| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.1 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹27.9 L+₹82,213.20 (3.03%)Rejected-Finance | L2 | Rejected-Finance 2794750.00 | |
| 3 | L3₹29.5 L+₹2.4 L (8.89%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L3 | Rejected-Finance 2953547.00 |
Tender Value
₹33.8 L
EMD Value
₹67,639
Closing Date
23 Nov 2020, 2:00 pmClosed
Executive Engineer PWD BDN ELEC DIVN
Room no 1081st fl purta bhawan salt lake kolkata
Supply Installation Testing and Commissioning of Fire Detection and Alarm system at Proposed Five Pump Fire Station G plus 5 New Town Rajarhat
2020_WBPWD_302337_1
WBPWD/EE/BED/18/e-IT of 2020_21
Open Tender
ELECTRICAL WORKS M/R
Item Rate
30 days
New town
Please refer Tender documents.
5 documents required · 5 mandatory
₹67,639
Yes
1 Dec 2020
16 Oct 2020
25 Nov 2020
5 Nov 2020
23 Nov 2020
5 Nov 2020
Amount
Supply, installation, testing & commissioning of EN Standard, VDS approved Addressable Multi-Sensor Detector (optical smoke as well as heat) with inbuilt / equal number of additional Isolator for each detector and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation and high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unquie address for communication and assigned through panel with Mounting Base as required. (Approved Make: Esser / Detectomat / Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Intelligent Analog Addressable Heat Detector (Static + ROR) with inbuilt / equal number of additional Isolator for each detector and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation. Detector should have unquie address for communication and assigned through panel with Mounting Base as required.(Approved Make: Esser / Detectomat / Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Inteliigent addressable manual call point with inbuilt / equal number of additional Isolator for each manual call point suitable for flush or surface mounting, call point shall include test key feature without removing the glass with extra acceesories as required.(Approved Make: Esser / Detectomat / Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Addressable One input & One output module with inbuilt / equal number of additional Isolator for each I/O module and shall have the LED indication for Normal, Fault, test, and activation.The module shall have the option for configuration as fail safe operation.(Approved Make: Esser / Detectomat / Siemens)
Supply, Installation,Testing & Commisioning of EN standard, VDS Approved Microprocessor based 4 Loops expandable up to minimum 6 Loops, fire alarm control panel fully networkable (Vender should consider Network card for panel to panel networking) with each loop capable of taking atleast 125 devices and each loop should be connected to a dedicated loop card, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having minimum 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V / 12 V with integral battery charger complete as required and as per specification. (Approved Make: Esser / Detectomat / Siemens)
Supply, erection, testing & commissioning of RESPONSE INDICATOR Complete with base, mounting box, gland, lugs, etc. as required completing in all respect.(Approved Make: Esser / Detectomat / Siemens)
Supply & Installation of Batteries for Main FACP, 7AH - 12 Volt DC. (Make: Exide\Amaron)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop). (Make. Finolex /Hemflex / MEM)
Supply & Laying of 20 mm NB PVC rigid conduit pipe on the surface of the wall. (Make: Precisson-Medium) .
L.W.C. must be quoted manually @1% on the total quoted value else the total quoted rate shall be treated incl. LWC as per rule. N.B. Rate should be quoted inclusive of GST.
MAGNUM SAFETY INDIA
GLYPTIC
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .