| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹44.0 LAccepted-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | 1 | Accepted-AOC Lowest and reasonable bidder | |
| 2 | 2₹47.9 L+₹57,871 (1.22%)Rejected-Finance | 2 | Rejected-Finance Not the lowest bidder | |
| 3 | 3₹48.4 L+₹1.1 L (2.30%)Rejected-Finance 3 SHITALNATH FLATE 1 NR KHANPUR JAIN TEMPLE OPP BANK OF INDIA SHAHPUR AHMEDABAD GUJARAT 380001 | AHMADABAD | GUJARAT | 380001 | 3 | Rejected-Finance Not the lowest bidder | |
| 4 | 4₹56.1 L+₹8.8 L (18.6%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | 4 | Rejected-Finance Not the lowest bidder | |
| 5 | 5₹56.6 L+₹9.3 L (19.6%)Rejected-Finance | 5 | Rejected-Finance Not the lowest bidder |
| Sl No | Description | Qty | Unit | Sukhi Electricals L5 | rajengineers L2 | SURESH ELECTRICALS L1 | JAMNAGAR ELECTRIC AND MACHINERY CO L7 | M/s SK Traders L4 | Nitesh Enterprise L6 | shree chamunda enterprise L3 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Deployment of manpower and cable fault locator machine duly mounted on vehicle for detection of HT UG cable fault of any size & make by applying upto 15 KV supply to locate the fault. Necessary arrangements required should be provided by the contractor. (Note: Payment under this item shall be measured and made only if any fault is detected) | 35 | Each Fault | 10,000 ₹3,50,000 | 8,000 ₹2,80,000 | 6,000 ₹2,10,000 Lowest | 7,400 ₹2,59,000 | 11,500 ₹4,02,500 | 10,000 ₹3,50,000 | 8,001 ₹2,80,035 |
| 2.00 | Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 95 sqmm 3 core complete all as specified and as directed. | 710 | RM | 5 ₹3,550 Lowest | 5 ₹3,550 Lowest | 5 ₹3,550 Lowest | 25 ₹17,750 | 10 ₹7,100 | 10 ₹7,100 | 7.99 ₹5,672.9 |
| 3.00 | Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 120 sqmm 3 core complete all as specified and directed. | 580 | RM | 5 ₹2,900 Lowest | 5 ₹2,900 Lowest | 5 ₹2,900 Lowest | 25 ₹14,500 | 10 ₹5,800 | 15 ₹8,700 | 7.99 ₹4,634.2 |
| 4.00 | Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 150 sqmm 3 core complete all as specified and directed. | 500 | RM | 5 ₹2,500 Lowest | 5 ₹2,500 Lowest | 5 ₹2,500 Lowest | 25 ₹12,500 | 15 ₹7,500 | 50 ₹25,000 | 11 ₹5,500 |
| 5.00 | Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 240 sqmm 3 core complete all as specified and directed.
Note for sl item no 2 to 5 : Rates includes taking out old cable,cable cover ,sorting of serviciable items etc | 325 | RM | 5 ₹1,625 Lowest | 5 ₹1,625 Lowest | 7 ₹2,275 | 30 ₹9,750 | 20 ₹6,500 | 100 ₹32,500 | 11 ₹3,575 |
| 6.00 | Re-Laying / Re-routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 95 sqmm 3 core all as specified and directed. | 150 | RM | 10 ₹1,500 | 5 ₹750 Lowest | 9 ₹1,350 | 60 ₹9,000 | 20 ₹3,000 | 10 ₹1,500 | 16 ₹2,400 |
| 7.00 | Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 120 sqmm 3 core all as specified and directed. | 100 | RM | 10 ₹1,000 | 5 ₹500 Lowest | 9 ₹900 | 62 ₹6,200 | 25 ₹2,500 | 100 ₹10,000 | 19 ₹1,900 |
| 8.00 | Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 150 sqmm 3 core all as specified and directed. | 100 | RM | 10 ₹1,000 | 5 ₹500 Lowest | 9 ₹900 | 65 ₹6,500 | 25 ₹2,500 | 150 ₹15,000 | 19 ₹1,900 |
| 9.00 | Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 240 sqmm 3 core all as specified and directed. | 75 | RM | 10 ₹750 | 10 ₹750 | 9 ₹675 Lowest | 80 ₹6,000 | 30 ₹2,250 | 150 ₹11,250 | 29 ₹2,175 |
| 10.00 | Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt grade of size 95 Sqmm 3 core earthed laid in trenches / duct passing through pipe / duct or fixed on pole and connecting complete all as specified and as directed. (Note :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.) | 560 | RM | 950 ₹5,32,000 | 972 ₹5,44,320 | 835 ₹4,67,600 | 1,085 ₹6,07,600 | 800 ₹4,48,000 | 650 ₹3,64,000 Lowest | 849 ₹4,75,440 |
Tender Value
₹60 L
EMD Value
₹1.1 L
Closing Date
9 Jul 2025, 6:00 pmClosed
CWE (AF) Jamnagar
CWE (AF) Jamnagar Airforce Station No 1
REPAIR / MAINT OF TRANSFORMERS, HT UG CABLES AND ALLIED WORK AT VARIOUS LOCATIONS UNDER GE (AF) JAMNAGAR NO 1.
2025_MES_715322_1
81243/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Jamnagar
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (AF) Jamnagar No 1
₹1.1 L
Yes
4 Sept 2025
18 Jun 2025
11 Jul 2025
18 Jun 2025
9 Jul 2025
2 Jul 2025
Amount
Deployment of manpower and cable fault locator machine duly mounted on vehicle for detection of HT UG cable fault of any size & make by applying upto 15 KV supply to locate the fault. Necessary arrangements required should be provided by the contractor. (Note: Payment under this item shall be measured and made only if any fault is detected)
Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 95 sqmm 3 core complete all as specified and as directed.
Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 120 sqmm 3 core complete all as specified and directed.
Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 150 sqmm 3 core complete all as specified and directed.
Taking out HT underground cable from trenches / pole etc, aluminium conductor of size 240 sqmm 3 core complete all as specified and directed. Note for sl item no 2 to 5 : Rates includes taking out old cable,cable cover ,sorting of serviciable items etc
Re-Laying / Re-routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 95 sqmm 3 core all as specified and directed.
Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 120 sqmm 3 core all as specified and directed.
Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 150 sqmm 3 core all as specified and directed.
Re-Laying / Re- routing old taking down serviceable HT underground cable from trenches /pole/ducts etc, aluminium conductor of size 240 sqmm 3 core all as specified and directed.
Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt grade of size 95 Sqmm 3 core earthed laid in trenches / duct passing through pipe / duct or fixed on pole and connecting complete all as specified and as directed. (Note :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.)
Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt grade of size 120 Sqmm 3 core earthed laid in trenches / duct passing through pipe / duct or fixed on pole and connecting complete all as specified and as directed. (Note :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.)
Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt grade of size 150 Sqmm 3 core earthed laid in trenches / duct passing through pipe / duct or fixed on pole and connecting complete all as specified and as directed. (Note :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.)
Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt grade of size 240 Sqmm 3 core earthed laid in trenches / duct passing through pipe / duct or fixed on pole and connecting complete all as specified and as directed. (Note :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.)
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmmsqmm t including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M & L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material andaccessories suitable for 3 core XLPEarmoured aluminium conductor cable ofsize 95 sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M & L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material andaccessories suitable for 3 core XLPE armoured aluminium conductor cable of size120 to 185 Sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M & L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material andaccessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
M & L for Servicing of up to 160 KVA capacity transformer/Isolation TR, 11 KV / 433 V, by disconnecting LT / HT connections from site of installation, inspection/assessing of the defective/burnt parts, core assembly of transformer in the presence of Engineer-in-Charge and cleaning complete for making it carbon free, checking for any loose bushings & making it rectified if found & reconnecting with LT / HT connections, testing and commissioning on load complete all as specified and as directed. (i) Filtration of transformer oil if required will be measured & paid separately. (ii) Topping up with new transformer oil if required will be measured & paid separately.(iii) Any spare Part if found unserviceable will be measured & paid separately and minor parts such as nuts, bolts, washers, etc. shall be arranged by the contractor and the cost thereof shall be deemed to be included in the unit rate quoted against this item.
All as per item No 20 above but 160 to 250 KVA capacity transformer 11 KV / 433 V.
All as per item No 20 above but 315 to 400 KVA capacity transformer 11 KV / 433 V.
All as per item No 20 above but 500 TO 750 KVA capacity transformer 11 KV / 433 V.
All as per item No 20 above but 1000 KVA capacity transformer 11 KV / 433 V.
S&F in repairs 11 KV HT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase) for transformer of capacity up to 250 KVA complete all as specified and as directed.
S&F in repairs 11 KV HT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase) suitable type transformer of capacity 315 to 400 KVA complete all as specified and as directed.
S&F in repairs 11 KV HT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase) suitable for out door/indoor type transformer of capacity 500 to 1000 KVA complete all as specified and as directed.
S&F in repairs 0.433 KV LT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase & neutral) suitable for transformer of capacity up to 250 KVA complete all as specified and as directed.
S&F in repairs 0.433 KV LT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase & neutral) suitable for transformer of capacity 315 to 400 KVA complete all as specified and as directed.
S&F in repairs 0.433 KV LT terminal comprising stud, insulator, nut, bolt, washer etc (for three phase) suitable for out door type transformer of capacity 500 to 1000 KVA complete all as specified and as directed.
Supply & topping up of transformer oil up to required level for transformer / PT's / stabilizers / HT switches etc of duly filtered with filtration plant to obtain high dielectric strength 50 KV & above all as per IS specification, complete all as specified and as directed. (Note : Transformer oil shall be supplied in sealed barrels with test certificate.) (ISI Marked)
Dehydration / filtration of transformer oil of transformers, isolation transformer, OCBs, PT's, oil switches, Ring main Tee unit , Stabilizers etc of various capacities installed at different locations by disconnecting plants electrically for recirculation existing transformer oil with trolley mounted filtration plant till dielectric strength not less than 60 KV.Note- Quoted rates shall be deemed to include for following :- (i) Oil shall be tested after filtration and test result will be recorded before & after filtration of oil.(ii) Contractor should make his own arrangement for oil filtration plant including transportation complete.(iii) New Transformer oil for topping up will be measured and paid in relevant item as required (iv) All necessary T&P / testing equipment shall be provided by the contractor at his own cost. No extra payment shall be made to the contractor.
Supply and fix in repairs breather with first quality silica gel dehydrated for transformer of capacity from 63 KVA to 1000 KVA complete all as specified and as directed. (Note :- Size of breather shall be provided as per OEM specification.)
Supply and fix in repairs temperature gauge suitable for transformer of capcity up to 160 KVA complete all as specified and as directed.
Supply and fix in repairs temperature gauge suitable for transformer of capcity up to 200 KVA to 1000 KVA complete all as specified and as directed.
Supply and fix in repairs oil level gauge for transformer of capacity from 63 KVA to 1000 KVA complete all as specified and as directed.
M & L for preparation of old painted surface of transformer of capacity 63 to 750 KVA, including connected accessories complete by cleaning / scraping oil, grease dirt and rust with steel wire brush and emery paper to obtain clean and smooth surface, and applying two coat of synthetic enamel paint as per MES colour code, including rewriting of MES No / Sl No complete all as specified and directed.
M & L for rewinding of HV / LV limb of transformer (Oil type/ Dry type)/stabilizer of any capacity taking down from site of installation, inspection/assessing of the defective/burnt parts, core assembly of transformer in the presence of Engineer-in-Charge and then lifting, loading and transportation of unserviceable transformer to the workshop for repair/rewinding and repair to the transformer by dismantling the top cove rby dismantling and removing the burnt out copper winding cleaning of limb thoroughly and rewinding the same with super enameled copper winding wire of the same gauge and turn with proper class of insulation impregnated & baking, assembling and testing complete all as specified & as directed .(Note:-(i) Transportation to local/ company workshop is deemed to be in above quotted rate (ii) The transformer shall only be got repaired from one of the authorized firms/agencies of the manufacturer as approved by GE.)
Cutting, trimming and pruning of trees/tree branches/creepers/climbers of all around Sub Stn up to 5 feet area including fencing/boundry wall and cleaning the disturbed area beneath and removing the tree branches and debris from site and depositing outside complete as specified and directed. (Girth of tree not less 30 cm measured 1m above GL.)
Material and labour for area cleaning and cutting of grass ,plants,shrubs ,vegitations using grass cutting machine or mannually within the sub statin area including removal of all debries complete all as specified and directed (Area not less than 10 sqm) Note:-(i) The grass,plants,shrubs,vegitation and bushes shall not be allowed to grow more than 15 Cm from hte ground level of any time
Supply and spreading 40 mm size graded stone aggregate on ground of sub station, average spreading levelling complete, all as specified and directed. (Note: Measurement shall be carried out for net finished volume of work executed).
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm including dismantling & taking out old unserviceable jointing kit, complete all as specified and as directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out soft/loose soil complete all as specified and as directed. .
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
Removing excavated soil to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed. .
M&L for providing dry river sand as in sand cushioning below and above cable thickness as specified in SSR to under ground cable including punning down of sand in layer complete all as specified and as directed. (Note: for measurement purpose punned thickness of sand will be considered.)
Laying only serviceable PCC cable cover for HT UG cable of any type complete all as specified and as directed.
Supply & laying ISI marked & conforming to IS - 5820 - 1970 unreinforced precast concrete cable cover Class HV ,type-1 flat of size 300 mm X 180 mm X 40 mm in trenches as protection to HT UG cable complete all as specified and as directed.
Supply and laying in repair GI tubing 100 mm dia bore light grade laid in trenches / floor / fixing on pole / wall for cable protection with necessary fittings etc including taking down old tubing complete all as specified and directed
M&L for Boring under roads / pavement / hard standing without disturbing the top surface by trench less technology using ultra sound technique and necessary machine including supply & inserting HDPE pipe of 150 mm dia (ISI Marked) suitable for 0.4 mpa working pressure for passing through the cables complete all as specified and as directed. (Note : Necessary T & P required for boring shall be arranged by the Contractor at his own cost.)
M & L Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment Fe-290 (Gde E 165)
Note for above Srl Item No 1 to 51 :- (i) Work shall be executed by the authorised service mechanic/Electrician of manufacturer,After satisfactorily completion of servicing of HT Transformer/VCB/HT Breaker/HT Tap changer If any fault occurs upto the completion of contract should be attended by concerned rep within stripulated time frame without fail , quoted rates is deemed to be included all such charges. (ii) If any above HT Equipment and connected items become breakdown, the contractor shall loacate the problem/fault at site within 12 hours on intimation by JE/Engineer-In-Charge and ensure that the fault to be rectified within 48 Hours , failing which an amount of Rs 200 /- per hour will be recovered as a penal recovery from any payment due to contractor after expiry of 48 hours.) (iii) Minor consumable items, ie Nuts bolts, Control wires , PVC tapes, Welding Job, cotton waste & cleaning clothes, petroleum jelly, grease , lubricating oil, emery paper , T & P items etc, is to be arranged by contracttor without any extra cost.
rajengineers (BID ID -3352003)
shree chamunda enterprise (BID ID -3352367)
M/s SK Traders (BID ID -3352687)
Sukhi Electricals (BID ID -3349636)
Nitesh Enterprise (BID ID -3352929)
JAMNAGAR ELECTRIC AND MACHINERY CO (BID ID -3352530)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .