Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.9 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹38.3 L+₹5.5 L (16.7%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN L1 | |
| 3 | L3₹38.9 L+₹6.1 L (18.6%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN L1 | |
| 4 | L4₹39.0 L+₹6.1 L (18.7%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN L1 | |
| 5 | L5₹39.1 L+₹6.3 L (19.1%)Rejected-Finance VIVEKANANDA PALLY UPPER BAGDOGRA PO PS BAGDOGRA DARJEELING WEST BENGAL 734 014 | DARJEELING | WEST BENGAL | 734014 | L5 | Rejected-Finance OTHER THAN L1 |
Tender Value
₹46.6 L
EMD Value
₹93,200
Closing Date
13 Jul 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (NORTH) TEZPUR
GE (NORTH) TEZPUR, C/O 99 APO
SPL REPAIR IN REPLACEMENT OF LT OVER HEAD LINE TO UNDER GROUND CABLE WITH ALLIED CONNECTED WORK AT PHULBARI UNDER AGE CHARDUAR UNDER GE (NORTH) TEZPUR
2024_MES_660209_1
GE(N)/TEZ/2024-2025/8946
Open Tender
Civil Works
Item Rate
180 days
GE (NORTH) TEZPUR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (NORTH) TEZPUR
₹93,200
19 Oct 2024
15 Jun 2024
20 Jul 2024
15 Jun 2024
13 Jul 2024
29 Jun 2024
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed.
Supply & spreading in trenches sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Supply and laying well burnt bricks sub class 'B' in trenches for cable protection of U/G cable all as specified and directed by Engr-in-Charges.
Taking out the existing ACSR Conductor /PVC/XLPE, 1100 volts grade, LT UG electric cable of any size and any type in trenches/ walls/ overhead lione (or) passing through pipes/in floor complete all as specified and directed by the Engr-in- charge Note:- Excavation and Earth work shall be measured and paid separately under appropriate items:-
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 25 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 35 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 50 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 70 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 95 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 150 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 185 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Laying only the under ground cable any type obtained from Items No -06 above in trench/wall/floor etc are connecting with suitable cable lugs/sleevs etc and size 240 sqmm 3.5 core complete all as specified and directed by Engr-in Charge .
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 25 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 35 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 50 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 70 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 95 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 150 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 185 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 240 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 25 to 50 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 95 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 150 to 185 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 240 to 300 sqmm 3.5 core complete all as specified and directed by Engr-in Charge.
Supplying & laying in repair 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in trenches 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
M&L preparing old painted surfaces by scraping and removing old paints, rust, etc. from steel tubular poles (above the planting depth and PCC copings of 11.0 Metre length Pole) and mild steel cross arms, cable protection pipe, brackets, etc. and applying one coat of red oxide zinc chrome primer, alternate yellow & black strips painting (4 Nos. each strip 200 mm wide) and remaining portion of pole and cross arms, cable protection pipe, brackets, etc. treated with two coats of Aluminium paint, complete all as specified and as directed.
Taking out the existing LT pole of any size and any type complete all as specified and directed by the Engr-in- charge
Supply & erecting steel tubular swaged pole type 410-SP-55 (11.0 Metre long) including cast iron base plate, finial taper plug, cap, mild steel bolts, nuts, screws, including necessary excavation and earth work, PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C1 as in plinth block and coping, disposal of surplus soil to a distance not exceeding 50m and depositing where directed, painting of exposed surafaces of steel tubular poles with two coats of Aluminium paint over one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.complete all as specified and as directed.
Re Fixing of Steel tubular swaged poles any type and any size after taking dwon with proper shut dwon without damage of pole any location within 100 mts complete including cast iron base plate, finial taper plug, cap, mild steel bolts, nuts, screws, including necessary excavation and earth work, PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C1 as in plinth block and coping, disposal of surplus soil to a distance not exceeding 50m and depositing where directed, painting of exposed surafaces of steel tubular poles with two coats of Aluminium paint over one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.complete all as specified and as directed.
M & L in repair for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
Road cutting for passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 25 sqmm 3.5 core. Complete all as specified and directed
M & L for cement concrete in foundation, filling and mass concrete in M15(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
S & F in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 mm X 4 mm galvanised mild steel strip complete all as specified and as directed.
Supply and fixing in repair 32 mm X 6 mm galvanised mild steel strip for horizontal conductors and down conductors including suitable design of fixing components of galvanised steel as per fig 28 of IS 2309: 1989 complete all as specified and as directed.
Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of (CPRI Approved) outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved having front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessary foundation work as per manufacturer instraction including foundation and including taking down the old panel required at site and comprising following:- Incoming (a) S&F for Electrolytic grade high conductivity solid 4 Nos Alu bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings. The bars shall be colour coded at required intervals for identification - 04 Nos (b ) S&F for LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3 (C ) S&F Ammeter and voltmeter digital multy meter Nos -01 (d ) S&F for MCCB 400 Amp 36 KA 4 pole Thermal magnatic setting complete - N0s -01 outgoing (a ) S&F MCCB of 4 pole of capacity 100 amps, with breaking capacity of 16 KA with fixed thermal & fixed magnetic setting - 04 Nos (b ) S&F MCCB of 4 pole of capacity 125 amps, with breaking capacity of 16 KA with fixed thermal & fixed magnetic setting - 02 Nos (c ) S&F MCCB of 4 pole of capacity 200 amps, with breaking capacity of 36 KA with fixed thermal & fixed magnetic setting - 02 Nos (d ) S&F MCCB of 4 pole of capacity 250 amps, with breaking capacity of 36 KA with fixed thermal & fixed magnetic setting - 01 Nos
Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar (CPRI Approved) of outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved having front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessary foundation work as per manufacturer instraction including foundation and including taking down the old panel required at site and comprising following:- Incoming (a) S&F for Electrolytic grade high conductivity solid 4 Nos Alu bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings. The bars shall be colour coded at required intervals for identification - 04 Nos (b ) S&F for LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3 (C ) S&F Ammeter and voltmeter digital multy meter Nos -01 (d ) S&F for MCCB 250 Amp 36 KA 4 pole Thermal magnatic setting complete - N0s -01 outgoing (a ) S&F MCCB of 4 pole of capacity 63 amps, with breaking capacity of 16 KA with fixed thermal & fixed magnetic setting - 03 Nos (a ) S&F MCCB of 4 pole 160 amps, with breaking capacity of 25 KA with fixed thermal & fixed magnetic setting, - 01 Nos
Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of (CPRI Approved) outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved having front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessary foundation work as per manufacturer instraction including foundation and including taking down the old panel required at site and comprising following:- Incoming (a) S&F for Electrolytic grade high conductivity solid 4 Nos Alu bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings. The bars shall be colour coded at required intervals for identification - 04 Nos (b ) S&F for LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3 (C ) S&F Ammeter and voltmeter digital multy meter Nos -01 (d ) S&F for MCCB 250 Amp 36 KA 4 pole Thermal magnatic setting complete - N0s -01 ( e ) Change over switch 250 Amp 4 pole front loaded operated 415 volts Nos -01 outgoing : (a ) S&F MCCB of 4 pole of capacity 100 amps, with breaking capacity of 25 KA with fixed thermal & fixed magnetic setting - 03 Nos (a ) S&F MCCB of 4 pole of capacity 63 amps, with breaking capacity of 25 KA with fixed thermal & fixed magnetic setting - 03 Nos
Earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6.3 mm thick burried directly in ground( earth pit not less than 2.25 m deep below the normal groungnd level) with top edgee of the plate not less than 1.5m below normal GL connected to GI earth strip of size 25x4mm by means of bolts, nuts, check nuts washers of GI or steel all as shown in electrical plate No-3 of SSR Part I connected to machanery/equipments installed power house/sub station all as specified including testing on completion. Note No-1 the unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete all as specified & shown in eletrical plate No.3 of SSR Part-1 2009.
M/S JALALUDDIN AHMED (BID ID -3052131)
M/S RSB ENTERPRISES (BID ID -3052520)
M/S GN ENTERPRISE (BID ID -3052228)
GANAPATI TRADING (BID ID -3051265)
DRISTEE ASSOCIATES (BID ID -3049057)
M/S L N ENTERPRISE (BID ID -3051580)
gurchan singh & sons. (BID ID -3054007)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .