 3 phase, 50 HZ, AC supply with enclosure protection
class IP 42 as required.
A. Incoming Feeder:-
(i) 1 No of 125 A,25KA, 415V,FP MCCB with
Thermalmagnetic Based Releases having O/C, S/C ,E/F
protection, Digital ELR 96x96mm with CBCT, FP Spreader
Terminals 1 set= 8 Pcs, Extended Rotory Handle for MCCB,
240V AC Shunt Trip coil for MCCB.
(ii) LED type indicating Lamp with suitable rating 2 Amp SP
MCB:- 1 Set (each set comprise of R,Y,B)
(iii) Digital type 3 phase Multi function Meter with suitable
rating of MCB & 3 Nos. of single core epoxy resin cast type
CTs of 125/5 Amps, 10 VA, CL 1.0 ratings -1 Set.
415 V, 125 Amps, FP Aluminium Busbars with Heat
shrinkable color code insulation sleeves.
OUTGOINGS:-( All outgoing feeders for pumps should have
digital Ammeter with selector switches and LED type
ON,OFF,Trip indicating Lamps )
1 sets - 80 A, 25kA TPN MCCB, Ics=100% Icu, with fully
automatic Star/Delta starter suitable for 60 HP pump with
overload protection, current sensing type single phase
preventor complete with all acceessories and internal wiring
required for automatic operation,selector switch for
local/remote, auto/manual/OFF operation.
1 no.40A,10KA MCB Ics=100%,Extended Rotry handle
with TM release having O/C & S/C protection with 10 HP
fully automatic star/ delta starter , current sensing type,
Single Phase Preventer, ON/OFF Push Button & LED type
Indicating lamps complete with all accessories and internal
wiring required for automatic operation, selector switch, for
local/remote, auto/manual operation
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch & 3 attempt starting device,
timers and relays as required, push buttons, start/stop in
ii) LED type Indication lamp for High/Low Lub. Oil pressure,
High Water Temp and Engine ON indication.
iii) Battery charger suitable for 12 V/24 V DC with boost and
trickle selector switch, 0-30 V DC volt meter, 0-20 Amp DC
iv) All standard relays, accessories for automatic operation
of diesel engine, wiring with 1.5 sq mm PVC insulated
copper wire between various sensors and system controller
/ starter, suitable size cable for battery charging etc. as
System Controller
Designing, Supply, Installation, Testing and Commissioning
of system controller to control operation of Main Electric Fire
Pump, Diesel Pump, Pressurisation Pump, Terrace Pump in
sequence as per specification consisting of relays, timers,
sensors, annunciation window for fault indication, control
wiring complete as specification.
3 NOS. 25A DP MCB " C " Curve
3.1 Providing and erecting Approved make Four pole moulded
case circuit breaker having breaking capacity ICU of 35 KA.
at 415 V. having normal current rating 125A. with Fixed
thermal & magnetic release suitable to work on A.C.supply
50 c/s. with all internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S. housing.
1 ICS=100% of ICU only 8773.60 No
3.2 providing and erecting Approved make Earth fault Relay
suitable to mount with inter connection suitable to following
size of moulded case circuit breaker having CT ratio &
MCCB rating as following along with shunt trip 220V AC.
with all internal connections & complete erected in existing
4 providing and erecting Mains with ISI marked, 1.5KV grade
electrolyte multi stranded, annealed copper conductor with
heat resistant PVC insulated conforms to IS 694, IEC -
erected in existing pipe of following size (Specifically for
control panel, relays, power switchgears, motor starters &
control wiring) with required size of copper lugs, nuts and
bolts if required.
20 (h) One wire 25.00 sq. mm 234.00 Mtr
5 1 Supplying, Installation, Testing and commissioning Sewage 19676.50 No
water submersible pumping sets of CI casing & impeller,
SS shaft, including with inbuilt water level sensors for
operating the pumps automatically and all accessories
suitable for operation on 220 V-240 V, single phase, 50 Hz.
AC supply etc. as reqd.
> 10 mm solid handling capacity,Minimum Capacity -
50 LPM,Minimum Head > 13.5 Mtr
Signature of contractor Additional City Engineer ( NORTH ZONE)
Seal Ahmedabad Municipal Corporation
AHMEDABAD MUNICIPAL CORPORATION
ENGINEERING DEPARTMENT- NORTH ZONE
NAME OF WORK:- SITC OF FIRE PUMP AND RELATED WORK AT SCHOOL BUILDING AT F.P. NO:
T.P.NO: 121 ( NARODA-HANSPURA-KATHWADA) IN NARODA WARD, NORTH ZONE, AHMEDABAD.
FINANCIAL BID ( To Be Submitted Online Only )
Sr. No. Description Amount
1 Amount For SITC of Fire Fighting Work Rs.
I/We am/are willing to carry out work at ______ % Above / Below (should be written in figures
and words) The Estimated Cost Mentioned Above.
Estimated cost put to tender: Rs.9,84,555.10 Estimated cost put to tender: Rs.
Add_____% above : Rs ___________ Deduct_____% below : Rs __________
In words : Rupees _______________________ In words : Rupees_____________________
Signature of contractor Additional City Engineer (NORTH ZONE)
Seal Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
T No 1 3 2026 27 Vol 1 part A Tender Document.pdf
T No 1 3 2026 27 Vol 1 part C Electrical Specification.pdf
T No 1 3 2026 27 Vol 1 part B Fire Fighting Specification.pdf
T No 1 3 2026 27 Final Price Bid Vol II.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .