Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC HARIBHAVAN NORTH ARIYAD P O ALAPPUZHA | L1 | Accepted-AOC L1 Agreement Executed | |
| 2 | L2₹7.6 L+₹5,130.54 (0.68%)Rejected-AOC LSGD DIVISION ALAPPUZHA | L2 | Rejected-AOC L2 |
Tender Value
₹7.6 L
EMD Value
₹18,988
Closing Date
4 Mar 2024, 3:00 pmClosed
Assistant Executive Engineer
PWD Electrical Sub Division, Alappuzha
Supply and installation of Diesel generator and UPS in SI MET Nursing college Nooranad
2024_PWD_663538_1
PWD/BLDG/TR/2606
Open Tender
Electrical Works
Item Rate
Noornad
Please refer Tender documents.
12 documents required · 12 mandatory
₹1,675
₹18,988
4 May 2024
24 Feb 2024
6 Mar 2024
24 Feb 2024
4 Mar 2024
24 Feb 2024
Amount
SITC of DG Set
OD235575/2023-2024:SITC of 20 kVA Diesel Generator set complete with integral acoustic enclosure as per existing CPCB norms as per present norms and as per technical details given below 1. Engine a) Make of Engine - Cummins/ Kirlosker b) Type of Engine - Diesel Engine c) No. of Cylinders- As per Std. d) Method of Cooling – Liquid cooled with radiator. e) Aspiration -Turbo charged after cooled. f) Design - Suitable for generating set operating. g) Output- As per manufactures standards. 2. Standard accessories with Diesel Engine. a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Electronic governor g) Fuel filter h) Exhaust silencer i) Exhaust Muffler j) Lubricating oil filter. k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button. b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter. e) Battery charging Ammeter. 4. Safety Controls for Engine. a) Trip for low lubricating oil pressure. b) Trip for high water temperature. 5.Fuel pipe: Oil resistance flexible hoses of 20mm dia or nearest size MS pipe as per manufacturer's standard, 6 Brush less Alternator a) Make - Stamford/Kirlosker b) Type - Self exited and self-regulated, brush less c) Capacity – 20kVA/ 16 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, 4 wire system. e) Speed - 1500 rpm f) Voltage regulation band - +/-2.5% of rated voltage g) Frequency - 50 Hz h) Insulation - Class -F/H .The Alternator should confirm to IS 4722. Operation and service manual shall be provided. . 7.Fuel Tank Suitable size built in type integrated with the acoustic enclosure. Fuel connection shall be done as per standards.7. Battery. Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 8. Separate external source 230V AC automatic Battery charger. 9. Push button switch for ON/OFF - 1 set. Metallic DNB - 1No Solid state phase indication lamp for supply ON/OFF with MCB protection , The standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 32A or nearest size 4Pole MCB , b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, KVA, PF, voltage, Current Frequency etc: c) Digital type single function KWH meter with accuracy class 1, d) Provision for connecting ATS/AMF for auto manual operation, 10. filling 75% fuel (Diesel) including for conducting test run at site 10.Exhaust Piping Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminum paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) including conducting load testing at site/assembling unit in the presents of department staff.
90.17.7.4:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD235585/2023-2024:Supply and fixing 2 x 25mm X 3 mm copper strip test joint for the earthing system.
OD235587/2023-2024:Supply and providing 25x6mm brass bolt
OD235586/2023-2024:Supply and providing 25x3mm brass bolt
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm
90.6.5.19:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 2.50 sq mm
90.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
OD236102/2023-2024:Supply and providing 63A or nearest size 4P automatic transfer switch with sheet steel enclosure including controller with all auxiliary components for DG auto start/stop operation if required and giving all connection from controller to ATS and DG set, KSEB mains etc as required (Make - Havells, L&T, HPL and Socomec)
90.11.1.18:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
OD239051/2023-2024:Supplying and fixing 40 amps to 63 amps rating, 415 volts, "C" curve, 10KA, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
OD236158/2023-2024:Re-glanding and re-fitting the existing cable from Load bank DB to Proposed MCCB VDB
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.7:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 1.5 sq. mm
90.6.4.53:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 3 Run
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.2.3:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface
90.9.2.14:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.8 module mounting box
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.10.3.23:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )16A 3 pin plug top
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
OD236192/2023-2024:Supply and installation of 3.5KVA/48V Luminous make or equivalent UPS with 4nos of 150AH batteries with 36 months warranty including battery connecting wires and give connections to existing UPS wiring etc as required (model Luminous I cruze + & LUM12V 150AH RC 1800)
OD235592/2023-2024:Painting letters or figures of the 2.5 cm, 4 cm or 5 cm height sizes with enamel paint as identification mark to SB, DB, Panel board as required.
7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
OD239055/2023-2024:Charges for preparation of Electrical Drawing per A2 sheet first copy (HT installation hence for Additional/Alteration approval)
OD239054/2023-2024:Copying charges for additional copies per A2 sheet
OD235593/2023-2024:Charges for submitting the completion report to Electrical inspectorate and arranging the inspection form the electrical inspectorate
OD235594/2023-2024:Electrical Inspectorate Charge for availing DG set sanction order including submitting completion report (Actual amount will be reimbursed on production of receipts)
Civil items
50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
OD236848/2023-2024:Providing Aluminium traffold roofing sheet 0.40mm thick including vertical/ curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, ( up to any pitch in horizontal / vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.( based on 12.1.1)
PHILIPOSE JOSEPH
Bidder Name
HARISH AND CO
PHILIPOSE JOSEPH
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1029170.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .