SE ETC II MORADABAD
220 KV MAJHOLA COMPUS MORADABAD
WORK FOR THE EXTENSION OF 132 KV SUBSTATION BACHRAUN FOR THE ERECTION OF 132 KV BUS COUPLER BAY AND 2X10 MVAR CAPACITOR BANK UNDER ETD AMROHA.
2022_UPTCL_731751_1
E-T-56/ETC-II/M/2022
Open Tender
Electrical Works
90 days
AMROHA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
EE ETD AMROHA, SBI CURRENT ACCOUNT NO.30723557626
₹18,000
1 Dec 2022
26 Sept 2022
17 Oct 2022
26 Sept 2022
17 Oct 2022
26 Sept 2022
Amount
WORK FOR THE EXTENSION OF 132 KV SUBSTATION BACHRAUN FOR THE ERECTION OF 132 KV BUS COUPLER BAY AND 2X10 MVAr CAPACITOR BANK UNDER ETD AMROHA.
SUPPLY
1) HARDWARES AS PER SPECIFICATIONS
Tension fittings for Twin Moose conductor
Tension Fittings for Single panther conductor
Suspension Fittings for Twin Moose conductor
PG Clamp suitable for Moose- Moose conductor
PG Clamp suitable for Moose-Panther conductor
PG Clamp suitable for Panther- Panther conductor
33 KV CT Clamp suitable for Single Panther conductor (As per sample of rod dia)
33 KV Isolator Clamp Single panther Conductor (As per sample)
132 KV Isolator Clamp Twin panther Conductor (As per sample)
132 KV Isolator Clamp Single panther Conductor (As per sample)
33 KV Section Isolator Clamp Twin moose Conductor (As per sample)
Spacer 250 mm suitable for Moose conductor Conductor (As per sample)
Spacer 100 mm suitable for Panther conductor Conductor (As per sample)
36 KV Bus Post Insulator
Bus post Clamp suitable for Twin Panther Conductor (As per sample)
Bus post Clamp suitable for Single Panther Conductor (As per sample)
Perforated Tray for supporting control cables of below sizes
Bay marshlling Kiosk for switchyard
1) 132 KV Section
Erection of main and aux. structure
Erection of 145 KV CB with structure
Erection of 145 KV BI with its operating mechanism
Stringing of Twin Moose condutor of 132 KV (Extension) bus bar per phase (12 Mtr span)
Interconnection of jumpers of complete 132 KV Bay
Erection of 132 KV bus coupler control panel (SAS based)
Erection of 132 KV bus coupler protection panel (SAS based )
Erection of Bay marshlling Kiosk for switchyard
2) 33 KV Section
Erection of main and aux. structure
Stringing of Twin Moose condutor of 33 KV Extension bus bar per phase (12 Mtr span)
Erection of 33 KV Bus section Isolator
Complete erection of 1x10 MVAr Cap. Bank including strining of bus bar, interconnection of jumpers, erection of VCBs, Isolators, CTs, NCTs, Series reactors, control panel etc. complete in all respect as per site requirement with all cost of men T&P, consumables etc. required for work.
3) Earthing Work
Fabrication of 3 Mtr long electrod with 40 mm dia MS round bar having 150mm long conical shape by cutting, straightening etc. then piercing it vertically inside the ground 700 mm below the ground level.
Laying of earthmat (40 mm dia MS round bar) 700 mm below the ground level after excavation by cutting straightening, welding etc.
Making of 150mm long lap joint of above laid 40 mm dia round bar by cutting, straightening, welding etc. on both side of the leg joint.
Making of 150mm long lap joint of above laid 40 mm dia round bar to connect with existing earthmat of the substation by cutting, straightening, welding etc. on both side of the leg joint.
Making of cross joint of above laid 40 mm dia MS round bar, 700 mm below the ground level by welding at all 04 corners including providing and welding of suitable size 02 Nos MS Angle Pieces on opposit corners of cross joint
Making of end joint of above laid 40 mm dia MS round bar with top of the already vertically pierced MS elctrodes, 700 mm below the ground level by welding.
Cutting, Straightening, bending, laying 700 mm below the ground and above the ground of MS Flat for the earthing of all equipments
4) Painting of MS Flat
5) Cabling work
Complete cabling work (laying, termination etc.) of different newly erected 132 KV and 33 KV equipments
a) Laying of 2X2.5 Sq.mm
b) Laying of 4X2.5 Sq.mm
c) Laying of 6X2.5 Sq.mm
d) Termination of 2X2.5 Sq.mm
e) Termination of 4X2.5 Sq.mm
f) Termination of 6X2.5 Sq.mm
Fixing of perforated cable tray of various size
Modification of structure parts for various 132 and 33 KV structures of different equipments, columns, beams, peaks and mast' as per site requirement after cutting in size, drilling of 12/16/20 mm dia holes, painting as required as per strict supervision it may be treated as 02 sections for 132 KV & 33 KV sites including carriage of diverted material upto 250 Km range.
NAVEEN AND COMPANY
TIRUPATI ELECTRICALS
A.RAMAN POWER ENGINEERS
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid