Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.8 CrAccepted-AOC | ₹27.8 Cr | L1 | Accepted-AOC Accepted being lowest and quoted amount found reasonable. |
| 2 | L2₹31.7 CrRejected-Finance | ₹31.7 Cr | L2 | Rejected-Finance Rejected being not lowest. |
| 3 | L3₹32.3 CrRejected-Finance MANATHA ENCLAVE 3RD FLOOR OLIMUGAL KAKKANAD P O KOCHI 682 030 KERALA | ERNAKULAM | KERALA | 682030 | ₹32.3 Cr | L3 | Rejected-Finance Rejected being not lowest. |
| 4 | L4₹34.9 CrRejected-Finance | ₹34.9 Cr | L4 | Rejected-Finance Rejected being not lowest. |
| 5 | L5₹35.8 CrRejected-Finance GP KIZHAKKAMBALAM KOLENCHERY | THRISSUR | KERALA | 680667 | ₹35.8 Cr | L5 | Rejected-Finance Rejected being not lowest. |
Tender Value
₹25.2 Cr
EMD Value
₹15 L
Closing Date
10 Oct 2022, 6:00 pmClosed
CE NW Kochi
CHIEF ENGINEER NAVAL WORKS KOCHI MILITARY ENGINEER SERVICE NAVAL BASE POST KATARIBAGH KOCHI 682004
PROVISION OF DEFICIENT MARRIED ACCN FOR SAILORS LDGS AND BELOW AT NAVAL BASE KOCHI
2022_MES_547832_1
891012
Open Tender
Civil Works
1095 days
KOCHI
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹3,000
Yes
GE (P) (NW) KOCHI
₹15 L
Yes
23 Feb 2023
26 Aug 2022
14 Oct 2022
27 Aug 2022
10 Oct 2022
26 Sept 2022
Amount
Total amount of Sch 'A' Part-I : (Buildings/ Structures )
Total amount of Sch 'A' Part-II : Excavation, earthwork, site clearance and site development)
Total amount of Sch 'A' Part-III : (Internal water supply)
Total amount of Sch 'A' Part-IV : (Internal Electric Supply)
Total amount of Sch 'A' Part- V : (External Water Supply )
Total amount of Sch 'A' Part-VI : (External Electric Supply)
Total amount of Sch 'A' Part-VII : (Lightning Protection)
Total amount of Sch 'A' Part-VIII : (Fire Fighting System)
Total amount of Sch 'A' Part-IX : (Area Drainage)
Total amount of Sch 'A' Part-X : (Sewage Disposal)
Total amount of Sch 'A' Part-XI (Road/ Path )
Sch 'A' Part- XII : (Miscellaneous B/R & E/M Items (BOQ) (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.)
PILE FOUNDATION
Providing and erecting piling equipment/plant suitable for Cast in situ DMC pile of 500 mm dia ( complete with all accessories) erecting in position and removing after piling is completed all as specified and directed.
Boring of cast in situ pile of 500 mm dia to any depth through any type of soil/strata by DMC method using bentonite slurry including removal of bored materials to place out side MD land all as specified and directed
RCC with ready mix concrete(RMC) M30 grade with min 400Kg cement per cum in cast in situ bored pile of any length/any sections complete all as specified and as shown on drg including non destructive integrity test on all pile as per IS 2911 part IV.Note:-(i) Reinforcement will be measured and paid separately under relevant items (ii) The unit rate quoted under this item is deemed to be inclusive of charges for non destructive integrity tests.
RCC with Ready Mix Concrete(RMC) M30 grade in pile cap , grade beam / tie beam of any length/section complete all as specified and shown on drg. Note :- Reinforcement will be measured and paid for separately under relevant items of this Schedule.
CRS/HCRS/CRM TMT bars as in main reinforcement conforming to IS 1786 as in piles including cutting, bending, welding, tying, assembling, placing, maintaining in position the reinforcement cages complete all specified and as directed.
CRS/HCRS/CRM TMT bars as in reinforcement 10mm dia and over for grade beams/tie beams and pile caps all as shown on drgs including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
CRS/HCRS/CRM TMT bars in reinforcement 5 mm dia and over up to and including 16mm dia conforming to IS-1786 as in Helical/stirrups for piles cut to length, bent to shape required, and binding with 0.9mm dia MS annealed wire or welding .
CRS/HCRS/CRM TMT bars 5mm dia and over upto and including 10mm dia , cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips quality complete all as specified and shown on drgs as in stirrups of grade beams and pile caps.
Plain Cement Concrete (1:4:8) type D2 using 40mm graded stone aggregate for concrete layer below pile caps/ grade beams and foundation complete all as specified and shown on drgs.
Formwork to sides of pile caps, grade beams and tie beams for rough finished flat concrete surfaces all as specified .
Testing of piles (Initial Load test) all as per IS including mobilising and removing the testing equipments from site after testing is completed all as specified and directed for 500 mm dia cast in situ pile.
Testing of piles (Routine Load test) all as per IS for 500mm dia Cast in situ piles including mobilising and removing the testing equipments from site after testing is completed all as specified and directed.
Conducting standard penetration test all as per IS-2131 at levels and locations as directed for 600/750 mm dia cast in situ bored piles all as specified.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep or area not exceeding 10 sqm on plan in any type of soil including bailing out/pumping out water on account of spring/rain or any other causes using any method as required and as directed by Engr-in-Charge for pile caps/grade beams/ raft foundation etc all as specified and shown on drawings.
Excavation over areas not exceeding 1.5m deep in any type of soil including bailing out/pumping out water on account of spring/rain or any other causes using any method as required and as directed by Engr-in-Charge for pile caps/grade beams/ raft foundation etc all as specified and shown on drawings.
Excavation over areas exceeding 1.5m deep and not exceeding 3m deep in any type of soil including bailing out/pumping out water on account of spring/rain or any other causes using any method as required and as directed by Engr-in-Charge for pile caps/grade beams/ raft foundation etc all as specified and shown on drawings.
Excavation over areas exceeding 3m deep and not exceeding 4.5m deep in any type of soil including bailing out/pumping out water on account of spring/rain or any other causes using any method as required and as directed by Engr-in-Charge for pile caps/grade beams/ raft foundation etc all as specified and shown on drawings.
Returning filling in around pile cap, plinth beams, raft foundation etc using excavated soil including spreading levelling and well ramming in layers not exc 25 cm thick complete all as specified and as directed.
Removal of surplus soil to a distance exceeding 50m and not exc. 100m deposited as directed..
Garbage Bin Construction of garbage bin as per permanent specification including excavation, earth work, foundation complete all as shown on drawing No TD/2022/03, Sheet No 1/1 and as specified
Internal Water Supply
Stop cock angular 15mm bore with wall flange complete of make Jaquar, Cat part no CQT-23059 or equivalent in other makes as specified
Bib cock 15mm bore wth wall flange complete of make Jaquar, Cat part No CQT-23047 or equivalent in other makes as specified
Two way Bib cock 15mm bore wth wall flange complete of make Jaquar, Cat part No ORP-10041PM or equivalent in other makes as specified
Internal Electric Supply
Submain wiring with 2 runs of 6 sqmm(for phases and neutral) multistranded copper conductor PVC FRLS insulated unsheathed with and 01 run of 6 sqmm multistranded PVC insulated unsheathed copper conductor (as earth continuity conductor) connected to common earth dolly drawn through and incuding concealed PVC conduit 32mm medium grade ISI marked with accessories. Note : 03 Runs of 6 Sqmm multistranded copper conductor PVC FRLS insulated unsheathed and one run of PVC conduit 32mm medium grade shall be measured as one unit.
All as per item No 39 here-in-before but with 4 Sqmm cable
Submain wiring with 4 runs of 4 sqmm(for phases and neutral) multistranded copper conductor PVC FRLS insulated unsheathed with and 01 run of 4sqmm multistranded PVC insulated unsheathed copper conductor (as earth continuity conductor) connected to common earth dolly drawn through and incuding concealed PVC conduit 32mm medium grade ISI marked with accessories. Note : 05 Runs of 4 Sqmm multistranded copper conductor PVC FRLS insulated unsheathed and one run of PVC conduit 32mm medium grade shall be measured as one unit.
All as per item No 41 here-in-before but with 16 Sqmm cable
Electric water heater storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre BEE 5 Star rated complete with all accessories such as safety valve, NRV, thermostat, connection piece etc.
Supply, install test and commissioning , microprocessor based single phase tamper proof static prepaid cum smart energy meter, 240V, 50Hz, 10-60A, conforming to IS-16444/2015, (reaffirmed in 2020),and as amended from time to time, with LCD display, showing parameters like Voltage, current, frequency, power, power factor,KVA/KWAh, default , with inbuilt communication system like Power line communication (PLC) or Radio Frequency(RF)or Cellular network or V-Sat for data with prepayment features and online monitoring billing system with disconnection re- connection through remote software, data export complete all as specified and directed by Engineer In Charge.
Supply, install test and commissioning , microprocessor based Three phase tamper proof static prepaid cum smart energy meter, 415V, 50Hz, 10-60A, conforming to IS-16444/2015, (reaffirmed in 2020),and as amended from time to time, with LCD display, showing parameters like Voltage, current, frequency, power, power factor,KVA/KWAh, default , with inbuilt communication system like Power line communication (PLC) or Radio Frequency(RF)or Cellular network or V-Sat for data with prepayment features and online monitoring billing system with disconnection re- connection through remote software/ data export to ERP complete all as specified and directed by Engineer In Charge.
Note for item Nos 44 & 45 : The rate for meters above is deemed to include expenditure towards integrating with existing server and software for prepaid metering of the Station. Cost towards expanding the capacity of server and software ( if required) for integrating also shall be included in the above rates.
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including all earthwork, PCC chamber, RCC cover, salt, charcoal etc and testing on completion.
Ceiling fan 1200mm sweep copper wound having minimum service value of 6.00, BEE five star rated with brushless DC(BLDC) motor and min air delivery 210CFM including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multi stranded copper conductor cable of size 0.5 Sq mm from ceiling rose/ connector to fan.
Exhaust fan Steel body, 300 mm sweep 230 Volts AC 50 Hz, with blades, frame and louvers, including connecting up from ceiling rose with 3 core flexible copper cable, PVC sheathed of size 1.5 sqmm, complete all as specified and directed at site.
Exhaust fan made of sturdy engineering plastic complete, with louvres, copper wound of sweep 300 mm 230 Volts AC 50 Hz, , including connecting up from ceiling rose with 3 core flexible copper cable, PVC sheathed of size 1.5 sqmm, complete all as specified and directed at site.
Exhaust fan made of sturdy engineering plastic complete, with louvres, copper wound of sweep 250 mm 230 Volts AC 50 Hz, , including connecting up from ceiling rose with 3 core flexible copper cable, PVC sheathed of size 1.5 sqmm, complete all as specified and directed at site.
LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder, including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
LED lights fitting 1x 18W, 220V, AC decorative box type with driver, holder, including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
LED lights fitting 1x 10W, 220V, AC mirror type with high out put diffuser, 2 feet, decorative type with driver holder and LED lamp, including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size.
Decorative wall light fitting, with un- breakable poly carbonate diffuser suitable for and including 1x10W LED lamp complete, all as per Havells Model City 1 or equivalent of approved makes.
LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete fixed as building security light on walls with suitable size GI pipe bracket, bent to shape up to 1.5 m long, including connecting up from junction box/ ceiling rose with twin core weather proof copper cable, I.5 sqmm all as directed..
EXTERNAL ELECTRIC SUPPLY
Supply,install,testing and commissioning of 11 KV 630 Amps, 20 KA Motor operated compact outdoor both side extensible non draw out type suitable for 01 No incoming LBS) and 01 No outgoing (VCB), model (+CV+) of ABB or equivalent in other approved makes for transformer with compact SF6 gas insulated unit, all live parts enclosed in a welded stainless steel tank of IP 67 class of protection including coupling accessories all as specified and as directed.(Note the panel shall be suitable make and model matching with existing RMU panel and also will ensure smooth and efficient functioning. The RMU will be tapped from proposed RMU of 26 CPO's.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 185 sq mm (Earthed system) complete all as specified
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150sq mm 3.5 core complete all as specified
All as per item 62 here-in-before but 3.5core 95 Sq mm
All as per item 62 here-in-before but 4core 25 Sq mm
All as per item 62 here-in-before but 4core 16 Sq mm
All as per item 62 here-in-before but 2core 6 Sq mm
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 Sq.mm
Supply, install, testing and commissioning of factory made and CPRI tested out door type feeder pllar box suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 400 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 3.15mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties( Location LTP No 1 of schematic plan) INCOMING (a) MCCB 415 Volts,400 Amp , rating 4 Pole (Four pole and neutral), Thermal Magnetic release (Service Breaking Capacity 50 KA -01 Nos Incomming. (b) Digital volt meter 0-500 Volts-01 (c) Digital Ampere meter 0-300 Amps with and including CTs
Item No 67 (Contd..) OUTGOING (a) MCCB 415 Volts,250 Amp , rating 4 Pole (Four pole and neutral), Thermal Magnetic release (Service Breaking Capacity 25 KA as out going (01 Nos) For AMF panel (b) MCCB 415 Volts,200 Amp , rating 4 Pole (Four pole and neutral), Thermal Magnetic release (Service Breaking Capacity 25 KA as out going (01 Nos) For capacitor bank (c) MCCB 415 Volts,125 Amp , rating 4 Pole (Four pole and neutral), Thermal Magnetic release (Service Breaking Capacity 25 KA as out going(03Nos) for LTP. 5 & 6 - 02 Nos & Spare-01 No (d) Internal wiring of panel with stranded copper cable of suitable size (e) Neon phase indicating lamp(Set of three)-01 Nos (f) Stenceling of pannel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 400 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :-(Location: LTP No.2 (DG AMF Panel) of Schematic plan)(for bldg No 1&2) INCOMINGS (a) MCCB 415 Volts,250 Amp , rating 4 Pole (Four pole and neutral), Thermal Magnetic release (Service Breaking Capacity 25 KA 1 Nos Incomming. (b) Digital volt meter 0-500 Volts-01 (c) Digital Ampere meter 0-300 Amps with and including CTs-01 No
Item No 69 (Contd….) OUTGOING (a) MCCB 415 Volts,100 Amp , rating 4 Pole (triple pole and neutral), Thermal Magnetic release (Service Breaking Capacity 18 KA (Ics=50%Icu)- 03 Nos.For LTP.4-01 No,LTP.3-01Nos,Spare-01Nos (b) MCCB 415 Volts 40 Amp , rating 4 Pole (triple pole and neutral), Thermal Magnetic release (Service Breaking Capacity 18 KA (Ics=50%Icu)- 1 No) for Pump. (c) Internal wiring of panel with stranded copper cable of suitable size (d) Neon phase indicating lamp(Set of three)-01 Nos (f) Stenceling of pannel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating200 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :-(Location: LTP No 3&4 of Schematic plan)(Lift,Fire,Common Area-02Nos.). INCOMINGS (a) MCCB 415 Volts, 100Amp, rating 4 Pole (triple pole and neutral), (Service Breaking Capacity 10 KA - 01 No (b) Digital volt meter 0-500 Volts-01 (c) Digital Ampere meter 0-100 Amps with and including CTs-01 No
Item No 71(Contd...) OUTGOING (a) MCB TPN 415 Volts, 63Amp, rating 4 Pole (TPN), (Service Breaking Capacity 10 KA - 02 Nos (b) MCB TPN 415 Volts, 40Amp, rating 4 Pole (TPN), (Service Breaking Capacity 10 KA - 02 Nos (c) Digital volt meter 0-500 Volts-01 (d) Digital Ampere meter 0-300 Amps with and including CTs (e) Neon phase indicating lamp(Set of three)-01 Nos (f) Stenceling of pannel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating200 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :-(Location: LTP No 5 & 6 of Schematic plan)(Bldg no.1 panel-01,Bldg no.2 panel-01Nos) INCOMINGS (a) MCCB 415 Volts, 125Amp, rating 4 Pole (triple pole and neutral), (Service Breaking Capacity 10 KA - 01 No (b) Digital volt meter 0-500 Volts-01 (c) Digital Ampere meter 0-100 Amps with and including CTs-01 No
Item No 73 (Contd...) OUTGOING (d) MCB TPN 415 Volts, 40Amp, rating 4 Pole (triple pole l), (Service Breaking Capacity 10 KA - 07 No (e) Digital volt meter 0-500 Volts-01 (f) Digital Ampere meter 0-300 Amps with and including CTs (g) Neon phase indicating lamp(Set of three)-01 Nos (j) Stenceling of pannel board including marking of distribuitions
Earthing complete with galvanised steel earth plate electrode size 600x600x6.00mm thick burried directly in ground vertically in pit of depth not less than 2.25 mtr below normal ground level with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised iron strip 25X4 mm earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and also including provision of GI pipe light grade 20mm bore for watering, funnel with wire mesh. PCC chamber pit in PCC 1:3:6 type C-1, 40 mm thick precast RCC M-25 (design mix) cover reinforced with 8 mm dia TMT bars @ 10 cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50 m complete all as specified and shown in electric plate No.3 of SSR Part-I(2009), all as specified including testing on completion.
Automatic Power Factor Correction (APFC) Panel for 3 Phase, 415 V & 50 Hz system of capacity 60 KVAR with incoming MCCB 125 Amps 415 Volts, 50 Hz ,16 KA, 4 pole MCCBs and standard protective equipments,APFC relays required all as specifed and as directed
LED Security/street Light 45 W new generation energy saving and environmental friendly long life, made up of pressure die cas aluminium housing with high efficiency LED as lighting source and lens with toughned glass having bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK07
Danger notice plate of 1.6mm thick mild steel sheet , vitreous enameled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 25x 20cm size
Fencing for outdoor H.T VCB and outdoor transformer by chain link steel wire of size 7mtr x 5 mtr of 2 mtr height with provision of entry gate of suitable size. The fencing laid by erecting intermediate 40mm x 40mm x 3mm flat iron angle of 02 mtr height. The base of flat iron angle laid above thick cement base. The complete fencing area filled with 20mm graded stones
Steel octagonal decorative pole 9 mtr long complete with cast iron base plate, bolts, nuts and screws fixing, including on suitable pole foundation with street light brackets suitable size and cable terminal junction boxes nut bolts, washers, terminal block, and glands suitable for 16 sq mm core cable including 6 Amps MCB SP complete anchor bolts and nuts as specified and directed including PCC 1:3:6 TYPE C-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete for stay,polesetc complete all as specified and directed. Dimensions of foundation concrete will be LXBXD :0.5MX0.5MX1.5M below ground level and 0.5MX0.5MX0.3M above ground level.
EXTERNAL WATER SUPPLY
Cutting existing 150 mm bore CI water mains and inserting Tee of size 150x150x100 mm dia for taking branch connection including fittings and lead joints complete all as specified
Supply and lay pipe ductile Iron , S/S including specials, Class “K-9” ,100 mm (4”) dia complete all as specified
Valve Chamber 900X900X900 mm size internally built with brick work in CM 1:6 plastering complete with CM 1:4 including necessary earthwork,PCC 1:4:8 , 100 MM thick as in foundation concrete including provision of cast iron hinged cover with using 2 mm thick steel with 'FH' empossed and painting with two coats of synthetic enamel paint over a coat of red Oxide primer complete all as directed.
Supply and install foot valve of size 2 1/2" inches to suction pipe of the monoblock centrifugal pump
Supply,install,testing and commissioning of centrifugal monoblock pump set with CI casing , bronze impeller, air release valve, pressure gauge and stainless steel shaft mounted in heavy duty bearing suitable for electricity operated 3 phase, 415 Volts 50 Hz AC Supply with head range 40 mtrs ,discharge 10.7 LPS, complete including wiring with suitable PVC Copper cable in PVC conduit from starter panel to motor connector box with and including PCC foundation etc complete all as specified
LT Motor Control Panel outdoor type with Front Operated Single door floor mounting type made out of 2 mm thick CRCA Sheet powder Coated, dust proof manufactured by CPRI approved manufacturer complete with 200 Amp TPN aluminium bus bar with the following components :- (a) MCCB TPN 63 Amps 25 KA as incoming -01 No (b) MCB TP 32 Amps -02 Nos (c) MCB SPN 16 Amps - 01 No (d) Provn for fixing & Supply 02 Nos Star Delta starter (e)Digital Volt meter with SS 0-500 V -01 No (f) Phase indication Lamp R,Y,B -01 set (g) Single phase preventor -02 Nos (h) Digital Ammeter 0-30 Amps
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 25X 4 mm GI strip as earthing lead by means of bolts, nuts, checknuts and washers of galvanised iron or steel all as shown in electricalplate No. 3 connected to earthing test point all as specified or indicated including testing on completion
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 4 mm dia GI wire as earthing lead by means of bolts, nuts, checknuts and washers of galvanised iron or steel all as shown in electricalplate No. 3 connected to earthing test point all as specified or indicated including testing on completion including PCC Pit and RCC Cover funnel with wire mesh all as specified and as directed
STANDBY DG SET
Supply and installation of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with foundation (as per OEM design), control panel with necessary meter and sound proof canopy as per CPCB norms of capacity 62.5 KVA/50 KW,87 Amps, 415 Volts, 3 phase,4 wire directly coupled to diesel engine, mounted on common base plate, vibration damper with AMF Panel suitable for 62.5 KVA DG Set along with connected accessories,relays,engine as per BS:5514, ISO:3046 and alternator as per IS 4722,BS: 50000, generator set prime rating as per ISO: 8528 complete with relay panel for automatic starting on main electric supply failiure, control panel having meters, sound proof canopy with avr control excitation, power factor 0.8 with suitable rated battery with acoustic encloure fabricated out of 1.6 mm CRCA steel after nine tank process, surface pretreated with foam materials, conforming to IS7888/IS8183 and pure polyster power coating complete as per CPCB-II norms, sound level 75 dB (A) at one mater from enclosure a surface in free feild condition as per ISO:8528 suitable for using with AMF system and founadtion etc complkete all as specified and directed by Engineer-in-Charge and comprising of the following DG Micro processer based AMF control panel, outdoor type-IP-54 rated, inclained type double door,
Item No 93(Contd...) fabricated out of 16 SWG CRCA sheet with powder coating, cubicle compartmentalized, freestanding, dust and vermin proof with reinforcement of suitable size angle iron and channel, Galvanised hardware with Zinc passivation, T section wherever necessary, including bottom channel supports,etc, fully meeting all the requirements specified in the inspectorate specifications foundation with PCC 1:2:4 type B-1 (using 20 mm graded aggregate)etc complete. DG micro processor based AMF control panel, out door type-IP-54 rated inclained top double door, fabricated out of 16 SWG CRCA sheet with powder coating cubicle compartmentalized, freestanding, dust and vermin proof with reinforcement of suitable size angle iron and channel, Galvanised hardware with Zinc passivation,T section wherever necessary, including bottom channel supports,etc, fully meeting all the requirements specified in the inspectorate specifications foundation with PCC 1:2:4 type B-1 (using 20 mm graded aggregate)etc complete. Note: The emission from DG set shall not exceed the limits set by CPCB norms and the environment protection third amendment rules 2013, issued by Ministry of Environment and Forest, Govt of India, amended upto date.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 32 X 6 mm GI strip as earthing lead by means of bolts, nuts, checknuts and washers of galvanised iron or steel all as shown in electricalplate No. 3 connected to earthing test point all as specified or indicated including testing on completion
Earth continuity conductor of size 32 X 6mm GI Strip all specified and directed
TV & TELEPHONE SOCKET
GI metal flush boxes 2 module complete all as specified
RJ 11 telephone socket 1 module with cover plate complete all as specified
TV socket 1 module with cover plate complete all as specified
Rigid non metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all Tees,bends,elbows,reducers,bell mouth,bell tube ends and fixing accessories such as couplers,lock nuts,saddles,pipe hooks etc, dia of conduit 20mm complete all as specified
Rigid non metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all Tees,bends,elbows,reducers,bell mouth,bell tube ends and fixing accessories such as couplers,lock nuts,saddles,pipe hooks etc, dia of conduit 25mm complete all as specified
AVIATION OBSTRUCTION LIGHT
Aviation obstructionLED integral aviation light Comprising of aluminium housing and polycarbonate enclosure with timer switch and one 10A MCB SP 230 Volts fixed in a sheet metyal enclosure complete all as specified
XLPE UG Cable with aluminium conductor 1100 volts grade armoured of size 2 core 6 sq mm on wall/floor/roof etc with suitable clamps complete all as specified
LIGHTNING PROTECTION
Earthing complete with galvanised steel earth plate electrode 60x60 6mm thick, burried directly in ground ( earth pit not less than 2.25 mtrs below ground level) with top edge of the plate not less than 1.5 mtr normal ground level, connected to GI strip 32x6 mm as eatthlead by means of bolts, nuts, check nuts and washers of GI or steel as shown in electrical plate No 3 connected to earthing test point all as specified and directed inclusing testing complete ( Earthing shoulod be interconnected)
SEWAGE DISPOSAL
Pre cast RCC hume pipe septic tank 100 users capacity designed to carry sewage and sullage water including excavation in any type of soil, PCC 1:4:8 in foundation, shaft connection etc all as shown on drawing No TD/A/157, Sheet No 1/1 complete all as specified and directed
Soak well 3.0 metre dia and 1.2 metre deep including excavation inany type of soil, PCC 1:3:6 foundation, honey combed PCC block wall, M-25 topping including intercepting chamber in Cement Mortar, RCC cover slab, interconnecting RCC pipe filled with brick bats etc all as shown on drawing No TD/A/162, Sheet No 1/1 complete all as specified and directed.
DWC PE Pipe (SN8) 180 (OD)/163 (ID) mm dia laid and jointed including all fittings and fixtures complete all as specified
ROAD/ PATH
150mm thick (compacted thickness) Wet Mix Macadam (WMM) with coarse aggregates of grading 2 (63 to 40mm size) or of grading 3 (50 to 20mm size), spread, rolled and consolidated to gradient and camber required using granite/trap/basalt aggregate complete all as specified
FIRE FIGHTING SYSTEM
Ductile iron pipe, S/S including specials, Class "K-9", 150mm dia including rubber ring tyton joint, ISI marked, complete all as specified
Gun metal air release valve 25mm dia
LED emergency exit signage luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency back up upto 05 hours
PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavu duty) with stranded copper conductor size 1.5 Sqmm, 2 core, 1100V grade
LED Emergency escape lighting luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency backup upto 05 hours
Analog addressable type active loop repeater (Loop power/external power) Fire terminal with inbuilt turbo isolator, Backlit LCD Display 6 x40 characters display, having controls for reset, mute,accept, silence alarms and self test, with programmable free keys and duly approved by EN54/LPCB/VDS/FM
LT Motor Control Panel outdoor type with Front Operated Single door floor mounting type made out of 2 mm thick CRCA Sheet powder Coated, dust proof manufactured by CPRI approved manufacturer complete with 200 Amp TPN aluminium bus bar with the following components :- (a) MCCB TPN 63 Amps 25 KA as incoming -01 No (b) MCB TP 32 Amps -02 Nos (c) MCB SPN 16 Amps - 01 No (d) Provn for fixing & Supply 02 Nos Star Delta starter (e) Digital Volt meter with SS 0-500 V -01 No (f) Phase indication Lamp R,Y,B -01 set (g) Single phase preventer -02 Nos
Sheet metal enclosure board fabricated with 2mm thick CRCA sheet powder coated for firefighting pumps -02 Nos installed at roof of building with height of 01 meter and front door with opening / closing hinges arrangement
Item No 125 (Contd....) during power / system failure with latest IGBI power devices. 3D infra red sensor in full length of doors and built in floor announcing system with 4 Nos hand set one each in car, machine room and near ground floor landing door and over load indicator with suitable for three phase , 415 volts, 50Hz AC supply for passenger lift including all connected civil works and 2 Nos earthing with & including provisions as mentioned in particular specification and as directed.
Item No 127 (Contd..) landings, fire man switch , emergency lamp alarm push button etc with and including automatic rescue device (ARD) battery operated with and including maintenance free battery of suitable capacity and battery charger with optimum direction section in start operation requiring no human intervention rescues during power / system failure with latest IGBI power devices. 3D infra red sensor in full length of doors and built in floor announcing system with 4 Nos hand set one each in car, machine room and near ground floor landing door and over load indicator with suitable for three phase , 415 volts, 50Hz AC supply for passenger lift including all connected civil works and 2 Nos earthing with & including provisions as mentioned in particular specification and as directed.
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised strip of size 32 x 6 mm earth continuity coductor by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion or any other equipment with provision of GI pipe light grade etc allas specified and directed including testing on completion including PCC pit and RCC cover funnel with wire mesh complete all as specified
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified
Earth continuity conductor of size 32 X 6mm GI Strip complete all as specified
ARBORICULTURE
Supply and planting Bermuda grass (by dibbling method @ 7.5 cm apart over a prepared surface with adequately devoleped root after providing anti-termite treatement including preparation of surface, earth work excavation, removing surplus spoil filling approved earth suitable for grassing, 20 cm thick, after mixing with fertiliser/ organic manure and regular maintenance of grass for one year complete all as specified.
COMPREHENSIVE MAINTENANCE OF LIFTS AFTER DEFECT LIABILITY PERIOD
All as per Item No 135 here-in-before but for the second year after completion of defect laibility period.
All as per Item No 135 here-in-before but for the second year after completion of defect laibility period.
All as per Item No 138 here-in-before but for the second year after completion of defect laibility period.
All as per Item No 138 here-in-before but for the second year after completion of defect laibility period.
Agarwal Jagdish Construction Company Pvt. Ltd.
Mecone Construction Contractors
Crescent Construction Company
VIJAY CONSTRUCTIONS
Kurian And Varghese
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid