COMPLETION OF INCOMPLETE WORKS FOR PROVN OF AIR CONDITIONING FOR TECHNICAL BUILDINGS AT AF STN HALWARA (TENDER-I)
2022_MES_504917_1
CEWAC/HAL/T-32/2021-22
Open Tender
Civil Works
Item Rate
210 days
GE (P) (AF) HALWARA
AS PER NIT AND TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE (P) (AF) HALWARA
₹1.5 L
Yes
25 Jul 2022
2 Feb 2022
26 May 2022
2 Feb 2022
18 May 2022
12 May 2022
Amount
CHILLER PLANT: Testing and commissioning of water cooled DX/Flooded type Chiller Packages with Single/double circuit 3 x 100 TR( Dedicated type Parallel Chillers with 2 No working at a time and 1 No standby). Each unit shall consist of Screw Chiller with hermetic / Semihermetic compressor (twin screw compressors) suitable for R134a Refrigerant, with Slider valve mechanism for stepless un loading,Shell and tube water cooled Condenser, Insulated Shell and tube Evaporator, Micro Processor Plant Manager all as supplied by OEM as part of Chiller Package. (The item has been supplied and installed under original work of Make VOLTAS Model No.ACEEWFXR1001MLB2) Note:- The quoated rates include making the item in Serviceable/Functional condition.
Scope of Supply : The Unit mounted starter panel with double door construction shall be single Power point type complete with IP 55 Degree of protection, consisting of Power disconnecting Switches with fuses/MCCBs, Fully automatic Star Delta starters for Motors and condenser Fan Motors complete with Under/Over voltage and phase reversal protection, Single Phase Preventers, communication card which can accept 4-20 mA or 2-10 V dc analog signal.( 2 No Chiller unit working at a time and 1 No standby)
Each unit shall be complete with Discharge Service valves to isolate refrigeration circuits, vibration Isolators to isolate chiller from building structure, pressure gauges Electronic expansion valves, solenoid valves, anti-freeze thermostats, refrigerant piping with Insulation for suction line, accessories of Safety valve, angle valve, liquid line indicator, water flow switch, Relief valve, Isolating valves and including MS stand to install the chiller units fabricated out of suitable size of structural steel sections etc. all as per OEM. All accessories housed in a single chasis design. The noise level measured at a distance of 1 Mtr from the machine at anywhere in the plant room shall not exeed 75 dBA.
Technical Parameters : The chilled water type AC plant will be suitable for operation on 3 phase AC 50Hz supply of capacity. The Compressor shall have step less control from 100 to 25% of rated capacity. The unit shall conform to ECBC norms as under:- (a) Minimum COP=4.7 (b) Minimum IPLV=5.49 where COP=3.516/(KW/TR); The IPLV shall be calculated as per AHRI 550/590-latest edition. The unit shall be factory tested as per AHRI standard 550/590 latest edition. Mode Auto/Manual . Protection: Single phasing , phase reversal, under/over voltage, compressor restart after 10 second, Antifreeze, display on micro controlling unit, entering/ leaving water temp, alarm/ alarm reset, compressor ON, Crank case heater ON/OFF.
Design parameters/Specifications: The specifications for Condenser and Chiller are as under:- Condenser: water in 29.44 Deg C water out 35 Deg C Fouling factor 0.000044(m²-deg C)/Watt). Chiller: CHW in 12.22 Deg C CHW out 6.7 Deg C Fouling factor 0.000018(m²-deg C)/Watt)
Testing, commissioining & Providing insulation for Centrifugal end suction back pull out, vertically split casing pumping set for condenser water circulation system.The pump shall be suitable for the given duty points - 3 Nos. Out of Three pumps, Two will be working and one will be stand by. The Pumps are dedicated type, one pump for each Chiller Unit). Motor is energy efficient motor conforming to IS 12615. (i) Water Quantity- 800 US GPM(181.44 M³/Hr) (Each pump to handle 400 US GPM), (ii) Static Head - 20 to 25 M, (iii) Speed - 1450 RPM (iv) Impeller - Bronze, (v) Shaft - High Tensile steel , (vi) Pump/motor body- CI (vii) Seal - Mechanical, (viii) Motor - Suitable HP, Sqirrel, Cage SPDP,Class 'B' Insulation, (ix) Starter - Fully automatic Star-Delta, (x) Base frame - Fabricated MS (xi) Foundation - RCC/PCC Foundation as per OEM Recommendations. Note:The pumps should be provided with Anti Vibration Pads and RCC/Cement concrete Foundation. Rubber bellows shall be provided on suction and discharge sides for vibration isolation. 2 Nos 100 mm dia dial type pressure gauges for inlet/outlet shall also be provided. The cost quoted by the contractor includes all above. (The item has been supplied and installed under original work of Make: KIRLOSKAR, Model No: K2219A1056/10) Note:- The quoated rates include making the item in Serviceable/Functional condition.
Testing, commissioining & Providing insulation for 3 Nos Pumps for Chillers, dedicated pump sets for each Chiller duly insulated with expanded polystyrene(TF Quality) insulation 50 mm thick duly cladded between aluminium sheets of 0.5 mm thickness and properly clamped to pump in 2 semi circular sections. Pump motor is energy efficient motor confirming to IS 12615. (i) Water Quantity-480 US GPM (108.86 M³/Hr) (Each pump to handle 240 US GPM of chilled water) (ii) Static Head - 30 to 35 M Other Parameters same as per Condenser Pump Note for Items 1.06 & 1.07 :(i) The Contractor shall provide calculations for Head of the Pump after acceptance of Tender (ii) In case of deviation of Head (more than 5m) financial adjustment will be made through a deviation order (The item has been supplied and installed under original work of Make: KIRLOSKAR, Model No: K2219A1056/10, Pump Type: DB 50/16) Note:- The quoated rates include making the item in Serviceable/Functional condition.
Testing and commissioining of Modular FRP cooling tower of 3 Cells, Each Cell of suitable heat rejection capacity (compatible with A/C load of 108 TR) with FRP water basin PVC fills, water distribution arrangement with self rotating sprinklers or fixed nozzles of PVC construction, statically and dynamically balanced axial flow fan direct driven, TEFC motor, suction screen, make-up and quick fill arrangement, overflow and drain connections, suitable GI inspection ladder, steel supporting structure, antivibration mounting etc, complete as per manufacturer's design/specifications - (Out of Three cells, Two will be working at a time and one will be stand by. The Cells are dedicated type, one Tower Cell for each Chiller Unit) Operating Parameter (i) Capacity - 3 x100 TR(100 TR per Cell) (ii) Water Flow- 400 US GPM(90.72 M³/Hr) per Cell (iii) Water in - 35° C (iv) Water out - 29.44° C (v) Design wet bulb temp - 28.33° C (vi) Min approach for Cooling Tower - 2.5°C Cooling tower shall confirm to NFPA 214 and it should meet criteria laid down by ASHRAE Standard 90.1-2004 .Note: The Capacity 100 TR per Cell shown is nominal capacity of Refrigeration.The Cooling Tower shall be suitable for Refrigeration capacity plus heat of compression which is 25 % (appx) of refrigeration capacity. The highest WBT is for monsoon(28.33°C) and Condenser piping is designed for 15.133 LPM/TR. The Cooling tower shall meet the load in both summer and monsoon. The Cooling Tower shall be complete with (a) Automatic Isolating Valves (Motorised Butter Fly Valves (150 MM) with flexible flanges at inlet and outlet of each Cell. (b) Over flow and equivalising line (c) Butter Fly Valve for make up water Connection including teflon tape to the threads (d) Standard Sump screen and additional fine mesh construction start up screen (e) Foundation with Staging to ensure positive head at Pump inlet The rate quoted for above Cooling Tower package includes for all the above (The item has been supplied and installed under original work of Make: DELTA, Model No: DFC-60) Note:- The quoated rates include making the item in Serviceable/Functional condition.
S&F Automatic Isolating Valves (Motorised Butter Fly Valves (150 MM) with flexible flanges at inlet and outlet of each Cell against Note (a) of Srl item No.1.08 above for checking of Over flow and equivalising line & for make up water Connection complete all as specified and directed.
CHILLED WATER PIPING, VALVES & FITTINGS: (UNDERGROUND PIPE) Supply, laying, fixing, testing and commissioning of chilled water piping Plumbing inside trenches with all necessary fabricated fittings such as bends, tees, reducers etc, and supports such as clamps, anti vibration hangars/pads etc( but excluding valves,valves/strainers/pr gauges etc) duly insulated with pipe sections of Fire retardent quality expanded polystyrene moulded pipe section of density 36 Kg per cum conforming to IS 12436 and thickness 50 mm upto 125 mm pipe and 75 mm thick for pipes 150 mm and above. The insulation applied after a thick coat of cold setting adhesive(CRPX compound) will be wrapped with 500 gm/sqm polythene faced hessian cloth sheet (vapour barrier seal) (Fire retardent grade) and secured with 0.5 mm x 20 mm GI wire mesh and 2 coats of cement plaster (1:4) 20 mm thick in 2 layers(each layer of 10 mm) and water proofed by applying hot bitumen and fixing tar felt over the plaster. It shall then be finally finished with a coat of hot bitumen. The work includes digging and refilling of trenches and providing 500 mm thick 1:2:4 cement mortar pads at 3 M interval.The pipes are required for installing outside the Building burried in ground. The size of pipes shall be as shown below:-
(a) 150 mm Pipe (75 mm thick insulation)
All as per Srl item No.1.11 above but only providing of 75mm thick insulation over 150mm bore pipe complete all as specified and directed. (The item has been supplied & installed under original work) Note:- The quoated rates include making the item in Serviceable/Functional condition.
All as per Srl item No.1.12 above but for 100mm bore Pipe & 50 mm thickness of insulation complete all as specified and directed. (The item has been supplied & installed under original work) Note:- The quoated rates include making the item in Serviceable/Functional condition.
CHILLED WATER PIPING EXPOSED OUT SIDE BUILDING Supply, laying, fixing, testing and commissioning of chilled water piping outside the building all along the wall/roof (with necessary fittings, clamps and vibration isolators but excluding valves/strainers/pr gauges) adequately supported on rigid supports and duly insulated with pipe sections of Fire retardent quality expanded polystyrene moulded pipe section of density 36 Kg per cum and thickness 50mm, applied after a thick coat of cold setting adhesive(CRPX compound) wrapping with a layer of 120 gm/sqm polythene faced hessian cloth sheet (vapour barrier seal) (Fire retardent grade) and secured with 0.63 mm GI sheet cladding complete with type 3 , grade 1 roofing felt strip (as per IS:1322) at the joints and repairing of damage to the buildings if any etc as per specifications and as required complete in all respects. The size of pipes shall be as shown below:-
(a) 100 mm Pipe(50 mm thick insulation)
All as per Srl item No.1.15 above but only providing of 50 mm thick insulaton to 100mm dia exposed chilled water piping complete all as specified and directed. (The item has been supplied & installed under original work) Note:- The quoated rates include making the item in Serviceable/Functional condition.
CHILLED WATER PIPING EXPOSED BUT INSIDE BUILDING Supply, laying, fixing, testing and commissioning chilled water piping inside the building (with necessary clamps, vibration isolators and fittings, but excluding valves/strainers/pr gauges etc) adequately supported on rigid supports and duly insulated with closed cell elastometric nitrile rubber of class 'O' insulation and insulation applied by adhesive confirming to standard OEM specifications secured with 0.511mm Aluminium sheet cladding complete with type 3, grade 1 roofing felt strip (as per IS:1322) at the joints and repairing of damage to the buildings if any etc as per specifications and as required complete in all respects.The size of pipes and insulation shall be as shown below:- Note: The Pipe of size 150 mm & below shall be M.S heavy class as per IS-1239 and pipe sizes above 150 mm shall be welded black steel pipes heavy class as per IS 3589,from minimum 6.33 mm thick M.S sheet for pipes up to 350 mm dia
(c) 100 mm Pipe(32 mm thick insulation)
(d) 80 mm Pipe(32 mm thick insulation)
All as per Srl item No.1.19 above but only providing of 32 mm thick insulaton to 150mm dia exposed chilled water piping complete all as specified and directed. (The item has been supplied & installed under original work)
All as per Srl item No.1.20 above but for 125mm dia of chilled water piping complete all as specified and directed. (The item has been supplied & installed under original work)
All as per Srl item No.1.20 above but for 80mm dia of chilled water piping complete all as specified and directed. (The item has been supplied & installed under original work)
All as per Srl item No.1.20 above but for 65mm dia of chilled water piping complete all as specified and directed. (The item has been supplied & installed under original work)
Laying, fixing, testing and commissioning 80mm bore chilled water piping inside the building (with necessary clamps, vibration isolators and fittings, but excluding valves/strainers/pr gauges etc) adequately supported on rigid supports and duly insulated with closed cell elastometric nitrile rubber of class 'O' insulation and insulation applied by adhesive confirming to standard OEM specifications secured with 0.511mm Aluminium sheet cladding complete with type 3, grade 1 roofing felt strip (as per IS:1322) at the joints and repairing of damage to the buildings if any etc as per specifications and as required complete in all respects.The size of pipes and insulation shall be as shown below:- Note: The Pipe of size 150 mm & below shall be M.S heavy class as per IS-1239 and pipe sizes above 150 mm shall be welded black steel pipes heavy class as per IS 3589,from minimum 6.33 mm thick M.S sheet for pipes up to 350 mm dia. (Pipe shall be issued free for fixing under Sch-B) Note:- The quoated rates include making the item in Serviceable/Functional condition.
Supply, fixing, testing and commissioning in position the following valves, strainers etc, in chilled water line complete with flanges etc, and duly insulated with uniformly cut pieces from slabs of expanded polysterene, covered with 500 gm/sqmtr polythene faced hessian cloth sheet (vapour barrier seal) (Fire retardent grade) with 50mm overlap and 26 G Aluminium cladding. Care shall be taken to ensure that no damage would be caused to the insulation when valves, stariners are in operation. The Valves shall be as under:-
(a) Butter Fly Valves (Manual) with CI body, Stainless steel disc, nitrile rubber seal & O ring, PN 1.6 Pressure rating for chilled water circulation
(aa)150 mm dia (75 mm Insulation)
(ab) -do- but 100 mm (50 mm insulation)
(ac) -do- but 80 mm (50 mm insulation)
All as per Srl item No.1.29 above but only for providing 50mm thick insulation to 125mm bore Manual Butter Fly Valve complete all as specified and directed. (The item has been supplied & installed under original work) Note:- The quoated rates include making the item in Serviceable/Functional condition.
Fixing, testing and commissioning in position 80mm bore (Manual) Butter Fly valve in chilled water line complete with flanges etc, and duly insulated with uniformly cut pieces from slabs of expanded polysterene, covered with 500 gm/sqmtr polythene faced hessian cloth sheet (vapour barrier seal) (Fire retardent grade) with 50mm overlap and 26 G Aluminium cladding. Care shall be taken to ensure that no damage would be caused to the insulation when valves, stariners are in operation complete all as specified and directed. (Valve shall be issued free for fixing under Sch-B)
All as per Srl item No.1.31 above but 65mm bore (Manual) Butter Fly valve complete all as specified and directed. (Valve shall be issued free for fixing under Sch-B)
(b) Motorised Butter Fly Valve (NC) with all the features as per Item (a)(aa) above, 100 mm dia (75 mm Insulation) but including Motor and electric connections.
(c) Non return valve with dual plate of CI body, Stainless steel plates, vulcanised NBR seal flanged ends and PN 1.6 Pressure rating for chilled water circulation, 100 mm dia(50 mm Insulation)
(d) Y type Strainer (40 mesh) of ductile Iron body flanged ends with stainless steel strainer
(aa) 100 mm (50 mm insulation)
(ab) -do- but 80 mm (50 mm insulation)
(ac) -do- but 65 mm (50 mm insulation)
All as per Srl item No.1.38 above but for only providing 50mm thick insulation to 125mm bore Y-Type stainer (40 mesh) of ductile iron with uniformly cut pieces from slabs of expanded polysterene, covered with 500 gm/sqmtr polythene faced hessian cloth sheet (vapour barrier seal) (Fire retardent grade) with 50mm overlap and 26 G Aluminium cladding. Care shall be taken to ensure that no damage would be caused to the insulationcomplete all as specified and directed. (The item has been supplied & installed under original work) Note:- The quoated rates include making the item in Serviceable/Functional condition.
(e) 3 Way Mixing Valve: Supply, Install, test & commissioning of 3 Way modulating proportional linear type motorised mixing valve having manual over ride facility with proportional thermostat and wiring with 1.5 sq mm copper conductor multi core armoured cable, 3 way valve size suitable for following GPM including actuator of suitable size complete with transformer etc . Note:Proportional thermostat is included in AHU. The rates quoted by the contractor is for 3 way valve and actuator
(aa) suitable for 100 US GPM
(ab) suitable for 91 US GPM
(ac) suitable for 87 US GPM
(ad) suitable for 82 US GPM
(ae) suitable for 67 US GPM
(af) suitable for 51 US GPM
(f) Automatic Balance Valve Wafer type to limit the flow through 3 way valve, GPM for the valve factory set to automatically limit the rate of flow with in +/- 5% of specified GPM over 95% of control range. The automatic balance valve shall have 2 Pressure ports to read Pressure difference across the valve.The valve shall operate by means of automatic balancing stainless steel catridges with replaceable orifice plate and internal EPDM diaphragms. The pressure class of valve is PN 1.6, The valve shall be complete as per specifications and as required. The pressure head loss added to the pump head shall not exceed 2.134 M. A pressure and temperature Kit shall be provided with the ability to read differential pressure from 0-5.2 Kg/cm² and temperature from 0 to 20 deg centigrade. The valve shall be suitable for flange connection for following GPMs. Note: Slight variation in specifications from one make to another is acceptable
(aa) suitable for 100 US GPM (with Pr & Temp kit)
(ab) suitable for 91 US GPM (with out Pr & Temp kit)
(ac) suitable for 87 US GPM (with out Pr & Temp kit)
(ad) suitable for 82 US GPM (with out Pr & Temp kit)
(ae) suitable for 67 US GPM (with out Pr & Temp kit)
(af) suitable for 51 US GPM (with out Pr & Temp kit)
(g) PRESSURE DIFFERENTIAL SWITCH Supply, installation & testing of water flow pressure differential switches in chilled water line and condensor water line complete as reqd and as specified.
(h) VICTUALIC COUPLING Supply, installation & testing of Victualic coupling for connecting to Chiller and connecting to condensor
PRESSURE GAUGE & PLUG
(j) Supply & installation and testing of bourdon type Pressure Gauges complete with fittings , isolation valve etc. complete as reqd 100 mm dial for chilled water pipe and condensor water pump
(k) Supply & installation of Pressure Gauge plug complete with fittings, isolation valve etc. complete as reqd.(with out pressure gauge)
TEMPERATURE GAUGE
(l) Supply, installation and testing of Thermometer gauge with thermowell complete with fitting etc. as reqd.
(m) Supply & installation and testing of auto air vent valve with ball valve size 25 mm dia
(n) Supply & installation of purging valve complete with fittings viz nipple, elbow, tee, bend, socket etc size 25 mm
(o) Supply & installation of GI 'B' class Drain water piping insulated as per chiller pipe
(aa) 25 mm dia pipe(for Chiller & AHUs)
(p) GATE VALVE Supply, installation & testing of Gate Valves complete with fiitting like nipples, elbows, tees, bends, sockets etc.
(aa) 25 mm dia size (for Chiller & AHUs)
(q) Supply, Install, test and commision screwed plug for 125 mm chilled water pipe
EXPANSION TANK: Supply, install, testing and commissioning of PVC Expansion water tank for chilled water make up water 500 ltrs. The Tank duly insulated with 50 mm thick fire retarding quality expanded polysterene of density 20 Kg/Cum and finished with sand cement plaster over chicken wire mesh and painted with 2 coats of primer and 2 coats of synthetic enamel paint of approved shade. This Expansion water tank shall be complete with float valve, overflow, drain and make up water connection. The tank shall be connected to suction side of pump with all fittings including necessary piping duly insulated but with out any valve . The tank will be connected with make up water tank piping . Pipe used shall be measured separately.
CONDENSER SECTION Design, supply, laying, fixing, testing and commissioning of condenser water piping with MS heavy class as per IS-1239, pipe complete with all accessories such as bends, elbows, flanges, nut-bolts, clamps, vibration isolators(but excluding valves, strainers and pressure gauges etc), The piping shall be laid overhead in plant and underground outside the plant room as per site conditions. Note: All pipes, pipe supports,structures shall be painted with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow.
(a) The pipes are to be laid out side the building, buried in ground.The pipes shall be given 2 coats of two coats of tarfelt each having thickness of 2 mm and stick with hot bitumen.Pipes shall rest on half round rigid block resting on GI structure including excavations and refilling the trenches and providing suitable thickness 1:2:4 cement concrete pads at 3 M intervals complete
(aa) 200 mm Pipe
(ab) All as per Srl item No.1.71 above but only laying, fixing, testing & commissioning incl painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for 200mm bore pipe complete all as specified and directed. (Pipe shall be issued free for fixing under Sch-B)
(b) Condenser pipes to be laid with in the plant, pipes resting on half round wooden blocks, resting on GI structures are as under:-
(ba) 150 mm Pipe
(bb) All as per Srl item No.1.74 above but only painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for 200mm bore pipe complete all as specified and directed. (The item has been supplied & installed under original work)
(bc) All as per Srl item No.1.71 above but only painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for 150mm bore pipe complete all as specified and directed. (The item has been supplied & installed under original work)
(c) --- DO--- as above but outside the building all along the wall/roof(with necessary fittings, clamps and vibration isolators but excluding valves/strainers/pr gauges) adequately supported on rigid supports
(ca) 200 mm Pipe
(cb) All as per Srl item No.1.78 above but only providing of two coats of tarfelt each having thickness of 2 mm and stick with hot bitumen including excavations and refilling the trenches and providing suitable thickness 1:2:4 cement concrete pads at 3 M intervals complete for 200mm bore pipe complete all as specified and directed. (The item has been supplied & installed under original work)
VALVES WITH CONDENSOR PIPE LINE
Supply, Fixing, testing and commissioning in position following valves, strainers and gauges
(a) Butter Fly Valves (Manual) with CI body, Stainless steel disc, nitrile rubber seal & O ring, PN 1.6. Pressure rating for 200 mm dia pipe including connecting pieces for fixing to 200 mm pipe
(b) ---do--- as above but 150 mm dia
(c) Fixing, testing and commissioning in position Butter Fly Valves (Manual) with CI body, Stainless steel disc, nitrile rubber seal & O ring, PN 1.6. Pressure rating for 200 mm dia pipe including connecting pieces for fixing to 200 mm pipe including painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow complete all as specified and directed. (Valve shall be issued free for fixing under Sch-B)
(d) All as per Srl item No.1.84 above but only painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for 200mm bore Butterfly Valve Manual complete all as specified and directed. (The item has been supplied & installed under original work)
(e) All as per Srl item No.1.84 above but only painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for 150mm bore Butterfly Valve Manual complete all as specified and directed. (The item has been supplied & installed under original work)
(f) only painting with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including marking direction of flow for Non return valve with dual plate of CI body, Stainless steel plates, vulcanised NBR seal flanged ends and PN 1.6 Pressure rating for water circulation, 150mm bore dia complete all as specified and directed. (The item has been supplied & installed under original work)
(g) 'POT' Strainer 200 mm dia
(h) Y type Strainer of ductile Iron body flanged ends with stainless steel strainer 150 mm dia including connecting pieces for fixing to 150 mm pipe
TEMPERATURE GAUGE
(k) Supply & installation of purging valve complete with fittings viz nipple, elbow, tee, bend, socket etc size 32 mm
(l) Supply & installation of GI 'B' class Drain water piping 40 mm dia pipe
GATE VALVE Supply, installation & testing of Gate Valves complete with fiitting like nipples, elbows, tees, bends, sockets etc. of 40 mm dia
DUCT WORK SECTION: Supplying, installing, balanncing, testing and commissioning of site fabricated GSS Sheet metal, rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter damper vanes, hangars, supports as per approved drawings and specifications of following sheet thickness complete
(b) 0.80 mm thickness sheet (22 gauge)
Note: (i) The duct work shall be as per IS 655. (ii) The GSS sheets for duct work shall conform to class viii with zinc coating of 120 gm/sq mtr as per ISS-277.
(e) Supplying, fixing, testing and commissioning of motorised combination fire & smoke dampers in supply air duct/main branch and return air duct as and where required of required sizes. The fire damper shall be motorised and spring return type so as to close the damper automatically in the event of power failure and open the damper when power is restored. The Fire & smoke damper shall be complete with electronic temperature sensor and electrically operated actuator and interconnecting wiring between AHU & dampers The fire damper shall be located in the supply / return air ducts.The control panel shall be located such that the reset can be done easily.
(ea) Fire Damper
INSULATION
Thermal Insulation to supply air duct in Conditioned Space Provide insulation to supply air duct (for indoor conditioned space applications) with 50 mm thick using closed cell anti microbial class O nitrile rubber elastomeric insulation density 40-60 Kg/cum having thermal conductivity 0.035 W/MK with one side factory laminated aluminium foil to be wrapped around the duct. The insulation applied after 2 coats of cold setting adhesive (CPRX Compound). All joints shall be sealed with 50 mm wide self adhesive aluminium tape and covering with 0.63 mm x 19 mm GI wire mesh netting, butting all joints and laced with GI wire complete all as required and as specified.
Return air duct insulation in Conditioned Space --DO-- as item no 2.00 above but with insulation thickness of 25 mm complete all as required and as specified. (in conditioned space for Supply air duct)
All as per Srl item No.2.01 above but except for 25 mm thick closed cell class O nitrile rubber elastomeric insulation complete all as specified and directed. (Nitrile insulation sheet 25mm class O shall be issued free for fixing under Sch-'B')
Return air duct insulation in Un Conditioned Space --DO-- as item no 2.00 above but with insulation thickness of 25 mm complete all as required and as specified. (in un conditioned space for return air duct)
ACCOUSTICAL LINING TO SUPPLY AIR DUCT Supplying and fixing Accoustic insulation for a length of 5 m from plant room, Insulation shall be carried out with 25 mm thick, 32 kg/m3, resin bonded fibreglass covered with RP tissue. Accoustic insulation shall be stuck to inside the ducting after applying 2 coats of cold setting adhesive (CPRX Compound). The insulation is held in position with rivets or galvanised steel bolt with counter sunk heads and 25 x 25 x 1.5 mm GI plate washers at the centre to centre distance of 600mm. The insulation shall be covered with reinforced plastic tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of the duct with cadmium plated nuts, bolts, stick pins complete as required and as per specifications
UNDERDECK INSULATION Supply, Install,test and commission under deck insulation with with Resin Bonded Fibre glass wool conforming to IS:8193 and density 32 kg/m3, 50 mm thick, wrapped in 200 G Virgin polythene bags fixed to ceiling with metallic cleats(50 x 50 x 3 mm ) @60 cm centre to centre and wire mesh of 12.5 mm x 24 G wire mesh for top most ceiling of the Building.
(a) Air Handling Rooms
(b) Complete roof
ACCOUSTIC INSULATION OF AHU ROOMS Supplying and fixing Accoustic insulation lining on wall of AHU Rooms with 50 mm thick, 32 kg/m3, rigid bonded fibreglass. Accoustic insulation shall be fixed in 610 mm x 610 mm frame work made out of 0.6 mm thick GI sheet U shaped channel and covered with reinforced fibre glass tissue paper and finished with 0.8 mm perforated aluminium sheet including aluminium beading of 25 mm wide and 1.00 mm thick fixed on all horizontal and vertical joints by means of screws etc complete as required and as specified.
AIR HANDLING UNITS: Supply, install, test and commission Factory made Double skin Air Handling unit (AHU) as under:- The casing panels shall be made of sandwich construction of at least 25 mm thick injected with CFC free R141b blended Poly Urethene foam insulation having density of 38-40 Kg/Cu.m and thermal conductivity of 0.02 W/m-deg K. The Casing panels(inside and outside) shall be constructed of 1.2 mm steel sheet coated with 120 gm/Sq.m galvanized Zinc(Zn) and 3% Chromate. The outer skin shall be 0.6 mm and inner skin 0.6 mm .The panels are removable type and are fixed to the frame with self tapping screws. Labyrinth type gasket sealing between panel and frame be provided to eliminate air leakages. The entire unit shall be supported on full perimeter base frame constructed from heavy duty galvanized steel sheet. Drain Pan shall be fabricated from 0.8 mm thick Stainless steel grade SS-304 insulated with 10 mm thick close cell cross linked irradiated FR grade Poly ethylene material. Intermediate tray is provided for stacked coils to collect the condensate from the top coil. Drain pan shall be of sufficient width and differential slope to ensure complete drainage of condensate. The AHU shall shall be complete with filter section, mixing bag, water coil of copper tube and aluminium fins. Chilled water shall be suitable for 10 deg temperature differencial, DIDW Forward Curved Centrifugal Fan, belt driven and vibration isolators, Energy efficien motor confirming to IS 12615 suitable for 415+/- 10% volts, 50 C/S, 3 Phase AC Supply The AHU shall be suitable for conventional floor mounting (with vibration pads) for cooling and de-humidifying the air with all accessories and controls for. The required AHUs are as under:-
(a) GF-AHU 2 - 20291 CFM at 80 mm wg STP
(b) FF-AHU 1 - 17343 CFM at 80 mm wg STP
(c) FF-AHU 2 - 21364 CFM at 80 mm wg STP
(d) All as per Srl item 2.09 above but installation, testing and commissioning of GF-AHU 1 - 9787 CFM at 80 mm wg STP complete all as specified and directed. (AHU shall be issued free for fixing under Sch-B)
(e) All as per Srl item 2.09 above for SS-AHU 1 - 13713CFM at 80 mm wg STP complete all as specified and directed. (AHU shall be issued free for fixing under Sch-B)
(f) All as per Srl item 2.09 above for SS- AHU 2 - 15852 CFM at 80 mm wg STP complete all as specified and directed. (AHU shall be issued free for fixing under Sch-B)
Each AHU shall comprise of (i) Cooling Coil 6 Rows with copper tubes (As per OEM Equipment design), 12-13 aluminium fins per inch (ii) Pre filter having dust Filtration capacity 90% efficiency down to 10 microns(synthetic non woven, fire retardent type suported with aluminium & HDPE mesh and generally conforming to EU-3 & EU-779 specifications) (iii) Micro Vee filter having dust Filtration capacity 95% efficiency down to 5 microns conforming to EU-7 specifications. Magne helic gauges be provided to read pressure drop across the Filter bank. (iv) Fan section fitted with statically and dynamically balanced Forward curved blower fan DIDW type suitable to requisite static pressure with belt diven Squirrel cage, Induction Motor, TEFC, 415 V, 3 phase, 50 Hz, AC suply, class 'F' insulation. The motor shall be energy efficient confirming to IS 12615. (v) Electrically controlled /operated control such as humidistat ( to control humidity) and stand alone micro controller based LCD proportionate temperature controller (to control 3 way modulating mixing valve) along with all equipment and accessories including 230V/24 V class 2 transformer. (vi) Pan type Humidistat and dry steam reheaters to control air humidity(20-80%) (vii) Self lubricating bearings with removable panels (viii) Sloped bottom to collect humidification and condensed water and draining piping of sufficint size and length as per standard practice. (ix) Moisturer drop eliminators be provided in AHU to avoid carry away of water condensed. (x) Suitable Fire retardent canvas connection at the outlet of blower (xi) Each Ahu shall be provided with interlocking with Smoke Detectors which are being provided by another Agency. (xii) Each AHU shall be provided with Aluminium extruded Fresh air intake louvres with bird screen, dampers and rain protection (xiii) Each Ahu shall also be provided with (aa) Butter Fly valves - 2 Nos(one at inlet and another at outlet (ab) Y strainer on incoming supply (ac) Automatic air vent valve (ad) drain plug with valve (ae) Manual air vent valve (af) Insertion test ports (Pressure, temperature ports with out Gauges)-3 Nos (ag) Union couplings -2 Nos(ah) 3 Way mixing valve(ah) Automatic Balance valve The Contractor can refer to the drawing enclosed.
MISCELLANEOUS ITEMS Supply of Miscellaneous items as under:-
(a). Digital thermometer and Humidistst are to be provided in Rooms as directed by Engr in charge- 1 Set (Each set consists of digital thermometer and digital humidistat)
(d). Schematic diagram of plant details on a luminous Flourescent sheet as directed by Engr-in-charge
(e) First Aid Box with kit as directed by Engr-in-charge
(f) Supply and install fire point made out of 40x40x6mm MS angle iron frame grouted in PCC and 0.6mm thick MS corrugated sheet canopy of suitable size complete with hooks etc duly painted with two coats of PO red synthetic enameled paint over a coat of red primer and inscribed 'FIRE' in white letter on either sides of the shed, for keeping fire fighting appliances, all as directed by Engineer-in-charge and including following (a) Galvanised MS fire bucket 14.0 ltr capacity - 4 Nos (b) Portable fire extinguishers CO2 type of capacity - 3 Kgs - 01 Nos (c) Portable fire extinguishers ABC type of capacity 3 Kgs - 01 Nos (d) Fire beater - 01 Nos (e) Fire Hook - 01 No (f) Pick axes - 01 No (g) Shovel - 01 No
Material and labour earthing complete with GI plate electrode of size 600 x 600 x 6 mm thick bured directly in ground vertically at a depth not less 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level surrounded from all sides by 1.5 cm thick packed layer of charcoal of dust and common salt filling in alternate layers and making electrode connection by using GI strip of size 32X6 mm by means of bolts nuts check nuts and washers made of brass and earth strip protected by light grade 40 mm dia GI Pipe upto test point and connected to main switch board are main controlled board with provision of GI pipe medium grade 20mm bore for watering including funnel wire mass RCC pit cover and PCC Chamber pit with 1:2: 4 type C2 (including excavation earth work) all as specified and shown in EP No 3 of MES SSR Part - I (Specifications) and testing on completion. Note: The earth test result should not exceed 5 ohms.
S&F Galvanised iron strip 32X6 mm as earth continuity conductor including fixing arrangement on suitable size insulator complete all as specified and directed.
Supply lay and fixing GI Tubing light grade for cable protection laid in trenches or fixed to wall / laid flooring of following sizes :-
(a) 50 mm bore
(b) 80 mm bore
S&F Rubber Mat 2.0 mm thick one meter wide two meter long tested for LT voltage 1100 volts complete all as specified and as directed by Engr-In-Charge.
Material and labour, supply and installation, testing and commissioning of chemical earthing manintainance free based on 3 mtr long pure copper earth pipe C grade of 80mm bore duly fixed with connector at top connection of strip 32x 6mm riveted /nut bolt after 12mm boring with 60Kgs BEFC including providing FRP pit cover of size 250mm x 250mmx 250mm complete as per manufacturer specification and directed at site. Note: (i) Rate included for testing, comissioning including checking of earth continuity and earth result complete all as specified and directed (for AHUs) (ii) Contractor is bound to get earthing result less than 1 ohm (iii) Earth strip to be measured and paid separately
Supply and fix copper strip 20x3mm all as specified and as directed by Engineer-in-charge. (for AHUs earth)
Supply, Installation, Testing and commissioning of ARM Cortex Microprocessor Based Intelligent Fire Alarm Panel UL listed 9th edition , 40 x 4 Characters LCD display, Maximum 4 number of loop cards with Class A Style 5,6 or 7 / Class B style 4 wiring, 254 devices per loop, Day / Night Mode Facility, USB 2.0 Interface for PC connectivity, RS 485 Communication facility for Network / Repeater, Programmable Auto Silence Facility, Programmable Trouble Reminder Facility, Programmable AC Loss Delay, Programmable Silence Inhibit, Two no’s of Programmable Inputs, Loop wise test facility, Battery low visual warning with audible tone, Three Programmable Form C relay for Fire, Fault and supervisory, Two nos. of Supervised Notification Appliance Circuits, Auto dialer / GSM Module, Ethernet Module, Printer Interface Module, Loop card : 4 Nos. Maximum, Numberof Devices per loop : 254, Loop resistance : 40 (Max.), Loop capacitance : 0.6 μf (Max.), Loop Current : 300mA (Max.), One conventional zone Class B Style B/C operation, Normal Operating Voltage : 14 - 21 VDC, Alarm Current : 15 - 30mA Short Circuit Current : 45mA Maximum, Loop resistance : 100 Maximum, End-Of-Line Resistor : 4K7, 1/2watt, Standby Current : 7mA (2mA for Detectors) with battery backup of 30 minutes in alarm condition and 24 hours in Normal Condition Note:- The work should execute by the party who is having Manufacturer Authorization support letter.
Supply,installation,Testing and commissioning of software for programming (mapping) the Fire detection and voice alarm system thorugh FACP / Laptop. The software shall consist of facility like Upload / download of informations to FACP, Graphics compatible to autocad, Detectors information with change in address / sensitivity, GUI interface, Facility to monitor and control the Fire Alarm control panel from window based systems, visual and Sound alerts for the fire and fault conditions, Instant Pop Up's for any events,information available on single screen allowing quick assement and action, facility of Zoom In & Out for better clarity while identifying the alarm location, Event log details with complete history of activity of Fire alarm systems, Three Level multi user access etc as required.
Supply,installation,Testing and commissioning of Computer having all accessories, Intel core processors i5, RAM 4 GB, HDD 1 TB 5400 rpm, DVD writer, Keyboard, Mouse, MFP Printer, having operating system window-7 or above, and MS office updated, 23.8-inch FHD (1920 x 1080) Anti-Glare LED Moniter complete as required or updated version.
Supply,installation,Testing and commissioning of Analog addressable Active Repeater Panel 32 bit processor.160 (40 X 4) Characters LCD display.Touch Keypad for user friendly operation.Remote silence and evacuate can be done from Repeater Panel.Remote Programming and control of any main panel in the network / system .RS 485 Communication for Standalone / Network Repeater.1000 Event storage with Real Time Clock.Battery low audio visual warning.One supervised Notification Appliance Circuits.One Form C relay for Common fire.USB 2.0 for PC Interface.
Supply,installation,Testing and commissioning of Analogue Addressable Multicriteria Detector, UL listed 9th edition, Dual LED’s for 360 visibility, Advanced detection and communication protocol, Regular 100mm base, Address setting by 8 digit DIP switch, Operating Voltage17 ~ 28V DC, Reset Voltage, ess than 3V, Start-Up Current, 500 μA Alarm Current, 5 mA, Remote Output, 2mA maximum open collector, Thermal Rating : 59C,Rate of Raise of Temp : 11.1C / min, Humidity-0 - 95% RH, non-condensing, Smoke Sensitivity : (2.12 ± 0.61) % / ft, High : 1.1% ft, Middle : 1.4% ft, Low : 2.3% ft, Air Velocity : 0 - 4000 fpm,IP Rating : IP – 42
Supply,installation,Testing and commissioning of Analogue Addressable Heat Detector,UL listed 9th Edition, Dual LED’s for 360 visibility,Polarity free wiring Bases, Advanced detection and communication protocol, Easy installation and maintenance, Sleek low-profile housing design, Regular 100mm base, Address setting by 8 digit DIP switch, Operating Voltage : 17 ~ 28V DC, Reset Voltage : less than 3V, Start-Up Current : 500 μA, Alarm Current : 5 mA, Remote Output : 2mA maximum open collector, Thermal Rating, Fixed Temperature : 59 OC (138 OF), Rate of Raise of Temp : 11.1OC / min (20OF/min), Operating Temperature : -10 OC to 37.8 OC, Humidity : 0 - 95% RH, non-condensing,IP Rating : IP – 42.
Supply,installation,Testing and commissioning of Analogue Addressable Duct Detector,For AHU unit tripping
Supply,Installation, Testing and commissioning of Analogue Addressable Bi directional Fault Isolator Module UL Listed 9th Edition, Min Supply Voltage (Vmin) : 17V Max Supply Voltage(Vmax) : 28VDC, Nominal Supply Voltage(V ) 24VDC nom, Current at 24V(Ic) : 30 A, Leakage Current at 24V(I ), 2 mA when isolating, Max Curent (through loop)
Supply of Analogue Addressable Control Module, UL-Listed (9th Edition), Modular Construction, Supervised a Class ‘B’ Style ‘Y’ output circuit, Module Status by RED LED, Analogue Communication with the panel, Module Addressing by 8 way DIP switches,Operating Voltage : 24 VDC Nominal, Current Draw, 2 mA Max.(Latched)
Supply, installation , Testing and Commissioning of UV & IR Flame Detector,Cast Aluminium LM6, Enclosure Hammer Tone Grey, Cable Entry 2x1.5 Sq.mm.- 3nos, IP 66 Protection Glass, Sensitivity UV/IR,UV : 185-260nm, IR : 3000-5000nm, SS304,OPERATING TEMPERATURE -20Deg.C to+60Deg.C, SUPPLY 24VDC±20% (RESETTABLE), QUIESCENT CURRENT < 80mA, ALARM CURRENT < 150mA, INDICATION NORMAL-FLICKERING GREEN LED, FIRE - RED LED, APPLICATION INDOOR AND OUTDOOR, RELATIVE HUMIDITY 0% - 95%, NON-CONDENSING, OUTPUT 1. ONE SET OF 'NO-COM-NC' CONTACT FOR FIRE + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT. ONE SET OF 'NO-COM-NC' CONTACT FOR FAULT + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT. ZONE / DETECTOR LINE RELAY CONTACT RATING 1A at 24VDC, 0.5A at 120VAC APPROVAL/CONFIRMATION/ CERTIFICATION 1. LPCB-1259a/01, 2. CE-CPR:0832-CPR-F0854, 3. CONFORMING REQUIREMENT OF EN54-10,NFPA-72 & IS2189, 4. IP PROTECTION CERTIFIED BY ETDC. Make :- Siemens, Simtronics, Agni-Fladet Series.
Supply,installation,Testing and commissioning of Analogue Addressable Relay Module UL-Listed (9th Edition), for Flame Detector Module Addressing by 8 way DIP swtiches,Low Standby Current, Available with suitable back boxes, Operating Voltage : 24 VDC Nominal, Nominal Current Draw : 2 mA Max.(Latched), Standby Current : 0.5 mA, Contact rating: 2A @ 30 VDC (Resistive), Temperature range: 0 Degree C to 49 Degree C Humidity, / 32- 120F, 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F, Dimensions : (95 W X 75 H X 24D) mm.
Supply,installation,Testing and commissioning of Analogue Addressable Relay Module UL-Listed (9th Edition), for AHU/Lift Shaft/Lift Lobby & stairs Pressurization Fan, Module Addressing by 8 way DIP switches, Low Standby Current, Available with suitable back boxes, Operating Voltage : 24 VDC Nominal Current Draw : 2 mA Max.(Latched), Standby Current : 0.5 mA, Contact Rating : 2A @ 30VDC(Resistive), Temperature Range : 0 DegreeC to 49 Degree C, Humidity, / 32- 120F, 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F, Dimensions : (95 W X 75 H X 24D) mm.
Supply,installation,Testing and commissioning of Sounder cum Strobe with addressable control Modules, UL Listed 9th Edition, Operates on 24VDC, 100db, Ceiling / Flush Wall Mount,Input Voltage : 24V DC (15-30V), Current : 100 mA @24V, Relative Humidity : 93 ± 2 @ 32 C, Operating Temperature : -10 to 50 C, Sound Level : 112 db +/- 5dB @ 30cm, Tone Type : Sweep Siren, Size : 126(W)*126(H)*55(D)mm
Supply,installation,Testing and commissioning of Addressable Manual Pull Station, UL listed 9th Edition,Type A Indoor Use, Resettable by an align key,shall painted by Die casting Housing,shall have a break Glass Rod,Shall have Single gang Mounting,Shall be RED in colour,Shall have corrosion free gold Contact with 10 A rating ,Shall be integrated with addressabel panel thru Monitor Module (UL Listed)
Supply, installing, testing and commissioning of 2c x 1.5 sq. mm, PVC insulated FRLS Armoured copper cable for SLC Loop & Power Supply, confirming to IS standards and specifications..Complete as required as per technical specification.
NOTE FOR COMPLETE SCHEDULE: A) ANY MINOR MODIFICATION REQUIRED FOR SUCCESFUL OPERATION OF PLANT ARE DEEMED TO BE INCLUDED IN OVERALL RATES QUOTED. B) On Successful issue of Phase-I completion plant shall be operated & maintained by contractor for a period of Eight (08) months or till completion of Phase-II test of AC plant which ever is later within overall cost quoted.
SHRI RAMSONS PROJECTS CORPORATION
Comfort Systems
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .