Loading…
Loading…
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
22 Sept 2026, 6:00 pm7d left
GE (AF) BARODA
GE (AF) BARODA ,DARJIPURA , GUJARAT-390022
REPAIRS,REPLACEMENT OF INTERNAL ELECT WIRING, SUBMAIN WIRING, DBS, FLAME PROOF LIGHTS, HIGH BAY LIGHTS AND CONNECTED ITMES AT OTM AND TECHNICAL ACCOMODATION OF MAKARPURA AT AFS VADODARA
2026_MES_787021_1
8214/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
MAKARPURA, GUJARAT-390014
AS PER NIT
9 documents required · 9 mandatory
₹500
GE (AF) BARODA
₹40,000
Yes
31 Aug 2026
31 Aug 2026
24 Sept 2026
31 Aug 2026
22 Sept 2026
15 Sept 2026
1 Sept 2026 - 8 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down carefully copper / Aluminium point wiring including (light, fan, socket or power complete fittings, such as switches, ceiling roses, pendant holders, Batten holders, shades conical fan regulators, light or power sockets etc) removing materials from site and making good disturbed surfaces of walls roofs etc all as directed. | 286 | POINT | - | - |
| 2Material and labour for point wiring for one light point or one fan point or one fan point controlled by one switch with using 1.5 Sq mm (nominal area) stranded copper conductor single core, PVC insulated & unsheathed cable, 1100 volts grade in and incl concealed PVC conduit (medium grade) existing /new conduit as per site requirement of suitable size all as specified and directed with using new sunken type pressed steel box/terminal boxes for mounting fittings/junction boxes not less than 1.6 mm thick duly painted with two coats of black bituminous paint over a coat of red oxide primer with and incl all accessories and using 1.5 Sq mm (nominal area) stranded copper conductor single core conductor, PVC insulated & unsheathed cable as in earth wire connected to common earth dolly complete all as specified and directed. Make PVC cable .Havells/Finolex/Polycab Note : (i) The quoted rates shall be deemed to be inclusive foe cutting chases in brick walls/pillars etc for concealing the depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the portion of point wiring at RCC columns/ Beems/ Cielings shall be in surface conduit of suitable size fixed on surface plugs and provision of covering sunken boards/terminal boxes/junction boxes of any shape and size with 3 mm thick with suitable GI screws and cup washers. (ii) Fittings like switches sockets regulators, lamp holders light fittings shall be measured and paid for seperatly of Sch’A’. (iii) The size of conduits shall be determined on permissible No of runs of wires as specified in SSR part I (2010) However minimum size of conduits shall be 20 mm dia (medium grade). | |||||
| 2.01 | One light point controlled by one one/way switch. | 25 | POINT | - | - |
| 2.02 | One Fan point controlled by one one/way switch. | 25 | POINT | - | - |
| 2.03 | One 3 pin 5 Amps socket outlet on same board with other switch. | 30 | POINT | - | - |
| 2.04 | One 3 pin 5 Amps socket outlet on independent board with cable of 1.5 sqmm size. | 30 | POINT | - | - |
| 2.05 | One bell point controlled by one way switches | 5 | POINT | - | - |
| 2.06 | One light point controlled by two way switches | 3 | POINT | - | - |
| 3 | All as per item No. 2 above but using 2.5 Sqmm PVC insulated, unsheathed cable for one 3 pin socket outlet 15 Amps on independent board. | 25 | POINT | - | - |
| 4M&L for point wiring for one light or one fan point controlled by one switch with using 1.5 Sq mm (nominal area) stranded copper conductor single core PVC insulated & unsheathed cable 1100 volts grade in and incl PVC casing and capping of suitable size fixed on surface all as directed with using new sunken type pressed steel box/terminal boxes for mounting fittings/junction boxes not less than 1.6 mm thick duly painted with two coats of black bituminous paint over a coat of red oxide primer with and incl all accessories and using 1.5 Sq mm (nominal area) stranded copper conductor single core conductor PVC insulated & unsheathed cable as in earth wire connected to commen earth dolly complete all as specified and directed.Make PVC cable .Havells/Finolex/Polycab Note : (i) The quoted rates shall be deemed to be inclusive for fixing the conduits to surface with using PVC of covering sunken boards /terminal boxes/junction boxes of any shape and size with 3 mm thick suitable GI screws and cup washers. (ii) Fititngs like switches, sockets, regulators lamp holders light fittings shall be measured and paid appropriate item of schedule ‘A’ (iii) The size of conduits shall be determined on permissible No of runs of wires as specified in SSR part- I however minimum size of conduit shall be 20 mm dia (medium grade). | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.17 MB
BOQ_881990.xls
BOQ • 0.38 MB
8214PS.pdf
Tender Documents • 0.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .