Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 3 5557 A SIVARAM TOWER MATTANNUR 670702 KERALA | KANNUR | KERALA | 670702 | Admitted-Finance |
Tender Value
₹15.7 L
EMD Value
₹36,000
Closing Date
2 Mar 2020, 6:00 pmClosed
DGM Subcontract
KEL Kochi
ELECTRIFICATION OF TALUK HOSPITAL IRITTY
2020_KEL_337554_2
KRO/ BDC/509/2019
Open Tender
Electrical Works
Item Rate
30 days
KEL Kochi
As per NIT
5 documents required · 5 mandatory
₹2,950
online
₹36,000
Yes
7 Mar 2020
18 Feb 2020
4 Mar 2020
18 Feb 2020
2 Mar 2020
18 Feb 2020
18 Feb 2020 - 2 Mar 2020
Amount
SPECIFICATION
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
Single Control light point with 6A, plate ceiling rose (MP)
Single control light point without ceiling rose (MP)
Single Control light point with 6A, plate ceiling rose (LP)
Twin Control light point with 6A, with ceiling rose(MP)
Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator
Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end
Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.
Independent Plug (IP+ WALL FAN)
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.00 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. (Group B )
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. (including MC plug)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/ 6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 4 Nos. 3 pin 5/6 A modular socket outlet and 4 Nos. 5/ 6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
25 A 3 Pin Shuttered Socket
32A DP switch with indicator
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Telephone socket outlet
TV antenna socket outlet
Supplying and fixing following size/ modules, GI/Fibre box alongwith modular base & cover plate for modular switches in recess etc. as required.
3 Module (100 mmX75 mm)
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
3 Module
Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.
Ding dong bell
Supplying and fixing PVC batten Straight/angle holder including connections etc. as required.
supply and fixing of 10W LED lamp in existing batten holder (Havellsadore B22 cool day light LHLDERUEML8X010 or equivalent make, philips, osram, syska).
Supply, conveyance, installation, testing and commissioning of surface mounting 19W Round/Square Panel Light (Osram,Philips, Havells or similiar make) of all types directly on the ceiling including giving connections with required 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring etc as required
Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required
1x28wT5/LED fitting with APF electronic ballast suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, high lumen tube .
Surface mounting Decorative flourescent tube fitting (cat-2) suitable for 2x28wT5 fitting with APF electronic ballast suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, high lumen tube .
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
40 mm dia with clamps made from 20 x 3 mm MS flat
Supply and fixing Panasonic bloom 45 Watts Led Street Light PSTM16458 or any other equivalent make and giving connections as required.
Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.
1200mm sweep -5star rated ceiling fan complete with 300mm down rod , canopies, shackeles and blades and resistance type regulator working on 230V/240V single phase A/C
Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
Supply,of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS.
300/ 305 mm, single phase light duty exhaust fan in metal frame havells ventililair TSP 300mm sweep FHDDEMTDBS12) or equivalent make of crompton, almonard
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and clamping following size of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required.
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.
1.50 sq.mm 3 Run ( for CP,IP )
2.50 sq.mm 2 Run+1.50 sq.mm 1 Run (for PP )
4.00 sq.mm 2 Run + 2.50 sq.mm 1 Run (for A/C & 1ф DB)
Supply and drawing of ISI marked 2 pair telephone cable with size 0.51mm ATC copper conductor through the fixed PVC conduit.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
3.5 core 50 sq mm with factory made clamp
4 core 16 sq mm with factory made clamp
4 core 25 sq mm with factory made clamp
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 1/2 X 50 sq. mm (35mm)
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
8 way (8+24) - three phase double cover (IP 42/43)
6 way (8+18) - three phase double cover (IP 42/43)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
16 way, Double door (UPS, COMMON)
16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 amps 100mA RCCB
40 amps 100mA RCCB
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
25 amps 2P RCCB
Supply and fixing 40A 2pole MC COS in Existing Enclosure and giving connection etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole (6-32A)
Triple Pole (40A)
Triple Pole (63A)
EARTHING
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 3 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and laying 25 mm X 3 mm copper strip including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 3.15 mm dia (10 SWG) copper wire on surface or in recess for loop earthing as required. (includes generaotr)
Supply conveyance, installation testing and commissioning of 1 phase 240V 1 Ton Inverter type split A/C unit of LG or any other equivalent make with R22or 410 equivalent gass and both indoor and out door units with copper ducts including clading, on wall /sun shade /parapet as per site condition including cartage and labour charges.
Supply conveyance, installation testing and commissioning of 1 phase 240V 1.5 Ton Inverter type split A/C unit of LG or any other equivalent make with R22or 410 equivalent gass and both indoor and out door units with copper ducts including clading, on wall /sun shade /parapet as per site condition including cartage and labour charges.
Supply conveyance, installation testing and commissioning of 4 KVA 1 phase 130/250V wide range voltage stabiliser of V-guard or any othe equivalent make suitable for 1.5T split A/C unit, on wall /floor/ as per site condition.
Supply conveyance and installing of GI bracket suitable for 1.5 Ton split A/C out door unit
Supply and providing copper duct for extending connection from 1.5 Ton A/C outdoor unit to Room Unit including , providing cladding and connection lead wire as per site requirement
STATUTORY APPROVALS,DRAWING PREPERATION ETC
Note :1 All materials, Items, Equipment shall be best branded items with IS and approved by client/KEL
2:Rate should be inclusive of Insurance,Transportation, delivery and installation cost for all items
3.Rate should be Exclusive of GST.
4.Work should be executed as per DSR/PWD specification and direction of Engineer at site.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .