Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC FLAT NO 304 SN TOWERS JAGANNADHAPURAM JUNCTION AKKAYYAPALEM VISAKHAPATNAM 530 016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | L1 | Accepted-AOC Tender awarded to Ms Murali krishna Associates enlisted Index No A 154 CE EC on 29 Feb 2020 being lowest tenderer and rates are found reasonable | |
| 2 | L2₹11.0 L+₹1.7 L (18.7%)Rejected-Finance 50 1 56 13 SURYA TOWERS ASR NAGAR SEETHAMMADHARA VISAKHAPATNAM 530 013 | VISAKHAPATANAM | ANDHRA PRADESH | 530013 | L2 | Rejected-Finance Being other than the Lowest tenderer | |
| 3 | L3₹11.7 L+₹2.4 L (26.2%)Rejected-Finance D NO 38 22 40 NEAR LAKSHMI NARASHIMA THEATER 104 AREA VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | L3 | Rejected-Finance Being other than the Lowest tenderer | |
| 4 | L4₹18.0 L+₹8.8 L (94.9%)Rejected-Finance | L4 | Rejected-Finance Being other than the Lowest tenderer | |
| 5 | Rejected-Technical | - | Rejected-Technical Performance is not satisfactory in CWE contract Provn of solar lighting under GE Chilka |
Tender Value
₹14.3 L
EMD Value
₹28,600
Closing Date
28 Jan 2020, 6:00 pmClosed
Commander Works Engineer 2 Visakhapatnam
Commander Works Engineer 2 ,Chief Engineer Navy Visakhapatnam Complex, Station Road, Visakhapatnam, 530004
ADDITION AND ALTERATION TO FIRE ALARM SYSTEM AT INS KALINGA BHEEMUNIPATNAM
2019_MES_306851_1
82432
Open Tender
Miscellaneous Works
Item Rate
180 days
GE Kalinga
Class E Cat c vi
6 documents required · 6 mandatory
₹500
Yes
GE kalinga
₹28,600
Yes
2 Mar 2020
16 Dec 2019
30 Jan 2020
16 Dec 2019
28 Jan 2020
6 Jan 2020
16 Dec 2019 - 21 Dec 2019
Amount
Supply, Installation, Testing and commissioning of CT Control Addressable Panel Single loop capacity with option of expandable up to four loops and consist one loop card of analogue addressable as per UL 864 9th Edition NFPA 72 & NABL with swich mode power supply battery back up and charger with all accessories comprise the following specifications,complete all as per manufacturers instructions and as directed by Eng-in-charge. (i) Each loop card have maximum capacity 254 analogue addressable field cevices in any combination of detectors/modules.
(ii)The panel shall consisting with 160 charactor LCD display and touch key controls not less than 32 bit process with the storage capacity of minimum 2000 events log on th system with real time clock,up to 192 group facility,pre alarm action and 1000 received events for fire, automatic device type verification. (iii) The loop cards with class A or B wiring shall supports 20 Nos of sensors without any add on cards. (iv) It shall be peer to peer net workable by on board RS- 485 to connect minimum of 8 panels. (v) TCP/IP and shall support 16256 decices in any combination and shall be compactable with touch screen. (vi) Master Control Unit for remote controlling and monitoring of the entire system through LAN & WAN,USB 2.0 for PC inrterface. (vii) Degraded redundency operating mode when the main CPU fails, operating power 110 to 220 VAC +10% -15%,50/60 HZ,3 Amps. (viii) All panel configuration shall be front panel programmable, programming software and programming hand held device shall not be allowed to confguration to the panel.
(ix) The configuration software shall be supplied along with the panel and it doesn't required any special key for the usage of the configuration software. (x) It shall be an option to connect thermal printer, Mod bus converters. (xi) It shall be UL listed and STQC tested along with supply of Plug in card with soft addressing facility according to the slot which shall be able to integrate with the field devices to the main control system. (xii) It shall be able to monitor any field faults and system shall be working with 100% redundancy of single open in the field cabiling circult. (xiii) It shall be an display on the board to show the Healthness of the system/fire on the system / Standalone performance of the system. (xiv) It shall be UL listed and ETDC approved with 2 Nos batteries of capacity 12 V, 7 AH. Make : Ravel Electronics Pvt Ltd/Honey well/ Morley/ Edward/Safex.
Supply,Installation,testing & commissioning of Addressable panels (Notifier) of 1 SLC,318 intelligent points (159 detectors/159 modules),4 on board NACs,networkable(Notifier-net,standard or high speed),80 character LCD display QWERTY key pad,BACNET/IP and MODBUS/IP compactable easy to use and maintain ON YX series panels feature full QWERTY key pads,large 80-640 character LCD displays and intuitive menu options,making it easy for facility managers to perform routine system maintenance,testing and basic programming functions such as enabling or disabling points and if an intelligent device is ever damaged and needs replacement facility personnel can do so quickly and easily without the need for specially tools or programming soft ware complete all as manufacturers instructions and as directed by Eng-in-charge. Make : Ravel Electronics Pvt Ltd/Honey well/ Morley/ Edward/Safex.
Supply, laying, testing, saddling and glanding termination of 2 core ,2.50 sqmm twisted pair armoured cable copper conductor, including removing unserviceable old cable complete all as specified and as directed. Make: Polycab /Havells/ Gloster/Finolex/Asian (RPG)/KEI industries Ltd
Supply, laying, testing, saddling and glanding termination of 12 core ,2.50 sqmm twisted pair armoured cable copper conductor, including removing unserviceable old cable complete all as specified and as directed. Make: Polycab /Havells/ Gloster/Finolex/Asian (RPG)/KEI industries Ltd
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth, for laying of cable etc and getting out in soft /loose soil complete all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm in any type of soil complete all as specified.
Removing excavated material to a distance not exc 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified.
M & L for natural river sand as cushioning of cables, including spreading and punning down complete all as specified and directed by Engineer in charge. Note : punned thickness (minimum 18 cm) shall be measured for the purpose of payment
Supply and laying of common burnt clay building bricks sub class A of size 230x115x75mm best locally available as in cable protection laid in trenches complete all as specified and directed.
M&L GI Pipe 40 mm bore ( light grade) with all fittings laid as in cable protection,complete all as specified.
M&L Boring of holes below ground level in any strata i.e road/pavement/hard standing by means of trenchless technology using ultra sound technique with nececessary machine including 50 mm dia HDPE pipe suitable for 0.40 Mpa working pressure,complete all as directed by Eng-in-charge.
SAI KRISHNA ASSOCIATES
AYYAPPA CONSTRUCTIONS
Continental Engineers and contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .