Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC 58 MODERN MARKET NEAR AMBER CINEMA JAMNAGAR | JAMNAGAR | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹20.8 L+₹74,940 (3.73%)Rejected-Finance PARTH B 203 PATEL COLONY STREET NO 11 ROAD NO 3 JAMNAGAR 361 006 GUJARAT | JAMNAGAR | GUJARAT | 361006 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹22.6 L+₹2.5 L (12.6%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹25.1 L+₹5.0 L (25.0%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹25.1 L+₹5.0 L (25.1%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
21 May 2022, 6:00 pmClosed
GE I NAVY JAMNAGAR
INS NAVY VALSURA JAMNAGAR 361150
REPAIR REPLACEMENT AND MAINTENANCE OF INTERNAL ELECTRIC SUPPLY AND REWIRING TO CERTAIN MD AND OTM ACCN OF ZONE B AREA UNDER GE I NAVY JAMNAGAR
2022_MES_517539_3
8583
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GE I NAVY JAMNAGAR
Please refer tender documents
6 documents required · 6 mandatory
₹500
GE I NAVY JAMNAGAR
₹60,000
Yes
13 Feb 2023
14 May 2022
23 May 2022
14 May 2022
21 May 2022
14 May 2022
14 May 2022 - 14 May 2022
Amount
Note: (i) The contractor has to check the fittings / fixtures and wiring as per the complaint given by the Engineer-in-Charge / concerned JE. Spares being replaced shall be intimated by JE and the replaced spares will be measured and paid under respective items of BOQ and no extra payment will be done for the same. (ii) It is the responsible of the Contractor to ensure that day to day complaints slips are collected every morning before distributing labours from JE from MES service centre and attend & complete the complaints the same day irrespective of any number of complaints and return back the complaint slip duly signed by the User to JE the same evening as a token of defect rectified as such contractor to make all arrangements including supply of materials required for attending complaints without any delay, the quoted rate against various items is deemed to be inclusive of above exercise Taking down existing light fittings fixed in any description and S&F new 20 Watt wall mounted 4 ft glaze LED batten CCT(K) 6500 high quality design aluminium extruded with decortive and caps fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Cat No. LGLZ01X020XW 20 W CCT 6500 or equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
Taking down existing light fittings fixed in any description and S&F new 10 Watt wall mounted 2 ft glaze LED batten CCT(K) 6500 high quality design aluminium extruded with decortive and caps fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Cat No. LGLZ01X010XCW10 W CCT 6500 or equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
Taking down existing street light fittings of any type and S&F new LED street light 45 Watt in aluminium pressure die cast housing with touch glass cover (IP 66 protection) on walls /steel/concrete pole any height including connection from ceiling rose / Junction Box to light fitting with and including three core 1.5 Sqmm cable multistranded copper conductor pvc insulated and pvc sheathed 1100 V grade any length fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Model No LED street light Cat No -LSRT01SO45XC CCT 6000K or an equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
Taking down existing any type of light fittings fixed in any description and S&F new LED Recess/ Pendent mounted LED light fittings 36/ 40 Watts white powder coated CRCA housing with full window acrylic diffuser (2ftx2ft) the CCT should be between 3000k to 6500k fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Model ULTIMA , Cat No LULT01S036XC or equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
Taking down existing light fittings fixed in any description S&F new 36 /40 W LED panel, indoor surface mounted made from CRCA housing with full window acrylic diffuser, 2 ft X 2 ft lighting fixture flat light dissipater. The CCT(K) should be between 3000 to 6500 fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Cat No. LSVR01S040XC or equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
Taking down existing light fittings fixed in any description S&F new 42 W ultra slim, LED panel light fittings extrucded aluminium housing frame(Pendant) 1x4 ft. The CCT should be 600 K including suspended accessories etc fixed as per manufacturers instructions and making necessary electrical connections and testing on completion complete all as directed. Make: Jaquar Cat No. LSVR03S042XC or equivalent of Bajaj / Crompton / Philips / Wipro/ Havells.
S&F in repairs ceiling rose surface bakelite White / Ivory / Urea finish 50 mm dia three terminals including supply and fix PVC square mounting block complete all as specified and directed.
S&F in repairs switch piano flush, single pole, one way 5 / 6 Amp complete all as directed. Make: Anchor / Standard / Leader
S&F in repairs switch socket outlet 3 Pin 6 Amp flush type complete all as directed. Make: Anchor / Standard / Leader
S&F in repairs switch socket outlet multipurpose 3 Pin 16 Amp and 3 pin 6 Amp, 240 Volt, controlled by one switch complete all as directed. Make: Anchor / Standard / Leader
S&F in repairs switch bell push, piano flush type, single pole, 6 Amp complete all as directed. Make: Anchor / Standard / Leader
S&F in repairs bell AC 230 Volt Ding Dong type, 240 Volt AC supply complete all as directed. Make: Anchor / HPL / Rider/ Leader
S&F in repairs bell push modular type 6A with all accessories complete all as directed. Make: Legrand Cat No 6755 04 or equivalent of Philips / Crabtree / ABB / Havells
S&F in repairs switch modular type single pole one way 6 Amp with all accessories complete all as directed. Make: Legrand Cat No. 6755 01 or equivalent in Philips / Crabtree / ABB / Havells
S&F in repairs switch modular type single pole one way 16 Amp with all accessories complete all as directed. Make: Legrand Cat No. 6755 11 or equivalent in Philips / Crabtree / ABB / Havells
S&F in repairs socket outlet 3 Pin 6 Amp modular type all accessories complete all as directed. Make: Legrand Cat No. 6755 52 or equivalent in Philips / Crabtree / ABB / Havells
S&F in repairs socket outlet multipurpose 2/3 Pin for 6 / 16 Amp modular type with all accessories complete all as directed. Make: Legrand Cat No. 6755 55 or equivalent in Philips / Crabtree / ABB / Havells
S&F in repair step type fan regulator 100 W, 2 module, AC, 230V, electronic complete all as specified and as directed. Make: Legrand Cat No. 6755 30 or equivalent in Indo Asian/ Havells/ Crabtree
S&F in repair step type fan regulator AC, 230V, electronic on the existing phenolic laminated sheet etc complete all as specified and as directed. Make: Anchor/ Legrand/ Havells/ Crabtree/ Indo Asian.
S&F in repair MCCB DB's VTPN (Vertical DB) type double door in wall/ nitch when MCCB's to be used four pole and neutral, 4 way, 415 Volt with rated busbar, suitable for flush mounting and surface mounting with 160 Amps copper busbar for each pahse and 2 neutral bar, 2 Earth bar and cable ties for cble management, fully insulated busbar and shrouded Neutral bar, improved pan assembly for ease of intallation, Prefitted masking sheet, Reversible door for IP 43 & IP 54 DBs with provision for DPX3 160 MCCB as incomer and TPN/ SPN/ DP/ SP outgoing IP 54 Protection Make: Legrand Cat No. 5077 50 (No. of modules DPX3 160+12) or equivalent in Indo Asian, Standard and incuding MCCB DPX3 160 Amp 415 V with adjustable thermal and magnetic setting of breaking capacity 36 kA complete all as specified and as directed by Engineer-in-Charge. Make: 4200 87 (MCCB 160 Amps) or equivalent in Indo Asian, Standard.
S&F in repairs epoxy powder coated sheet with metal door enclosures with 2 mm thick CRCA sheet for and including MCB DB SPN 4 way, 240 V with 200 Amp rated bus bar with double door locking system complete. Make: Legrand Cat No. 5076 10 or equivalent of Havells / L&T / ABB
S&F in repairs epoxy powder coated sheet with metal door enclosures with 2 mm thick CRCA sheet for and including MCB DB SPN 8 way, 240 V with 200 Amp rated bus bar with double door locking system complete. Make: Legrand Cat No. 5076 11 or equivalent of Havells / L&T / ABB
S&F in repairs epoxy powder coated sheet with metal door enclosures with 2 mm thick CRCA sheet for and including MCB DB TPN 4 way, 240 V with 200 Amp rated bus bar with double door locking system complete. Make: Legrand Cat No 5076 70 or equivalent of Havells / L&T / ABB
S&F for Single pole and neutral enclosure with a two pin and earth plug and socket complete 240 V with one single pole MCB 20 Amps complete all as directed. Make Legrand Cat No. 5078 11 or equivalent in Havells/ L&T/ ABB
S&F in repairs MCB SP 16 to 32 amp, 50 Hz, AC supply, 10 kA. Make: Legrand Cat No. 4085 92 to 4085 95 / Havells / L&T / ABB
S&F in repairs MCB SPN 10 to 32 Amp 240 V 50 Hz AC supply, 10 kA. Make: Legrand Cat No. 4086 12 to 4086 17 or equivalent of Havells / L&T / ABB
S&F in repairs MCB SPN 40 to 63 Amp 240 V 50 Hz AC supply, 10 kA. Make: Legrand Cat No. 4086 18 to 4086 20 or equivalent of Havells / L&T / ABB
S&F in repairs MCB TPN 32 Amp, 50 Hz, AC supply, 10 kA with proper size lugs. Make: Legrand Cat No. 4086 80 or equivalent of Havells / L&T / ABB
S&F in repairs MCB TPN 63 Amp, 240 V, 50 Hz, AC supply. Make: Legrand Cat No. 4086 83 or equivalent of Havells / L&T / ABB
Taking down carefully copper/ aluminium point wiring (light, fan, socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators, sockets etc. to be measured separately), removing materials to store for keeping in safe custody for re-use at site and making good disturbed surfaces of walls, floors, etc to match with the existing surface complete all as directed.
M&L for point wiring with 1100 V, 1.5 Sqmm single core PVC insulated unsheathed cable, copper conductor multistranded passing through heavy duty PVC casing, capping, double lock type, min 25 mm wide including sheet metal box, terminal plates suitable for modular switch, socket etc. with all accessories, concealed MS box / PVC modular box with cover and 1.5 sqmm earth copper cable, for one light point, bell point, fan point controlled by one switch including cutting and making good surface of walls applying suitable painting as required all as directed.
All as per item No. 31 here-in-above, but for 6 Amp (2/ 3 pin), modular switch socket in same board with earth wire 1.5 Sq.mm PVC insulated multistranded copper conductor cable complete all as directed.
All as per item No. 31 here-in-above, but for 6 Amp (2/ 3 pin), modular switch socket in independent board with earth wire 1.5 Sq.mm PVC insulated multistranded copper conductor cable all as directed.
All as per item No. 31 here-in-above, but size of cable 2.5 Sq.mm for 16 Amp and 6 Amp (3 pin) combined, modular switch socket in independent board with earth wire 2.5 Sq.mm PVC insulated multistranded copper conductor cable all as directed.
M&L for point wiring with 1100V grade with 1.5 Sqmm single core PVC insulated cable, copper conductor multistranded passing through in existing PVC concealed 20 mm dia conduit and conduit accessories with concealed MS/ PVC Box and logic modular white plate of suitable size as required at site with PVC insulated unsheathed stranded copper conductor of size 1.5 sqmm as earth wire connected to common earth dolly as specified for one light point controlled by one switch complete all as directed. Note : (1) Rate include cost of cutting wall / floor / ceiling and making chasses and MS box in concealed for cutting and sinking for boxes and making good to walls, no extra payment will be made for the same. (2) Switch and socket shall be measured and paid separately.
All as per item No. 35 here-in-above, but for 6 Amp (2/ 3 pin), modular switch socket in same board with earth wire 1.5 Sq.mm PVC insulated multistranded copper conductor cable complete all as specified.
All as per item No. 35 here-in-above but for 6 Amp (2/ 3 pin), modular switch socket in independent board with earth wire 1.5 Sq.mm PVC insulated multistranded copper conductor cable complete all as specified.
All as per item No. 35 here-in-above but size of cable 2.5 Sq.mm for 16 Amp and 6 Amp (3 pin) combined, modular switch socket in independent board with earth wire 2.5 Sq.mm PVC insulated multistranded copper conductor cable all as directed.
Taking down old existing sub main wiring and M&L for sub main wiring with 2 run single core 2.5 Sq.mm PVC insulated unsheathed copper multistranded conductor 1100 Volts grade drawing into and including PVC heavy duty casing and capping with PVC coated copper earth conductor 2.5 Sq.mm one run complete. Note: 2 run of 2.5 Sq.mm cable one run 2.5 Sq.mm PVC insulated cable copper multistranded conductor alongwith PVC cassing capping will be measured as one unit.
Taking down old existing sub main wiring and M&L for sub main wiring with 2 run single core 4 Sq.mm PVC insulated unsheathed copper multistranded conductor 1100 Volts grade drawing into and including PVC heavy duty casing and capping with PVC coated copper earth conductor 4 Sq.mm one run complete. Note: 2 run of 4 Sq.mm cable one run 4 Sq.mm PVC insulated cable copper multistranded conductor alongwith PVC cassing capping will be measured as one unit.
Taking down old existing sub main wiring and M&L for sub main wiring with 2 run single core 6 Sq.mm PVC insulated unsheathed copper multistranded conductor 1100 Volts grade drawing into and including PVC heavy duty casing and capping with PVC coated copper earth conductor 6 Sq.mm one run complete. Note: 2 run of 6 Sq.mm cable one run 6 Sq.mm PVC insulated cable copper multistranded conductor alongwith PVC cassing capping will be measured as one unit.
Taking down old existing sub main wiring and M&L for sub main wiring with 4 run single core 6 Sq.mm PVC insulated unsheathed copper multistranded conductor 1100 Volts grade drawing into and including PVC heavy duty casing and capping with PVC coated copper earth conductor 6 Sq.mm two run complete. Note: 4 run of 6 Sq.mm cable 2 run 6 Sq.mm PVC insulated cable copper multistranded conductor alongwith PVC cassing capping will be measured as one unit.
M&L for casing and capping min 25 mm wide, double lock type in repairs by using existing wiring, for light point, fan point, bell point, PVC boards, good finishing for including screws, bolts nuts, drilling etc.
S&F in repairs aluminium strip 25x3.15 mm complete with insulators and fixing materials for fitting the strip including testing on completion complete all as directed.
S&F in repairs GI strip 32x6 mm complete buried in ground / wall including testing on completion complete all as directed.
M&L for earthing complete with galvanized steel earth plate as electrode 600x600x6 mm buried directly in ground vertically to a depth not less than 2.25 m below ground level with top edge of earth plate at a depth not less than 1.5 m below ground level connected using galvanized iron earth lead strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of GI earth lead strip protected by Gl light grade pipe 40 mm bore, including provision of concrete pit of PCC 1:2:4, type B1 (using 20 mm graded stone aggregate) with 40 mm thick cover of RCC 1:2:4 reinforced with 8 mm dia TMT bars reinforced at 100 mm C/C both ways and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 2 m long placed on top edge of earth plate, char coal and common salt filling test point made out of 40x8 mm flange with fixing arrangement, funnel, wire mesh and earth work in any type of soil, returning, filling in and removal of surplus soil to a distance not exceeding 50 m all as per electrical Plate No. 3 of SSR Part I and connected to earth test point, including taking down existing earthing complete all as specified including testing on completion.
M&L for earthing complete with galvanized steel earth plate as electrode 600x600x6 mm buried directly in ground vertically to a depth not less than 2.25 m below ground level with top edge of earth plate at a depth not less than 1.5 m below ground level connected using galvanized iron earth lead wire 4 mm dia as earthing lead by means of bolts, nuts, check nuts and washers of GI earth lead wire protected by Gl light grade pipe 15 mm bore, including provision of concrete pit of PCC 1:2:4, type B1 (using 20 mm graded stone aggregate) with 40 mm thick cover of RCC 1:2:4 reinforced with 8 mm dia TMT bars reinforced at 100 mm C/C both ways and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 2 m long placed on top edge of earth plate, char coal and common salt filling test point made out of 40x8 mm flange with fixing arrangement, funnel, wire mesh and earth work in any type of soil, returning, filling in and removal of surplus soil to a distance not exceeding 50 m all as per electrical Plate No. 3 of SSR Part I and connected to earth test point, including taking down existing earthing complete all as specified including testing on completion.
S&F in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and as directed by the Engineer-in-Charge.
S&F PVC rectangular block and laminated sheet cover of size 100 X 100mm and 50mm deep for mounting switches, sockets, fan regulator etc.
S&F PVC rectangular block and laminated sheet cover of size 175 X 100mm and 50mm deep for mounting switches, sockets, fan regulator etc.
S&F PVC rectangular block and laminated sheet cover of size 200 X 150mm and 50mm deep for mounting switches, sockets, fan regulator etc.
S&F in repairs electronic driver suitable for LED security light fittings of 25 to 45 Watt 240V AC rating. Make: Philips/ Osram/ Jaquar/ C&S/ Bajaj/ GE etc
S&F in repairs electronic driver suitable for LED Panel light 2x2ft fittings of 36/ 40W 240V AC ratting. Make: Philips/ Osram/ Jaquar/ C&S/ Bajaj/ GE etc
S&F in repairs electronic driver suitable for LED Panel light 1x4 ft fittings of 42W 240V AC ratting. Make: Philips/ Osram/ Jaquar/ C&S/ Bajaj/ GE etc
M/s Balaji Enterprise
JAYESH TRADING CORPORATION
JAMNAGAR ELECTRIC AND MACHINERY CO
J J ENTERPRISE
M/s. Vimal Enterprise
1R K Traders
M/s Jagdish Machinery Stores
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .