| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing, installation, testing and commissoning of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Grundfos/ Kirloskar / BE/ Maxflow/ Beaconweir Sabar make conforming to BIS 5659-1970) pump (Latest with upto to date ammendments, read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/ Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC/ABB & suitable for operation on 415 (+/-) 10% volts 50 cycle per second 3 phase AC electric supply conforming to BIS 900-1972 and IS: 12615:2011 with IE 2 specifications, 2900 RPM (latest upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below:- | 2 | Sets | - | - |
| 1.01 | Discharge(Q) - 2.89 LPS for each pump, Total Dynamic heads - 362.21 Meter, a) LWL in sump well(h) - 807 Meter, b) Shaft Level - 808 Meter, c) Level at Discharge point - 908 Meter, d) Suction Lift - +ve, e) Discharge Head - 100 Meter, f) Static head - 100 Meter
Rising Main
a) Length - 2700 Meter, b) Dia - 50 mm, Pumping Hours - 8 Hours, Altitude of installation above MSL - 808 Meter, Characterstics of water - Raw Water with turbidity up to 6000 PPM, Temperature - 25 degree centigrade. | - | - | - | - |
| 2 | Supply, Installation, Testing and Commissioning of Soft Starter panel for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand bye) each of the rating 40 HP through Star Delta Starter mechanism. Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators.
Make: JSV Approved | 1 | No. | - | - |
| 3 | Star Delta and Mains Power Contacts of required ratings as per type-2 co- ordination for 40 HP starter complete job in all respect with in all leads and lifts as per the direction and satisfaction of Engineer-in-Charge. | 2 | Set | - | - |
| 4 | Voltage Protection device to protect panel from over voltage and under voltage complete job in all respect with in all leads and lifts as per the direction and satisfaction of Engineer-in-Charge. | 2 | Nos. | - | - |
| 5 | Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage complete job in all respect with in all leads and lifts as per the direction and satisfaction of Engineer-in-Charge. | 2 | Nos. | - | - |
| 6 | Multi Function meter indicating different parameters like current, Voltage, KWH, PF, THD etc. with RS 485 communication of JSV approved make complete job in all respect with in all leads and lifts as per the direction and satisfaction of Engineer-in-Charge. | 1 | No. | - | - |
| 7 | Main incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 (Latest edition). | 1 | No. | - | - |
| 8 | Individual Starter incomer MCCB/MCB of suitable capacity of L&T/ Schnieder/ABB make or any other JSV approved make on the feeder for pumping set confirming to BIS 2516-1985 (Latest edition). | 2 | Nos. | - | - |
| 9 | LED three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 (Part I & II ) latest with upto date ammendments. | 1 | Set | - | - |