Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.5 LAdmitted-Finance Q 158 SHIVALIK NAGAR HARIDWAR PIN 249 403 | HARIDWAR | UTTARAKHAND | 249403 | ₹37.5 L | L1 | Admitted-Finance |
| 2 | L2₹37.5 LAdmitted-Finance | ₹37.5 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical 221 VIJAY PARK EXTENSION LANE NO 11 DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | - | - | Rejected-Technical BID IS NON RESPONSIVE |
| Sl No | Description | Qty | Unit | Garg Construction L2 | Purohit Hydro Power Management L1 |
|---|---|---|---|---|---|
| 1.00MV CABLES | |||||
| 2.00Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required. | |||||
| 3.00 | Upto 35 sq. mm | 65 | Mtr | 39 ₹2,535 | 38 ₹2,470 |
| 4.00Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written. | |||||
| 5.00 | 3C x 4 Sq.mm. CU XLPE armored cable | 25 | Mtr | 472 ₹11,800 | 471 ₹11,775 |
| 6.00 | 3C x 6 Sq.mm. CU XLPE armored cable | 20 | Mtr | 651 ₹13,020 | 651 ₹13,020 |
| 7.00 | 3C x 10 Sq.mm. CU XLPE armored cable | 20 | Mtr | 1,047 ₹20,940 | 1,046 ₹20,920 |
| 8.00CABLE TERMINATION | |||||
| 9.00Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. | |||||
| 10.00 | 3C x 4 Sq.mm. CU XLPE armored cable | 12 | Nos | 269 ₹3,228 | 269 ₹3,228 |
Updated dates
Tender Value
₹37.6 L
EMD Value
₹75,000
Closing Date
12 Dec 2025, 3:00 pmClosed
PM BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrical and Allied works for Shop ABC at Mahasu Devta Hanol
2025_BRID3_89112_1
1231/BRIDCUL/233/25 Dated 10.11.2025
Open Tender
Electrical Works
365 days
Uttarkashi
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
Project Manager, Project Unit Dehradun, BRIDCUL
₹75,000
BRIDCUL Dehradun
12 Feb 2026
24 Nov 2025
12 Dec 2025
24 Nov 2025
12 Dec 2025
2 Dec 2025
1 Dec 2025
MV CABLES
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required.
Upto 35 sq. mm
Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written.
3C x 4 Sq.mm. CU XLPE armored cable
3C x 6 Sq.mm. CU XLPE armored cable
3C x 10 Sq.mm. CU XLPE armored cable
CABLE TERMINATION
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.
3C x 4 Sq.mm. CU XLPE armored cable
3C x 6 Sq.mm. CU XLPE armored cable
3C x 10 Sq.mm. CU XLPE armored cable
DISTRIBUTION BOARDS
Supply, installation, testing and commissioning following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) - 8way, Double door (IP43, IK09)
Supply, installation, testing and commissioning following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) - 12way, Double door (IP43, IK09)
Supply, installation, testing and commissioning following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) - 16way, Double door (IP43, IK09)
Supplying and fixing of weatherproof enclosure for double pole, 240 volts, MCB (6A-32A) complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A Double pole
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A
Supply, installation, testing and commissioning 'C' series, SP MCB Supply, installation, testing and commissioning 5 amps to 32 amps rating, 240 volts, 'B' series, miniature circuit breaker suitable for lighting and other loads of folloeing poles int the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
POINT WIRING
Point wiring in PVC conduit, with modular type switch: Wiring for light point/ fan ponit/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required- Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 & 15/16A amps modular socket outlet and 15/16 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supplying and fixing stiff pendent with 300 mm long, 20 mm dia X 1.6 mm thick steel conduit, aluminium cast back plate and brass holder complete, including wiring the down rod with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and painting etc. as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2X1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1X2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
2 X 16 sq. mm + 1 X 6 sq. mm earth wire
CONDUIT & OTHER
EARTHING
S/L SWG GI wire in ground: Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc. as required
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Earthing with GI earth plate 600 mm x 600 mmx 6 mm thick including accessories and providing masonary enclouser with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcole/coke and salt as required.
LIGHT FIXTURES
20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures: 20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures complete with suitable rating lamps and all other necessary accessories to complete the installations as per specifications. * Minimum lumen 2000 Lumens in CCT range of 3000/4000 with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained. * Colour of light fixture shall be WHITE as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply of Weather Proof Recessed false ceiling light Recessed Celiing Light - 10W,800lm,IP65,3000/4000K, Dimension 100X80mm, Height 80mm Diameter is 100mm, Weight is 0.5kg, Fixing Suitable for ceiling-mounted recessed installation. Fixture is made of Die Cast Aluminium, Powder Coated, LED is COB, Inbuilt driver, Input AC 240V, 50/60Hz * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply of Weather Proof Recessed Downlighter (On Roof Chajja) Recessed Celiing Light - 10W,800lm,IP65,2700/3000K, Dimension 100X80mm, Height 80mm Diameter is 100mm, Weight is 0.5kg, Fixing Suitable for ceiling-mounted recessed installation. Fixture is made of Die Cast Aluminium, Powder Coated, LED is COB, Inbuilt driver, Input AC 240V, 50/60Hz * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Up & Down Light SITC of 2X10 W LED Up down light suitable for wall mounting , BIS approved , Body made of pressure Die cast aluminium , proper heat sink should be designed for better heat dessipation , The diffuser should be clear toughned glass with IK08 protection . The luminaire is provided with surge protection of 4 KV . Electronic driver having power factor>0.95, THD <10 % and input voltage range from 150-270V AC at 50Hz. Minimum lumen 2000 Lumens in CCT range of 3000/2700 with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained.Ambient Operating Temperature is -10 Deg. to 50 Deg. Luminaire should Maintain Ingress Protection of IP65/IP66 for better weather proofing. * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
25x50mm Linear light fixture-10watts per meter- 10x60 deg- CCT : 3000K: Supply of Customized exterior rated wall mounted 25x50mm Linear light fixture with antiglare visor mounting without bracket, Wattage - 10 watts per meter, Beam Angle - 10X60deg, IP-66, Life of fixture L70 @Ta-35 deg C should be at least 50,000 burning hours. CCT - 3000K, Suitable driver/controller. (All the technical parameters of the luminaire need approval from the lighting consultant) With Driver * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
JUNCTION BOXES
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector. Equivalent to Hensel catalogue no KF 1006 G/OBO/CAPE
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector. Equivalent to Hensel catalogue no KF 1610 G/OBO/CAPE
CABLE TRAYS
supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
DWC PIPES
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
120 mm dia (OD-120 mm & ID-103 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
CCTV SYSTEM
Supply, installation, testing and commissioning of Cat6 cable.
Supply, Installation,testing and commissioning of 8Port POE Network Switch to provide Power and Data Communication for mentioned Camera. With 1 G SFP Module.
Supply, Installation, Testing & Commissiong of 5 MP IR Dome Camera 1/3″ Megapixel progressive scan Exmor CMOS, Infrared, Dome camera with D/N ICR, IR, varifocal lens, 2.8mm-12mm, F1.6, with Audio, H.264, IP66 rated 720p @ 25fps, H.264: 4–8192 kbps, BLC/HLC/DWDR, IR distance up to 30m, RJ-45 connection, Inbuilt microSD card slot, BLC/HLC/DWDR, 3D DNR, ROI, ONVIF, PoE Complete as per specification, IP66, IK10, Including necessary accessories for mounting * Colour of Camera shall be Black as per Architectural requirements. * Contract
or to submit samples for Approval before ordering the fixture.
Supply, Installation, Testing and Commissioning of Wall mounted 9U Rack along with power sockets strips and all other require components & acceessories to mount all the equipments for satisfactory job.
Supply, Installation, Testing and Commissioning of 6 single mode fiber optic cables (9/125 µm) with all necessary accessories to comply the installation.
Hard Drive Disk: SITC of Enterprise surveilliance HDD 8 TB for 60 days storage at D1 resolultion.
Supply, Installation, Testing and Commissioning of industrial type 32" LED Display for 24x7 runningg (ON), 1920 X 1080 Resolution, 450 CD/M2 Brightness, Wall Mounting Bracket.
Supply, Installation, Testing and Commissioning of 1 mtr. Cat 6 Patch cord.
Supply, Installation, Testing and Commissioning of 24 Port fully loaded patch panel
Any other Item Not included in CCTV system but required to complete the Job:-
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
SBD_ELECTABC.pdf
Tender Documents • 1.78 MB
BOQ_105709.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid