Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 CrAccepted-AOC 6TH FLOOR CG HOUSE DR ANNIE BESANT ROAD WORLI MUMBAI MAHARASHTRA 400030 | MUMBAI | MAHARASHTRA | 400030 | ₹3.4 Cr | L1 | Accepted-AOC being L1 |
| 2 | L2₹4.1 Cr+₹72.7 L (21.5%)Rejected-AOC DOOR NO 48 50 PRAKASAM STREET SKCL HARMONY SQUARE T NAGAR T NAGAR CHENNAI TAMIL NADU 600017 | CHENNAI | TAMIL NADU | 600017 | ₹4.1 Cr+₹72.7 L (21.5%) | L2 | Rejected-AOC being L2 |
Tender Value
₹4.1 Cr
EMD Value
₹4.1 L
Closing Date
7 Dec 2022, 4:00 pmClosed
CE, Transmission (North), Kozhikode
The Chief Engineer, Transmission (North), KSEB Limited, Vydyuthi bhavanam, Gandhi Road, Kozhikode-11
A) 22kV Indoor VCB Panel set (with BCPU) to be installed at 220KV SS Palakkad, Kanjikode Bus Bar 1250A. B) 33kV Indoor VCB Panel set (with BCPU) to be installed at 33kV Substation Feroke, Kozhikode. Bus Bar -1250A.
2022_KSEB_530509_1
CE/TRN/E3/15/2022-23
Open Tender
Equipments
Supply and Service
150 days
Transmission (North)
Refer Bid document
6 documents required · 6 mandatory
₹29,500
Yes
₹4.1 L
Yes
CE, Transmission (North), Kozhikode
27 Apr 2023
18 Nov 2022
9 Dec 2022
19 Nov 2022
7 Dec 2022
19 Nov 2022
19 Nov 2022 - 23 Nov 2022
25 Nov 2022
Supply, Design, Documentation, Engineering, Manufacture, Inspection and testing, Packing at suppliers works, commissioning support and after sales support for 33 kV HT Indoor VCB Panel set with combinations of Incomer(Cable/ OH) Feeder Panels (2 Nos), Transformer Feeder Panels (2 Nos), Bus Coupler Panel (1 No), Bay control and protection unit (BCPU) for implementing Substation Automation System (SAS)with protection philosophy specified in the technical specification, along with supply of accessories necessary for operation and spares, to be installed at 33KV Substation, Feroke. Bus Bar Ratings are 1250A. Circuit Breakers shall be E2 M2 C1 Class as per IEC 62271-200. Feeder panels and Incomer panels shall have Capacitive voltage Indicator (CVI) and all panel BCPU’s will have PT inputs. Feeder and Incomer panels shall house one each Multifunction meter (MFM) and DLMS Compatible Energy meters. Items shall be engineered with necessary wiring and arrangements and so that each panel shall be assembled to meet the requirement as per schedule. The panel is intended for integrating with existing Substation Automation System (SAS) using BCPU in panels through HSR topology (IEC 61850 Rev 2 compliant), INCLUDING FOLLOWING SPARES :-
CB Closing &Tripping coil
CB Truck assembly complete
Supporting insulator for one pole
CB Auxiliary contact
BCPU with 3 O/C + E/F Relay with SEF, LBB features. (For Incomer)
Master trip relay with Electrical reset
LED Indicating lamp with assembly
Multi-Function meter (MFM)
CT suitable for transformer panel
PT Fuse
Loose Cable Differential relay for Remote end
Neutral CT 33 kV 300-150/1-1A (Same specification of PS class CT provided in panels, both Core as PS)
VCB Bottle
Supply, Design, Documentation, Engineering, Manufacture, Inspection and testing, Packing at suppliers works, commissioning support and after sales support for 22kV HT Indoor VCB Panel set with combinations of Incomer (Cable/ OH) Feeder Panels (2 Nos), Outgoing Feeder Panels (12 Nos), Bus Coupler Panel (1 No), Bay control and protection unit (BCPU) for implementing Substation Automation System (SAS)with protection philosophy specified in the technical specification, along with supply of accessories necessary for operation and spares, to be installed at 220 kV Substation Palakkad, Kanjikode. Bus Bar Ratings are 1600A. Circuit Breakers shall be E2 M2 C1 Class as per IEC 62271-200. Feeder panels and Incomer panels shall have Capacitive voltage Indicator (CVI) and all panel BCPU’s will have PT inputs. Feeder and Incomer panels shall house one each Multifunction meter (MFM) and DLMS Compatible Energy meters. Items shall be engineered with necessary wiring and arrangements and so that each panel shall be assembled to meet the requirement as per schedule. The panel is intended for integrating with existing Substation Automation System (SAS) using BCPU in panels through HSR topology (IEC 61850 Rev 2 compliant) INCLUDING FOLLOWING SPARES :-
CB Closing &Tripping coil
CB Truck assembly complete
Vacuum Interrupter Bottle
Supporting insulator for one pole
CB Auxiliary contact
Master trip relay with Electrical reset
LED Indicating lamp with assembly
Multi-Function meter (MFM)
CT suitable for Incomer panel
CT suitable for Outgoing feeders
PT Fuse
ABB INDIA LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
PDF • 0.56 MB
tech_eval.pdf
PDF • 0.05 MB
fin_bid_open.pdf
PDF • 0.05 MB
boq_comp_chart.xlsx
xlsx • 0.01 MB
fin_eval.pdf
PDF • 0.06 MB
aoc.pdf
PDF • 0.06 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .