Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC Being lowest |
| 2 | L2₹1.6 Cr+₹34.3 L (26.6%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | ₹1.6 Cr+₹34.3 L (26.6%) | L2 | Rejected-Finance Being not lowest |
Tender Value
₹1.7 Cr
EMD Value
₹2.5 L
Closing Date
6 Dec 2021, 6:00 pmClosed
CE AF GANDHINAGAR
CE AF GANDHINAGAR CHILODA
CERTAIN E/M AND B/R WORKS AT EEC BAY AT AF STN JAMNAGAR
2021_MES_481842_1
86270
Open Tender
Electrical and Maintenance Works
Lump-sum
365 days
GE AF JAMNAGAR NO 1
AS PER NIT AND TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE AF JAMANAGR NO 1
₹2.5 L
Yes
10 Jan 2022
14 Oct 2021
7 Dec 2021
14 Oct 2021
6 Dec 2021
22 Nov 2021
18 Oct 2021 - 23 Oct 2021
Amount
NOTE: Schedule ‘A’ Part I to VI are under Ser No. 1.00 to 6.00. are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lump sum price worked out for Building / Structures as listed in Sch `A’ Part I.
Lump sum price worked out by the Contractor for Excavation & Earth works as listed in Sch `A’ Part II
Lump sum price worked out by the Contractor for Internal electrification as listed in Sch 'A' Part III
Lump sum price worked out by the Contractor for External Electrification as listed in Sch `A’ Part IV.
Lump sum price worked out by the Contractor for Lightening Protection as listed in Sch `A’ Part V.
Lump sum price worked out by the Contractor for Air Conditioning as listed in Sch `A’ Part VI.
SCHEDULE 'A' PART - VII (MISC ITEMS) (Note for items 07 to 33 : The contractor shall quote his rate for each of these items separately. The estimated rate is left blank since the same is not prepriced by MES)
Dismantling existing central AC Plant of cap 3 x 50 TR alongwith connected items viz. Chiller piping, electrical panel, AHU's electrical motor/pump, cooling tower etc and depositing in MES store Yard. All as per direction of Engr-in-Charge. Note :- (a) Tools and equipments required for its dismantling process is deemed to be included in the rate quoted. (b) Vehicle reqd for shifting of unsv central AC plant including loading and un loading is deemed to be included in the rate quoted.
Supply and installation of Air cooled scrolled type chiller unit with CFC free R-407C/134A refrigerent, each unit of equal capacity not less than 3x 50 TR.(=Total 150 TR, 2x 50TR=100TR working and 1 x 50TR standby) with following specification:-
Supply, Installation, testing and commissioing of Air cooled, floor mounted water chilling machine Net capacity complete with chilled scrolled type multiple compressor, star delta starter, shell and tube chiller, Air cooled Fin and tube type condenser, condenser fan, common based frame/skid structure, interconnected copper refrigerent piping, vibration insulator, gauge panel, flexible connector at chiller connections, automatic safety controller, ozone friendly CFC free refrigerent gas R-407C/ 134A and oil, Nitrile rubber insulation of chiller and suction pipe etc. The motor shall be suitable for operation on 415+ 10% Volt, 50 Hz, 3 Phase AC power supply. Chilling machine shall be complete with its micro processor based control panel and starter with main switch. Chiller panle shall be complete for remote operation and should provide status (additional potential free contacts shall be required to perform this function) and electrical heater. Necessary civil work such as PCC foundation for placement iof chiller to be covered in the scope of work.
The chiller shall be as per the techincal specification. The water chilling machine shall meet the following design parameters: (a) Actual minimum cooling cap required : 100 TR @ local ambient condition. (b) Chilled water leaving temp 44° F (6.6 Deg.C) (c) Chilled water entering temp : 54° F (12.2 Deg.C) (d) Evaporator fouling factor : 0.0005 (FPS) Make of strip heater : Industrial/Rapid cool/Dashpass Make of Thermostat : SIEMENS/Honey well/Jhonson/Steffa Make of chiller unit : Voltas/Carrier/Blue star/York (e) LKW/TR : Not exceeding 1.3 (f) Refrigerent (Ozone friendly type) : R 407C/R-410/R-134A (g) Two working simultaneously and one as standby.
Note :- 1. contractor before quoting the tender will visit the site,calculate tonnage,check the design to meet the cooling parameter and feasibility of installation of design and sepecification provided by the department. 2. Accessories, fittings, supporting items complete as specified in BOQ shall be included in the rate. No extra payment shall be allowed for the same.
Supply, Installation, testing and commissioing of end suction and top discharge type centrifugal pump back pull out type for chilled water recirculation, complete with cast iron body, bronze impeller complete with mechanical seal, TEFC squirrel cage high efficiency induction motor, base plant, mounted channel frame, accessories and fittings i.e flexible connectors (bellows) at inlet and out let connections, mechanical seal, pressure gauge, thermometer, drains, coupling, coupling guard, vibration isolatiion arrangement by means of springs/rubber type mounting of resistoflex make as specified of the following capacities and shall be suitable for operation on 415 +10% V, 50 Hz, 3 phase AC supply. The pumps shall be insulated with nitrile rubber with suirable thickness. (a) Capacirty : 105 USGPM (b) Head : 30 Mtrs. (contractor to check and verify the pump head as per actual site condition). (c) Impeller : Bronze. (d) Appx electrical rating 10 HP. Make of pump : Jhosnson/Beacon/Kirloskar. Make of motor : Crompton/NGEF/BEEL/ABB/SIEMENS.
Supply and fixing 43mm thick double skin type Air handling unit with 10 micron per filters with starter panel with following description:-
Supply, Installing, testing and commissioing of double skin type horizontal floor mounted, top/side discharge Air handling unit with double skin thermal brake aluminium profile construction using 22 G sheet metal sanwitch panel with 43mm thick injected spray type PUF panels,desity 38Kg/Cum. the AHU shall be as per the specification under section "double skin Air Handling Units" in the tender document. (a) Fan section with AMCA certifiied backward curved type imported nicotra/kruger. Make blower with outlet velocity not exceeding 9.2 mtr per second. (b) Drive motor suitable for 400 + 15% volt, 50 Hz, 4P, TEFC squirrel cage high efficiency induction motor and BHP rating 20% higher than the peak capacity. (c) 'V' belt drive assembly with pullys, belt guard, etc, double canvas/rexin connection with Zip to discharge duct/Plenum etc. (d) Filter section consist of 50mm thick wasable HDPE 90% down 10 micron pre-filters, filter fixing frame work, hinged type access doors, etc.
(e) 6 row deep chilled water coil section with chilled water coil should be as per ARI condition, aluminium finnes and copper tube on 21 Kg/cm2 with assessed sandwitch drain tray etc. (f) 18 Gauge MS CRCA duly powder coated AHU sub panel board in compartmentalised construction with in comer and out going feeders for AHU motors, 3 way valve actuator motor, Fired dumper actuator motor etc. complete with reqd star delta starter, relays, time, contactor, voltage transformer, push buttons, switches, internal wiring etc. (g) Accessories like hinged type access doors for filter section, fan secton etc, side glass, marine lamp with limit switch, supply, return and fresh air flanged type connection with low leakage arrow foil design dampers, rubber sleeves for pipes and cable entry, flow direction arrows vibration isolation spring type pads, motor sliding rail etc. (h) Double skin horizontal floor mounted AHU. TR : 51, CFM: 14500 to 15000, Static pressure mm : 65. Make of AHU : CARYAIRE/Citizen/Zeco/ EDGETECH/CARE Make of AHU Fan : Nicotra/Kruger. Make of motor : Crompton/ NGEF/BBL/ABB/SIEMENS
Supply & Fixing in position of approved make flow switch complete with aiuminum control wiring at chiller outlet each machine.
Supply, Installation, testing and commissioining of 80mm dia (for pump) of 'Y; type strainer CI/MS body, bolt, cover, flanged ends, baskets of brass/ bronze/SS Wire mesh 24G x 14 Mesh for chilled water application complete with flanges, nut bolts, gaskets duly insulated with 50mm thick TF quality EPS and covered with 12mm sand cement plaster and complete all as specified. Make : TRISHUL/LEADER/SANT/ FLOWEL/ HONEY WELL
Supply, Installation, testing and commissioining of 150mm dial type temperature gauge with appropriate range and staineless steel valves and SS tubing complete all as specified. Make : H GURU/FIBIEG/
Supply, Installation, testing and commissioining of 32 mm dia drain valve for chilled water piping complete all as specified. Make : H GURU/FIBIEG/
Supply, Installation, testing and commissioining of 25 mm dia auto Air purge valve for chilled water piping complete all as specified.
Supply, Installation, testing and commissioining of site fabricated MS channel/angle support structure/pipe rack for the piping and the ducting work complete all as specified.
Supply, Installation, testing and commissioining cabling work with cable end termination for 35 sqmm x 3.5 core XLPE insulated copper conductor armoured cables/wires fo 1100/650V grade for chiller units inlcuding cost of all crimping lugs and single compression glands, cable sockets insulating tape, ceiling compound etc. Make : Havells/Finolex/Polycab
Supply, Installation, testing and commissioining cabling work with cable end termination for 4 sqmm x 4 core XLPE insulated copper conductor armoured cables/wires fo 1100/650V grade for Air Handling Unit/pumps etc including cost of all crimping lugs and single compression glands, cable sockets insulating tape, ceiling compound etc. Make : Havells/Finolex/Polycab
Supply and fixing cabling work with cable end termination for 50 sqmm x 3.5 core XLPE insulated copper conductor armoured cables/wires fo 1100/650V grade for Air Handling Unit/pumps etc including cost of all crimping lugs and single compression glands, cable sockets insulating tape, ceiling compound etc. Make : Havells/Finolex/Polycab
Supply, Installation, testing and commissioining of floor mounted indoor type,(CPRI approved Manufacturer) cubicle and compartmentlised front SS type, medium voltage electric panel of duct and vermin proof, fully tropicalised construction, front openable doors and shutters with locking arrangements, made out of 14 SWG (2.0mm thick) CRCA shhet steel, fabricated, powder coated, suitable for operation on 450 V, 3 Ph, 4 wire, 50 Hz, AC supply complete with all inter connections and consisiting of all accessories like 4 Nos 800 Amp aluminium bus bar, indicating lamps, push button, CT's, digital ampere , voltage, frequency and KWH meter, danger plate, lifting hooks, feeder name plate suiatable for following feeders:- Note :- (The Panel shall be of suitable size to accommodate all the accessories mentioned below installed on padestal made out of angle iron of size 50mm x50mm x 6mm and earth work, PCC foundation, suitable cable glands for cable entry etc).
(a) Incomer - MCCB 500A, FP, 415V, 50 KA with Thermal and magnatic -01 Nos (b) Out going :- MCCB 125 Amps 25 KA, TP,415V, 50 Hz - 05 Nos (c) MCCB TP 25 Amps16 KA 415V -08 Nos (d) MCCB TP 40 Amps 16 KA 415 V -04 Nos (e) MCB SPN 32 Amps 10KA C series - 01 Nos (f) MCB SP 10 Amps 10 KA C series- 14 Nos
Supply, Installation, testing and commissioining of floor mounted indoor type,(CPRI approved Manufacturer) cubicle , medium voltage electric panel of duct and vermin proof, fully tropicalised construction, front openable doors and shutters with locking arrangements, made out of 14 SWG (2.0mm thick) CRCA shhet steel, fabricated, duly powder coated, suitable for operation on 450 V, 3 Ph, 4 wire, 50 Hz, AC supply complete with all inter connections and consisiting of all accessories like 4 Nos 300 Amp aluminium bus bar in suitable size of enclosure consisting the following for chiller pumps :- (a) MCCB 4P, 50Hz, 100A, 25 KA - 01 No (b) Fully automatic Star Delta Starter 15 HP for chiller pump motor -01 No (c) Digital Multifunctional meter -01 No (d) Start -Stop push button- 01 set (e) Control wiring with suitable size of copper conductor wire- 01 Job
Supply, Installation, testing and commissioining of floor mounted indoor type,(CPRI approved Manufacturer) cubicle , medium voltage electric panel of duct and vermin proof, fully tropicalised construction, front openable doors and shutters with locking arrangements, made out of 14 SWG (2.0mm thick) CRCA shhet steel, fabricated, duly powder coated, suitable for operation on 450 V, 3 Ph, 4 wire, 50 Hz, AC supply complete with all inter connections and consisiting of all accessories like 4 Nos 300 Amp aluminium bus bar in suitable size of enclosure consisting the following 3 Ph Star Delta starter in suitable size of enclosure consisting the following for AHU :- a) MCCB 4P, 50Hz, 100A, 25 KA - 01 No (b) Fully Automatic Star Delta Starter 20 HP for chiller AHU -01 No (c) Digital Multifunctional meter -01 No (d) Start -Stop push button- 01 set (e) Control wiring with suitable size of copper conductor wire- 01 Job
Supply, installation, testing and commissioning of automatic fire damper of fusible link type as required for operation complete all as specified. Note :- The fire damper shall be spring activated on melting of fusible link having melting point of 67 to 78 deg C. Fire damper shall be tested as per ULL/555 and certified by CBRI. Make :- CARYAIRE/ TCS/ TRISTAR/ GREENHEOK
Supply, installation, testing and commissioning of thermal insulation of internal supply & return air duct using 50mm thick fibre glass wool insulation of fire retardant quality faced with factory backed aluminium foil. The joints shall sealed with 50mm wide self adhesive tape for inside duct work.
Supply and installation of acuostic insulation with using 18mm thick open shell nitrile rubber to reduce the noise level duct/plenum. Make :- ARMAFLEX/ AEROFLEX/ DURKEE
Supply and fixing, installation, testing and commissioinig of Industrial Dehumidifier 3000 CMH process air flow, 300 Pa process ESP, 1.5 KW process motor, React Air flow 1000 CMH, 250 Pa react ESP, React motor KW 0.746, React Heater 32 KW, 3 ph, 415V, making 2 Nos 100mm dia holw in existing wall for supply and return air duct in existing wall for supply and return air duct including providing flwxible aluminium duct 2 nos for supply & return air all as specified and directed by Engr-in-charge comprising following items :- Make -Bry Air or equivalent DRI, Advance international. (i) Basic dehumidifier comprising of a high efficiency "Ecodry" desiccant honeycomb rotor/bed mounted on a horizontal fixed shaft arrangement. It shall have positive sealing of process and reactivation air stream tp allow for independent air low with no balancing reqd.
(ii) Supply air section oomprising of :- (a) Inlet pre-filter EU-4- synthetic non woven media filter. The filter shall be encased in housing which will form an integral part of dehumidifier. (b) Process fan and motor arrangement. The TSP of fan is 3.5" wg. (iii) Regeneration package mounted on the main sub structure comprising of :- (a) Inlet pre-filter synthetic non woven media filter. The filter shall be encased in housing which will form an integral part of dehumidifier. (b) Either electrical heater abnk or steam coil with electrical heater for steam reactivation. (c) Regeneration fan. (d) Regeration fan motor control. (e) Thermostat (f) Standard electrical panel, pre-wired, pre tested mounted on the unit. Note :- Steam reqd at 7Kg/Cm 2 pressure.
(iv) Requisite number of manual controlled dampers. (v) Brystat humidity controller (Humidi stat). (vi) Skid for mounting the entire unit as discribed above to avoid foundation at site. The skid shall be complete with adequate lifting legs. Note :- The rate quoted shall include all Misc civil work to pass pipes, cables & ducts at site PCC foundation fotr chillers, Pumps, AHU, Electrical panel board, expansion tank etc. The cut outs shall be closed and finished to the original finish after completion of work.
Supply and fixing of prefabricated type trays of size 300mm wide x 50mmx1.6mm fabricated out of preforated hot deep galvanised sheet for minimum 1.6mm thick with 50mm flame to be installed be completetd including cost of bends, elbow, cross, tees reducers etc as per anchor fastners screw, nuts, bolts and support strcture etc fixing hardware painting all as speicfied and as directed as apprroved by GE
Supply and fixing of prefabricated type trays of size 150mm wide x 50mmx1.6mm fabricated out of preforated hot deep galvanised sheet for minimum 1.6mm thick with 50mm flame to be installed be completetd including cost of bends, elbow, cross, tees reducers etc as per anchor fastners screw, nuts, bolts and support strcture etc fixing hardware painting all as speicfied and as directed as apprroved by GE
S&F PCC block Hollow (15cmx15cmx20cm) for fixing of GI/Aluminium/Copper strip with suitable size of insulators on roof top complete all as specified and as directed by Engr-in-Charge.
Supply, installation, testing and commissioning of DUCT (square/rectangular) fabricated with galvanised steel sheet (GSS) 0.914mm thick, 20 Guage (SWG) having zinc coating of 140gm/sqm total on both sides complete with gaskets, elbows, splitters, vanes, supports etc as per IS : 655/1963 (Revised upto date) and including with required scafolding work to install the ducts all as directed by Engr-in-charge.
Supply, installation, testing and commissioning of DUCT (square/rectangular) fabricated with galvanised steel sheet (GSS) 0.711mm thick, 22 Guage (SWG) having zinc coating of 140gm/sqm total on both sides complete with gaskets, elbows, splitters, vanes, supports etc as per IS : 655/1963 (Revised upto date) and including with required scafolding work to install the ducts all as directed by Engr-in-charge.
Supply & fix 100mm size balancing valves, cast iron body, flanged type, stainless steel stem, EPDM disc, pressure test cocks complete with companion flanges, nuts, bolts, gaskets and probes for pressure measurement complete with needle valves and dial type gauge for pressure reading etc duly insulated all as directed.
Supply & fix 65mm size balancing valves, cast iron body, flanged type, stainless steel stem, EPDM disc, pressure test cocks complete with companion flanges, nuts, bolts, gaskets and probes for pressure measurement complete with needle valves and dial type gauge for pressure reading etc duly insulated all as directed.
M/s SK Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .