Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | LI₹1.3 CrAccepted-AOC | ₹1.3 Cr | LI | Accepted-AOC l1 |
| 2 | L2₹1.4 CrRejected-Finance | ₹1.4 Cr | L2 | Rejected-Finance Other then lowest |
| 3 | L3₹1.4 CrRejected-Finance VPO CHAMBI | CHAMBA | HIMACHAL PRADESH | 176207 | ₹1.4 Cr | L3 | Rejected-Finance Other then lowest |
| 4 | L4₹1.5 CrRejected-Finance | ₹1.5 Cr | L4 | Rejected-Finance Other then lowest |
| 5 | L5₹1.5 CrRejected-Finance | ₹1.5 Cr | L5 | Rejected-Finance Other then lowest |
Tender Value
₹1.2 Cr
EMD Value
₹1.5 L
Closing Date
14 Jun 2021, 5:00 pmClosed
EXECUTIVE ENGINEER
EE JS DIVISION CHAUNTRA
Providing LWSS to PC Habitation of GP Bihun and Nauhli alogwith house hold connection SH P Laying , Jointing and testing of Rising Main Supply erection of pumping machinery
2021_HPIPH_48281_1
2336-76 dt 08.06.2021
Open Tender
Pumps/Motors
Item Rate
270 days
Joginder Nagar
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,500
EE CHAUNTRA
₹1.5 L
Yes
5 May 2022
8 Jun 2021
15 Jun 2021
8 Jun 2021
14 Jun 2021
8 Jun 2021
Amount
Excavation in foundation and trenches etc. up to all depths and in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out of water, blasting soft or hard rock or chiselling / wedging out of soft/hard rock , where blasting is prohibited, in all lifts including trimming and dressing of sides, levelling of beds to correct grade including shoring, strutting , planking, timbering and dewatering where ever required. Stacking usable and unusable material /soil seperataly , returning the usable soil in 15cm layers by ramming and watering and then dISOsing of all surplus excavated soil/ unusable material as directed within all leads/ lifts complete in all respects within all leads and lifts as per direction of the Engineer-in-charge.
Providing and laying cement concrete 1:4:8 (1cement:4 sand:8 graded stone aggregate 40mm nominal size) and curing complete excluding cost of from work in foundation and plinth complete in all respect with in all leads and lifts and as per the entire satisfaction of Engineer-in Charge.
Providing tor steel reinforcement for R.C.C. work including bending,binding and placing in position complete upto floor two level in all respect complete with in all leads and lifts as per the direction of Engineer-in-Charge.
Providing form work of steel plate 3.15mm thick planking so as to give a rough finish including shuttering, centring, shuttering and propping hight of propping and centring below supporting floor to ceiling not exceeding 4 mtrs and removal of the same for in-situ reinforced concrete and plain concrete work in lintels, beams etc. including all leads and lifts in: and as per the entire satisfaction of Engineer-in Charge.
Foundation , footing basis of columns & the like and mass concrete complete in all respect and as per the direction of Enginer-in-Charge
Providing and laying cement concrete 1:2:4(1cement:2sand:4graded crushed stone aggregate 20mm nominal size)and curing complete excluding cost of form work and reinforcement for reinforced work in:- foundation and plinth
Laying, fixing, jointing and testing in trenches Galvanised mild steel tubes of following dia meters confirming to BIS 1239-2001 (GI Pipes MG) (latest with upto date amendments) having wall thickness as per code with plain ends in random length of 4 to 7 meters, including specials, short pieces, bends, reducers, tees etc. made from parent tube, providing and welding of MS flanges detailed as below. The MS flanges shall confirm to BIS 6392-1971 (with latest up to date amendments) duly welded in two layers (two inner and two outer) with pipes at both ends as per relevant BIS standards along with nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets confirming to relevant BIS standards. The laying of pipe will include all operation such as cutting, welding, jointing, providing & fixing of MS flanges, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The damaged portion of the pipes and specials made form the parent tube during welding or otherwise shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately).
125mm dia GI (Medium grade ) T-5
Providing , laying,jointing ( by way of circumfrential flanged joints of various flanges by electrical arc welding ) and testing of Steel pipes of following dia meters confirming to ISO 3183-2007, pipe gradeAPI pipe 5 L (latest with upto date amendments) having wall thickness as specified below with bevelled ends and capable of withstanding required test pressure in a random length of 4 to 7 meters, including manufacturing reducers/ tapers , all short pieces, beds etc. as per site requirement made from parent tubes . The laying of pipe will include all operation such as cutting, welding, jointing, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipes shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards and the damaged portion of the pipes and specials made form the parent tube shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately).
125 mm dia , (ISO 3183-2007), Wall thickness 5.20 mm, MSERW F.T=38
Providing , laying,jointing ( by way of circumfrential butt welded joints by electrical arc welding ) and testing of Steel pipes of following dia meters confirming to ISO 3183-2007, pipe grade API 5 L (latest with upto date amendments) having wall thickness as specified below with bevelled ends and capable of withstanding required test pressure in a random length of 4 to 7 meters, including manufacturing reducers/ tapers , all short pieces, beds etc. as per site requirement made from parent tubes . The laying of pipe will include all operation such as cutting, welding, jointing, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipes shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards and the damaged portion of the pipes and specials made form the parent tube shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately).
125 mm dia , (ISO 3183-2007), Wall thickness 5.20 mm, MSERW BUTT WELDING.
125 mm dia , (ISO 3183-2007), Wall thickness 4.80 mm, MSERW BUTT WELDING.
125 mm dia , (ISO 3183-2007), Wall thickness 4.00 mm, MSERW BUTT WELDING.
Laying,jointing ( by way of circumfrential butt welded joints by electrical arc welding ) and testing of Galvanised mild steel tubes (GI Pipes) of following dia meters confirming to BIS 1239-2001 (latest with upto date amendments) having wall thickness as per code with bevelled / plain ends in a random length of 4 to 7 meters, including manufacturing reducers/ tapers , all short pieces, bends etc. as per site requirement made from parent tubes . The laying of pipe will include all operation such as cutting, welding, jointing, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The damaged portion of the pipes and specials made form the parent tube during welding or otherwise shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately).
125mm dia GI (Medium Grade) Butt welding
Pumping Machinery (Ist Stage) Supply of submersible raw water pump set of reputed make such as KSB/Calama/SU/joinsion conforming to latest relevant BIS code. The pump should be fitted with free flow impellers of suitable alloys as per BIS 8034-1978 latest suitable for lifting raw water having 6000 PPM turbidity, grease packed bearings and shaft with wound stator on motor side and with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specification. The pump shall be directly coupled to submersible squirrel cage electrical induction motor of same make conforming to BIS 9283-1979 (latest with up to date amendments) totally dust and water proof for submersible duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical load with minimum bear and tear. It should also be fitted with a device to take up expention of water with heating of motor. The pump should include water level guard,errection clamps,cable clips and depth gauge etc. and suitable for opration in data given
Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standarad make such as MEI/Kilburn/Jyoti/ Siemens cnonforming to BIS-8544-1979 latest with up to date ammendments for squirrel cage (make to be specified by the tenderers) mounted on panel board with magnetic type over load release & dashpot,time lag,under voltage release with initial oil filling .
Providing & fixing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angale iron post of suitable height and size ISA 40x40x6mm duly paintedcomprising and capable of mounting the following accessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer in charge.
ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediatly after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length equal to width of board of 3 live phases and one copper bar of half reating of full length for neutral conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto date ammendments.
MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS 3452 part I & II latest with up to date ammendments.
Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitaible range with which should have control box, oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring condition of the circut breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker on occurance of earth fault on/ of breaker load side.
Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/recommendations.
Suitable three phase voltage monitor relay with all protections & usual indicators with electrical sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference
Change over Switch of reputed make & suitable capacity
Single phase preventor of reputed make & suitable capacity
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/ Kartar of reputed make of suitable size cast iron PN-1 double flanged sluice valve having size equal to due step higher than delivery of pump and capable of with standing nominal seat pressure of 10 kg/cm^2
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/Kartar of suitable size cast Iron PN-1 double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 10 kg/cm^2
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/Kartar of suitable size cast Iron double flanged swing check type reflux valve having bye pass arrangement & size equal to dia of R/main for withstanding nominal seat pressure of 10 kg/cm^2
P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC make from meter of HPSEB to OCB & from OCB to Busbar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost..
P/L suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC make from switch to starter & starter to motor (one cable for carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor.The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments for above motors & other electrical equipment.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834- 1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.
Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/L column pipe considering site requirements,NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers, flanges ,rubber gaskets, 3mm thick as per BIS-2712-1978 nuts & bolts as per 1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge The pipes shall be capable of withstanding 1.5 times the total presure indicated in item no. 1e(ii).
(2nd Stage)Supply of horigental spindle, vertical split casing single/Multistage centrifugal / reciprocating pumps of standarad make such as KSB/Mather & Platt/Jyoti/Kirloskar/WASP /Best & Crompton conforming to BIS latest with upto date ammendments read with BIS 9137-1978 or latest to handle clear water having turbidity 500PPMwith impellers ,casing ring& saft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity coupled directly through a flexible coupling on a common base plate to Kirlosker/ NGEF/Crompton/Siemen/Joti/ABB/Marathan approved by the department .slip ring/ squirrel cage screen protected drip proof induction electric motor suitable for operation on the data given below.NOTE: RECIPROCATING PUMPS SHALL BE OF WASP/ASPEE MAKE ONLY & SHALL CONFIRM TO RELEVENT BIS CODES
Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standarad make such as MEI/Kilburn/Jyoti/ Siemens cnonforming to BIS-8544-1979 latest with up to date ammendments for squirrel magnetic type over load release & dashpot,time lag,under voltage release with initial oil filling .Note:- Star delta -starter upto 37.5 KW ,ATS between 37.5 KW to 50 KW and Stater rotor starter with slipring motor.
Providing & fixing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angale iron post of suitable height and size ISA 40x40x6mm duly painted comprising and capable of mounting the following accessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer in charge.
ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediatly after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length equal to wirdth of board of 3 live phases and one copper bar of half reating of full length for neutral conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto date ammendments.
MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS 3452 part I & II latest with up to date ammendments.
Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitaible range with which should have control box, oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring condition of the circut breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker on occurance of earth fault on/ of breaker load side.
Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/recommendations.
Suitable three phase voltage monitor relay with all protections & usual indicators with electrical sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference
Change over Switch of reputed make & suitable capacity
Single phase preventor of reputed make & suitable capacity
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/ of reputed make of suitable size cast steel double flanged ASA-300 sluice valve having size one step higer to delivery of pump and capable of with standing nominal seat pressure of 52 kg/cm^2 class ASA-300 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure ) 104 Kg/Cm2as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast steel ASA-300 double flanged swing check type reflux valve having bye pass arrangement & size one step higher to delivery of pump for withstanding nominal seat pressure of 52 kg/cm^2class ASA-300 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size Cast Steel ASA-300 double flanged swing check type reflux valve having bye pass arrangement & size one step higher to delivery of pump for withstanding nominal seat pressure of 5 size equal to dia of R/main ie 65mm diafor withstanding nominal seat pressure of 51 kg/cm^2class ASA-300 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/Kartar of reputed make of suitable size cast iron flanged sluice valve confirming IS 780, size equal to dia of suction pipe ; PN1 provided with hand wheel/Cast iron Cap.
P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC make from meter of HPSEB to OCB & from OCB to Busbar switch & starter (one cable carrying carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost..
P/L suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC make from switch to starter & starter to motor (one cable for carrying all three phases) imake from switch to starter & starter to motor (one cable for carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor.The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses specified by the tenderer.(Range to be
Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
Erection of all items except item no. 22.00 to 22.02 i/c cost of tees,bends tapes & any others fittings required as per site conditions and as per direction of Engineer-in -Charge.
sanjeev govt cont
Tek Singh Raghav
SB Trading company
SANGRAM NAIK
Oasis Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .