Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹1.4 LAccepted-AOC GOVT CONTRACTOR VILLAGE PO RAJA KA TALAB TEHSIL FATEHPUR DISTT KANGRA HP | KANGRA | HIMACHAL PRADESH | 176001 | ₹1.4 L | l1 | Accepted-AOC L1 |
| 2 | l2₹1.4 LRejected-Finance R O VILLAGE GOPAL CHOWK PO MAHADEV TEHSIL SUNDERNAGAR DISTRICT MANDI HP 175018 | MANDI | HIMACHAL PRADESH | 175018 | ₹1.4 L | l2 | Rejected-Finance Rejected (highest) |
| 3 | Rejected-Technical | - | - | Rejected-Technical Rejected |
| 4 | Rejected-Technical HAMIRPUR ROAD NEAR BUS STAND UNA DISTT UNA HP | UNA | HIMACHAL PRADESH | 174301 | - | - | Rejected-Technical Rejected |
| Sl No | Description | Qty | Unit | KULDEEP DOGRA L1 | AJAY KUMAR SHARMA L2 |
|---|---|---|---|---|---|
| 1.00 | Supply of submersible pumping set of Kirloskar/Kilburn/Clama/Crompton/KSB make conforming to BIS; 8034-1976 latest suitable for lifting clean water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- | 1 | P/set | 1,35,999 ₹1.4 L | 1,40,000 ₹1.4 L |
| 1.01i) Total Head 62.50 Mtrs | |||||
| 1.02ii ) Discharge required from each pump. 6.5 LPS | |||||
| 1.03iii) No. of pump required 1.00 Nos. | |||||
| 1.04iv) Location of the site of installation of machinery. The site is located at a distance of 27 KM from Pathankot (chakki) Railway station by road & 0.100 KM on head load (for the installation of both machineries. | |||||
| 1.05v) The Altitude of installation. The altitude of place is 310.00 mtrs. Above MSL | |||||
| 1.06vi) Type of current. AC Three phase supply with | |||||
| 1.07vii) Rate Voltage 415+ 10% | |||||
| 1.08viii) Type of water and its source Tubewell Dainkwan | |||||
| 1.09ix) Charactristics of water. - | |||||
Tender Value
₹3 L
EMD Value
₹6,000
Closing Date
8 Jan 2026, 11:00 amClosed
EXECUTIVE ENGINEER
EE JSV Division Indora
Providing and Installation of Submersible Pumping Machinery
2025_HPIPH_124642_1
EE-JSV-IND-5023-80 dated 29-12-2025
Open Tender
Civil Works
Indora
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
₹6,000
17 Feb 2026
29 Dec 2025
8 Jan 2026
29 Dec 2025
8 Jan 2026
29 Dec 2025
Amount
Supply of submersible pumping set of Kirloskar/Kilburn/Clama/Crompton/KSB make conforming to BIS; 8034-1976 latest suitable for lifting clean water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
i) Total Head 62.50 Mtrs
ii ) Discharge required from each pump. 6.5 LPS
iii) No. of pump required 1.00 Nos.
iv) Location of the site of installation of machinery. The site is located at a distance of 27 KM from Pathankot (chakki) Railway station by road & 0.100 KM on head load (for the installation of both machineries.
v) The Altitude of installation. The altitude of place is 310.00 mtrs. Above MSL
vi) Type of current. AC Three phase supply with
vii) Rate Voltage 415+ 10%
viii) Type of water and its source Tubewell Dainkwan
ix) Charactristics of water. -
a)Ambient Temperature dig.c 20 dig. C
b)Turbidity NTU 113NTU
c)Hardness260Mg/Ltrs(as CaCO3) 540 Mg/ltr
d) PH 6.5 to 8.5
e) TDS 540 PPM
f)Other -
x) Depth ofTUbe Well 90 mtrs
xi) LWL in Tube Well 45 mtr
xii) Center line level of Pump 45 mtrs.
xiii) Discharge level of highest point 120 mtrs.
xiv) Total head in Mtrs 62.50 mtrs.
xv) Length of R/Main 1250 mtrs.
xvi) Dia of Rising main 100 mm dia GI pipe 4.80 mm thick (MC)
xvii) No of working hours per day 20 Hours
xviii) Limit of pump operation. (-) 15 % (+) 10% of total head
xix) R.P.M. of pumping set. 2900 RPM
xx) Test run. 8 Hours continueously for 7 days
AJAY KUMAR SHARMA (BID ID -606133)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.89 MB
forms.pdf
Tender Documents • 1.64 MB
terms.pdf
Additional Documents • 0.10 MB
BOQ_183230.xls
BOQ • 0.23 MB
Download all tender documents and submit your bid