Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.1 CrAdmitted-Finance | ₹34.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹36.3 CrAdmitted-Finance | ₹36.3 Cr | L2 | Admitted-Finance |
| 3 | L3₹37.4 CrAdmitted-Finance | ₹37.4 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Ajay Kumar Sood Engineers and Contractors L1 | Vasu Constructions Co. L3 | KDN Infrastructure Pvt. Ltd. L2 |
|---|---|---|---|---|---|---|
| 1.00EARTH WORK Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 Sqm on plan including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra. | ||||||
| 1.01 | All kinds of soil | 9,548 | Per Sqaure metre | 70 ₹6.7 L | 50 ₹4.8 L | 60 ₹5.7 L |
| 2.00Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra. | ||||||
| 2.01 | All kinds of soil | 1,256.8 | Per Cubic Metre | 250 ₹3.1 L | 100 ₹1.3 L | 200 ₹2.5 L |
| 3.00Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as perdirection of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra. | ||||||
| 3.01 | Ordinary rock | 5,590.78 | Per Cubic Metre | 250 ₹14.0 L | 250 ₹14.0 L | 250 ₹14.0 L |
| 4.00Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra. | ||||||
| 4.01 | All kinds of soil. | 771.7 | Per Cubic Metre | 205 ₹1.6 L | 250 ₹1.9 L | 200 ₹1.5 L |
| 5.00 | Filling available excavated earth (including rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating Each deposited layer by ramming and watering including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharge . | 3,980.68 | Per Cubic Metre | 70 ₹2.8 L | 100 ₹4.0 L | 75 ₹3.0 L |
| 6.00 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge . | 10,935 | Per Cubic Metre | 205 ₹22.4 L | 415 ₹45.4 L | 500 ₹54.7 L |
Tender Value
₹39.5 Cr
EMD Value
₹79.0 L
Closing Date
24 Feb 2026, 5:00 pmClosed
Executive Engineer
O/O Project Director HPTDB Shanti Bhawan Phase 3 Kangnadhar Shimla 9
Sub Head Construction of Food Court, Toilet block, shops, Landscaping, External development , Finishing of Hotel and Recreation block, External and internal E.I work and fire fighting etc.
2026_DTCA1_127276_1
Construction of Balance work of Tourist Complex at Auhar, Distt. Bilaspur, HP
Open Tender
Composite Works
545 days
As Per Tender Document
Please refer Tender documents.
4 documents required · 4 mandatory
₹40,000
Director Tourism and Civil Aviation Shimla
₹79.0 L
20 Apr 2026
4 Feb 2026
25 Feb 2026
4 Feb 2026
24 Feb 2026
4 Feb 2026
EARTH WORK Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 Sqm on plan including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra.
All kinds of soil
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra.
All kinds of soil
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as perdirection of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra.
Ordinary rock
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, including getting out and disposal of excavated earth at approved dumping sitel by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. dumping site/disposel site shall be arranged by the contractor at he own cost and nothing shall be paid extra.
All kinds of soil.
Filling available excavated earth (including rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating Each deposited layer by ramming and watering including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharge .
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
All kinds of soil
Ordinary or hard rock
Supplying chemical emulsion in sealed containers including delivery as specified.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termtite treatment (excluding the cost of chemical emulsion) :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / Sqm of the vertical surface of the substructure to a depth of 300mm including excavation channel along the wall & rodding etc. complete: With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration
Treatment of soil under existing floors using chemical emul- sion @ one litre per hole, 300 mm apart including drilling 12 mm diarmt holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge
1:4:8 (1 Cement : 4 coarse sand) : 8 graded stone aggregate 20 mm nominal size)
1:5:10 (1 cement : 5 coarse sand): 10 graded stone aggregate 40 mm nominal size)
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Extra for addition of synthetic Polyester triangular fibre of length 12mm, effective diameter 10-40 microns and specific gravity of 1.34 to 1.40 in cement concrete / RCC / Flooring / water retaining structures by using 125gms of synthetic Polyester triangular fibre for 50 Kg cement used .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Centering and shuttering including strutting, propping etc. and removal of form. for :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Foundations, footings, bases of columns, etc. for mass concrete
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Suspended floors, roofs, landings, balconies and access platform.
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Columns, Pillars, Piers, Abutments, Posts and Struts
Stairs, (excluding landings) except spiral-staircases
Edges of slabs and breaks in floors and walls Under 20 cm wide
Cornices and mouldings
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 Rmt or part thereof (Plan area to be measured) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .Make (TATA/Sail/Jindal panther )
Thermo-Mechanically Treated bars of grade Fe-500D or more.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .Make (TATA/Sail/Jindal panther )
Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
All works upto plinth level
All works above plinth level upto floor V level
Extra for providing richer mixes at all floor levels.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Add for using extra cement in the items of design mix over and above the specified cement content therein.
(2nd class) Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Cement mortar 1:6 (1 cement : 6 coarse sand)
(2nd class) Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Cement mortar 1:6 (1 cement : 6 coarse sand)
(2nd class) Brick work in plain arches in superstructure above plinth level and upto floor five level including centering and shuttering complete for span up to 6 Rmts with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in cement mortar 1:3 (1 cement : 3 coarse sand). including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Cement mortar 1:4 (1 cement :4 coarse sand)
Extra for providing and placing in position 2 Each 6mm dia. M.S. bars at every third course of half brick masonry. including carriage of material by mechanically & manual upto all lead & lift and as pe rdirection of Engineer incharge .
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length ( hold fast lugs or dash fastener shall be paid for separately).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Second class seasoned teak wood
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conformingto IS : 2046 Type S, including cost of adhesive of approved quality.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1.0 mm thick
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured) including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Extra for providing vision panel not exceeding 0.1 Sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured) including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Rectangular or square
Providing and fixing wooden moulded beading to door and window frames with iron screws, plugs and priming coat on unexposed surface etc. complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge :2nd class teak wood. 50x12 mm
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diaRmt bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & Fixing veneer of approved make with wood grain finish with polishing as required both side surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.4.0 mm thick including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Card Reader of approved make with necessary screws etc. complete.( Indian make of approved quality) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing eye Viewer of approved make with necessary screws etc. complete.( Indian make of approved quality) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
SLIDDING FOLDDING PARTITION Providing & fixing both side 4mm thick veneer & Polish finish sliding folding partition of consisting of series of individual flat elements of 100 mm thick travelling along the ceiling track assembled to form a solid wall. The entire system must function as a solid wall and even when closed should reveal minimal screws, fixing or other similar solid metal parts. The sound insulation of the operable partition 45 dB tested under third party reputed laboratory in accordance to EN 20140-3. The test certificate should show the make and model of the system. Elements must be constructed of a torsion-free steel horizontal tube frame and torsion-stiff vertical aluminium profiles, bolted together to make the element strong and sturdy. The frame must be clad either side with 16mm MDF panels hung in acoustic free suspension from the panel frame. The panel skin shall be installed on site and able to be replaced without totally disassembling the panel frame. The element must be constructed in accordance with the specified sound insulation requirements. The elements must be inter-connected by means of a positive locking concave/convex aluminium profile with an integrated magnetic strip and sealing lip having a linear attraction of 40N/m. The spindle mechanism in every element should be connected to the top and bottom horizontal seals which should be constructed of aluminium plates with flexible rubber at the contact point. Specially formed polyurethane corner rubber seal to be provided for overlapping acoustic seals horizontal sealing strip. Each element must have a spindle mechanism which should be connected to the spring loaded top and bottom retractable seal. The spindle mechanism should be operated manually by a bayonet connected crank handle that acts as a lock in function during cranking process. Drop down seal are not acceptable. The horizontal top and bottom seals must be retracted as per the operating mechanism and should ensure a contact pressure of 800N when the seals are completely extended. The spring loaded retractable horizontal seals should also be able to adjust to minor floor undulation for better accoustic efficiency. No fixed sweep seals allowed in top and bottom of the element that would rub against the track or floor while moving the element. The seal spindle mechanism must be accessible while the panel is hanging for servicing and adjustment if necessary. The fascia boards to be clipped on as free oscillating panels to offer optimum sound insulation. The fascia boards must be removable without dismantling the Movable walls elements. Sound Barrier Partition above Operable Sliding/Folding Partition Providing and fixing to the required profile and shape 2 layers of 12.5mm thickGypsum board on GI framework comprising 40x40x18G galvanized tubular frame 610x610mm centre to centre fixed on Roof Structure with 40x40x5 MS cleat, 100mm long 1200 c/c and ceiling framework with welded connections. The Gypsum board to be backed with 50mm thick resin bonded fiberglass cut to size and inserted in GI framework and held in place with 28G x 12mm GI wire netting. The first layer of Gypsum board to have joints over frame and second layer of Gypsum board tohave joint staggered with respect to the first layer, all joints between board in both layers to be taped with paper tape and filled with sealing compound. Gypsum board layer to be sealed at junction with Roof sheeting / structure and false ceiling below with the non-hardening mastic compound, so as to provide smooth surface.Entire work to be done as per drawing, specifications and as per directions of Engineer-in-charge and measured only sqm area and nothing shall be paid extra..
Providing & fixing full hight storage cabinets ( 600mm Deep ) made out of 18mm thick waterproof board (Refer Image) with 4 mm thick veneer of approved make & shade finished with polishing as required shutter in facia and balancing laminate all inside adjustable laminated shelves,20mm laminated groove. Rate should be inclusive of necessary Lock sets, self-closing hinges, spring loaded shutter latch inside,all cabinet hardware including locks to be approved make & as/Architects approval. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing refrigerator cabinate (600x600x850mm) with drawer made out of 18mm thick waterproof board (Refer Image) with 4 mm thick veneer of approved make & shade on external surface finished with polishing as required with shutter in facia and balancing laminate all inside adjustable laminated shelves, top of cabinate finish with italian stone. Rate should be inclusive of necessary hardware of approved make, & as/Architects approval. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. stone to be paid sepretly.
Providing & fixing luggage rack ( 600mm Deep ) made out of 18mm thick waterproof board (Refer Image) with 4 mm thick veneer of approved make & shade finished with polishing as required shutter in facia and balancing laminate all inside adjustable laminated shelves,20mm laminated groove. Rate should be inclusive of necessary hardware and SS strip at top be approved make & as/Architects approval. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing under counter storage with necessary drawers & Shelves as per design made out of 19mm thick HDHMR board fixed with the help of all necessary hardware like nail and fasteners and all internal surface of storage to be finished with 0.8mm thick laminate & external surface to be finished with 1mm thick laminate including required drawer unit, required shelves , shutters and required hardware like handle, knobs, magnetic catcher, drawer lock, hinges, shutter lock, drawer channel etc. all are superior quality of approved make complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing over head storage with necessary shelves as per design made out of 19mm thick commercial board fixed with the help of all necessary hardware like nail and fasteners and all internal surface of storage to be finished with 0.8mm thick laminate & external surface to be finished with 1mm thick laminate including required shelves, shutters and required hardware like handle, knobs, magnetic catcher, hinges, shutter lock etc. all are superior quality of approved make complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing Buffet Counter ( 600mm Deep ) made out of 18mm thick waterproof board (Refer Image) with 4 mm thick veneer of approved make & shade finished with polishing as required shutter in facia and balancing laminate all inside adjustable laminated shelves,20mm laminated groove & conter top finish with granite stone including grinding polishing & moulding complete. Rate should be inclusive of necessary hardware veneer, Laminate, granite stone and SS strip at top be approved make & as/Architects approval including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing Making & fixing wooden ledge as per design mabe of 19mm thick commercial board over existing RCC Slab including all fixing arrangement & finally fnished with Laminate of approved make & shade complete nothing shell be paid extra including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Single layer of 12mm thick Waterproof ply/ commercial ply fixed over existing MS tube frame work including all fixing arrangement Complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixixng 600mm dia Antique looking Mirror in Bed rooms as per approved sample including all fixing arrangement complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing beveled edge mirror of superior glass of approved make (thickness of glass as per technical specifications) and fixed to wooden cleats/rawl plug with C.P. brass/SS Stud screws and washers etc. all complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing frame work for partitions/ wall lining etc. made of 50x50x1.6 mm hollow MS tube, placed along the walls, ceiling and floor in a grid pattern with spacing @ 60 cm centre to centre both ways (vertically & horizontally) or at required spacing near opening, with necessary welding at junctions and fixing the frame to wall/ ceiling/ floors with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for opening for doors, windows, electrical conduits, switch boards etc., including providing with two coats of approved steel primer etc. complete, .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Make(TATA/Sail / jindal panther).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.Make(TATA/Sail / jindal panther ).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete..Make(TATA/Sail / jindal panther).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Electric resistance or induction butt welded tubes
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.Make (TATA/Sail / jindal panther).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Providing and fixing ornamental Metal Jali as per Design or as per approved by Architects on External walls over MS tube / Angle frame work including necessary clamps, Fastners, Scaffoldings required etc. all complete by specified vendor instrict supervision of manufacture including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Cost of MS tube / MS Angle shall be paid in basic item)
Providing and fixing colour coated metro sheet (1mm thick) of approved make and colour roofing sheet fixing over exising 12 mm thick Cement fiber board and MS frame (Cement fiber board & MS steel shall be paid saperately) with ridge of approved thickness J or L hooks, bolts and nuts 6mm dia metre with prepainted limpet and rubber washers accessories etc. all complete as per drawings or direction including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
25 mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .Granite of any colour and shade
Area of slab upto 0.50 Sqm
Area of slab over 0.50 Sqm
Providing and fixing 18 mm thick gang saw cut, Italian Marble of any colour and shade mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying machine cut, mirror polished Italian Marble stone Skirting, in required design (Simple geometrical, abstract etc.) and in patterns in combination with Italian marble stones of different colours, shades and finished surface texture etc., in linear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab laid over 12 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry @ 4.4 kg/sqm, including pointing with white cement slurry admixed with pigment to match the marble shade, including rubbing, curing and polishing etc. all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. 18 mm thick Italian Marble stone slab, Perlato, Rosso verona, Fire Red or Dark Emperadore etc.
Providing edge moulding to 18 mm thick Granite / marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharg.
Granite/marble work
Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharg.
Extra for providing hole of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in Granite work etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Mirror polishing on marble work/Granite work/stone work where ever required to give high gloss finish complete.including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharge.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conformingto IS : 15622, of approved make approved make (Somany/Nitco/ kajaria or equivalent) in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ Sqm including grouting the joints with white cement and matching pigments etc., complete. .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying wooden look like Vitrified tiles with (3 to 5)mm spacer for flooring, Skirting in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete Size of Tile 1200x200 mm including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make (Akio Wood Robble make somany)
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conformingto IS: 15622, of approved make (Somany/Nitco/ kajaria or equivalent) in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ Sqm including grouting the joints with white cement and matching pigments etc., complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Double Chargerd Size of Tile 1200x600x10mm make:-( Grande Persain crema make somany)
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conformingto I.S. 15622, of approved make (Somany/Nitco/ kajaria or equivalent), in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ Sqm including grouting the joint with white cement & matching pigments etc. complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.( Grande Persain crema make somany)
Double Chargerd Size of Tile 1200x600x10 mm make:-( Grande Persain crema make somany)
Providing and fixing Glazed subway wall tiles ( 300 x 100 ) conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. approved make (Somany/Nitco/ kajaria or equivalent)
Providing and laying machine cut, mirror polished, Italian Marble stone flooring laid in required pattern in linear portion of the building all complete as per architectural drawings, with 18 mm thick stone slab laid over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry @ 4.4 kg/Sqm including pointing with white cement slurry admixed with pigment to match the marble shade including rubbing, curing and polishing etc. all complete as specified and including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
18 mm thick Italian Marble stone slab, Perlato, Rosso verona, Fire Red or Dark Emperadore etc.
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified andincluding carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
In 75x75 mm deep chase
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying modular carpet of approved make and shade or as per approved by Architects and made with 100% nylon 6/6.6 tufted textured tip sheared/ cut & loop piles, tiles of minimum 500mm x 500mm in size, stain resistant, anti microbial, and having colour fastness to water, fastness to light, rubbing fastness and castor chair suitability as per relevant standard for heavy commercial usage, with PVC free backing, nominal total thickness of minimum 6.50 mm, pile height minimum 3.4 mm, minimum Total Pile weight – 800g/sqm). fixing with adhesive of approved make, all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & laying 30mm thick solid WPC planks 6" wide 7'-3" long flooring as per approved by Architects over Aluminium base frame 50mm x 50mm x 1.6mm thick @ of 600mm c/c and cross members @ 1500mm c/c fixed over existing kota stone flooring with help of aluminium cleat angles & fastners. The solid WPC planks shall have side grooves for fixing aluminium clip to fix the WPC members to base frame and to form groove on top surface for aesthetics. The aluminium clip shall be fixed to aluminium joists with self taping screws and sides of clips shall be inserted to side grooves of planks complete in all respect. The rate included cutting, finishing, level long, cleaning the site before & after the job, all leads, lifts & heights. The finished area in sqm shall be measured for payment. The rate is inclusive of all materials, labour, tools, tackles, machines , cartage etc. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing of high performance, heavy duty multi-use and multi-layer/heterogeneous vinyl Sports flooring of approved make, shade, design and pattern and in sizes as per manufacturer's specifications, or as per approved by Architects having minimum total weight of 4200g/m2 and minimum thickness of 6.5 mm, having performance parameters like sliding coefficient of friction, shock absorption, vertical deformation, vertical ball behavior, resistance to rolling load, abrasion resistance (Group T), Specular reflectance, specular gloss, resistance to indentation, impact resistance and slip resistance all as per EN 14904 or equivalent, fire classification of CfI-S1 as per EN 13501-1:2009 or equivalent, having low VOC and low formaldehyde compliant to GRIHA requirements, including laying and fixing of sheet with low VOC low formaldehyde adhesive as per manufacturer’s specification and sealing of joints between adjacent sheets by a hot air gun and PVC welding bar of matching shade as per manufacturer's specifications all complete as per drawings including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Extra for leatherite finish on granite stone insteade of polish finish including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing 60mm thick coloured pavement tiles / as per approved by Architects manufacturer with required fine sand under tiles & cement conc. 1:2:4 ( 1 Cement : 2 Coarse sand :4 graded stone aggregate ) on edge of pavement tiles complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.( Only Pavement tile area to be measured & paid)
Providing and fixing machine cut, mirror polished, Granite stone of approved shade in required pattern as per architectural drawings with 18 mm thick stone slab in riser of steps, skirting, dado, cladding and pillars laid on 12 mm (average) thick base of cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment to match the stone shade etc. all complete at all levels/floors as specified and including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & Laying Carpet Flooring of approved make including all fixing arrangement as per approved by Architects. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing Natural Cobbled Stone ( 100 x 100 x 25mm thick ) as per approved by Architects Flooring with 25 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry admixed with pigment of matching shade of stone including curing etc. all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & laying 12mm thick Laminated wooden Flooring as per approved by Architects with base 2mm thick foam including all fixing, & 100mm high skirting arrangement complete. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
PEDESTALS Pedestal Assembly : The pedestal of 25mm dia shall be of all steel construction, Zinc plated and consisting of an anti-vibration head cap with cruciform up stands and four panel locating studs, positively clipped to the steel top plate. Head cap shall be of adjustable type from 50 - 150mm Third party test certificate shall be provided for the Zinc coating Installation methodology : All pedestal shall be fixed to the floor with special adhesive and firmly anchored to the floor with suitable screws etc Axial load : 2200 kg without permanent deformation Overturning moment : 113 Nm PANELS Nominal size of floor panel : 600 x 600 mm Permissible thickness : 33mm Square ness/Flatness : +/- 0.2mm Variation in height : +/- 0.2mm Permissible Point Load : 4.5KN on a 25mmx25mm Square Permissible UDL : 1080 Kg/Sqm Factor of Safety : 3 Air Leakage : 0.44Lit/sec/m2 Fire Rating : Class ‘O’ Panel weight : 12 Kg Weight of system : 44Kg/m2 Top sheet thickness : 0.5mm Bottom sheet thickness : 0.5mm Core thickness : 30mm thick Cementations core Finish : 1.5mm/2mm thick Fire retardant floor grade Antistatic Laminate finish Panel installation type : The panels shall NOT be screwed onto the pedestals but shall have a self locking system to ensure stability of the finished floor and to give easy access to the cavity below False floor shall be inclusive of cut-outs with rubber gaskets/aluminium foils for cut-outs as per details.The cost shall include for heavy-duty MS powder coated Grommets as required The access floor panel must be positively grounded to the understructure, providing for less than 10 ohm resistance from the metal top of the panel to the bottom of the pedestal base where the building's grounding system is attached. Manufacturer to comprehensively address this problem by incorporating a solid brass Positive Grounding Device (PGD) in every panel as standard equipment. Note : The Electrical earthing connection for PGD is done by electrical Contractor.
300 MM HIGH RAISED FLOORING WITH ANTISTATIC LAMINATE FINISH including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing pebbles flooring of approved make & shade or as per approved by Architects with 2mm thick base foam including all fixing arrangement & required profile & skirting complete in all respect. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, filling, spreading & leveling coarse sand of size range 2.00 mm to 2.50 mm in recharge pit, in required thickness over gravel layer including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing plain multipurpose cement board(Hight pressure steam cured) with suitable screws for cement particle board in ceiling etc. complete (frame work to be paid seperatately).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
12 mm thick Cement fiber board as per IS: 14862
POP false Ceiling: Providing, fabrication and fixing in position of false ceiling ( height will be decided on the spot as per site conditions) as per design/drawing ( Plain/ Curved/ Arch/ in slope ) by fixing jali on frame work then Appling 12 mm to 15mm thick POP on Jali over frame work of GI sheet section. The main runners of 22 gauge GI sheet and cross runners of 24 gauge GI sheet must be framed to form a mesh of 2’0”x2’0” c/c. The POP must be Applied on jali fixed to the GI frame to get a smooth ceiling in line & level & finally finished with paint of approved make & shade complete. Rate inclusive of all material for POP False Ceiling i.e jali,G.I sheet frame work,POP etc, cutting of light opening, additional supports for light fixtures to hold the concealed light fixtures etc. directed by the site engineer including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Only Plain Area to be measured & paid and nothing shall be paid extra )
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :
12.5 mm thick tapered edge gypsum plain board conformingto IS: 2095- (Part I) : 2011 (Board with BIS certification marks)
12.5 mm thick tapered edge gypsum moisture resistant board
Providing & Fixing of Metal Galvanized Steel PLAIN metal ceiling System consisting of 600x600mm tiles of galvanized steel in 0.5 mm thickness in powder coated Global White color of 60-80 microns painted to a minimum of 120 gsm (both sides combined) galvanizing to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm & 600 mm Cross Tees.The tiles shall be in module size of 600 X 600/ 600x 1200/ 300 x 1200 mm, suitable for Green Building application, with Recycled content of 25%. The grid should be of 15mm wide T - section flanges color white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 38mm and a load carrying capacity of 15.43 Kgs/M. The T Sections have a Galvanizing of 90 grams per M2 having pull out strength of 100 Kgs. The Tile & Grid system used together should carry a 10 year warrantee.IINSTALLATION: To comprise main runner spaced at 1200mm centers securely fixed to the structural soffit using GI angles of 25x25x0.5/0.6mm or M8 threaded rods at 1200mm maximum centre. The First/Last suspension system at the end of each main runner should not be greater than 450mm from the adjacent wall. Flush fitting 1200mm long cross tees to be interlocked between main runners at 600mm centre to form 1200 x 600 mm module. Cut cross tees longer than 600mm require independent support. 600 x 600mm module to be formed by fitting 600mm long flush fitting cross tees centrally between the 1200 mm cross tees. The tile is engaged on the exposed grid system. Perimeter trim to be wall angles of size 3000x19x15mm, secured to walls at 450 mm maximum centers Rate inclusive of all material i/c frame work including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.(Only metal ceiling tile area to be measured & paid nothing shall be paid extra)
Providing and fixing Veneer false Ceiling with or without grooves with base skin of 12mm thick Waterproof ply with appropiriate GI frame work with Wooden battens inside GI frame work for extra supports & making cut-outs, holes etc:, for lights and complete with all fixing, hanging arrangement, hardware in all respect & Finally finish with veneer of approved make & polishing complete in all respect Rate inclusive of all material i/c frame work including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Only Plain Area to be measured & paid and nothing shall be paid extra ).
Providing and fixing acoustic ceiling tiles having noise reduction co-efficient (NRC) of 0.90 Measurement of sound absorption coefficient in a reverberation room according to EN ISO 354 room method testing, light reflectance 85% and humidity resistance of 95%. Fire classifications for the tiles should be according to class B s1 d0 according to UNE-EN 13501-1: 2007. Tiles should be ecology friendly , confirm to international enviormental standards & totally recyclable Rate inclusive of all material i/c frame work. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing Veneer Paneling as per design on wall with 12mm thick waterproof ply over existing MS Frame work & finally finish polishing as required complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.. ( Base Rate of Veneer @ Rs. 150/- Sqft ).
Provideing & fixing PVC ribbed Paneling as per design on wall over existing wall ( without frame work ) including all fixing arrangement complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.. ( Base Rate of PVC Ribbed Panel @ rs. 210/- Sqft )
Providing & fixing Acoustic Paneling on wall as per design made of MS Frame work then fixed 12mm thick waterproof ply & finally finished with Acoustic panels of approved make & shade complete with all material & labour including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing 25 x 25mm 2nd class teak wood moulding as per design including all fixing arrangement & finally finish with polishing as required complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing, fitting & fixing HPL strip Cladding (exterior grade) of work made out of 1"X1.5" almunium section frame work. The sections are to be placed 600mm c/c. 6mm HPL to be nailed over the suface of the frame work as per design approved by architect. The edges to be covered with decorative beading, including two coat of waxpolish to superior finish,including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge(Cost of aluminium tube shall be paid in basic item)
12 mm cement plaster of mix :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1:4 (1 cement: 4 coarse sand)
15 mm cement plaster on rough side of single or half brick wall of mix:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1:4(1 cement: 4 coarse sand)
15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of mix :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1:4 (1 cement: 4 coarse sand)
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:4 (1 cement : 4 fine sand).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
6 mm cement plaster of mix :.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1:3 (1 cement : 3 fine sand)
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and applying plaster of paris putty of 10 to 12 mm thickness over plastered surface to prepare the surface even and smooth complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
New work (two or more coats) over and including water thinnable priming coat with cement primer
Finishing walls with textured exterior paint of required shade .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make(Asian or Nerolac)
New work (Two or more coats applied @ 3.28 ltr/10 Sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 Sqm
Finishing walls with textured internal paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of internal primer applied @ 2.20kg/10 sqm including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Finishing walls with Acrylic Smooth exterior paint of required shade .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make(Asian or Nerolac)
New work (Two or more coat applied @ 1.67 ltr/10 Sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 Sqm)
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make(Asian or Nerolac)
New work (Two or more coats applied @ 1.43 litre/ 10 Sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 Sqm.
Finishing walls with 100% Royal emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives.New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Applying priming coat:With ready mixed pink or Grey primer of approved brand and manufacture on wood work (hard and soft wood) .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make(Asian or Nerolac)
Applying priming coat : With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make(Asian or Nerolac)
Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture
Expose Ceiling Area Paint with Base Bila Putty on GYM Area, Pool Table area and Caram area as per Design or as per approved by Architects including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conformingto IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
For fixed portion Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron) including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ Sqm)
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conformingto IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
With brass cover plate minimum 1.25 mm thickness
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary screws etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Polyester powder coated minimum thickness 50 micron aluminium
Providing and Placing in position suitable PVC water stops conformingto IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Serrated with central bulb (225 mm wide, 8-11 mm thick)
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including: (a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. (b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. (c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium
item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Toughened glass 6 mm thickness
Providing and fixing 32 mm dia D- type min 750mm long brush/matt finish Stainless steel grade-304 pull handles of approved make with necessary screws etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing, fitting & fixing HPL Cladding (exterior grade) of work made out of 1"X1.5" almunium section frame work. The sections are to be placed 600mm c/c. 6mm HPL to be nailed over the suface of the frame work as per design approved by architect. The edges to be covered with decorative beading, including two coat of waxpolish to superior finish, including cost of all labour & material etc. all complete as per direction of engineer-in-charge. (Cost of aluminium tube shall be paid in basic item) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Extra for making ACP sheet jali by CNC machine of pattern approved by architect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
METAL FIRE DOOR Providing and fixing of Metal Fire door from ISO 9001:2015 certified Manufacturer. Fire doors must satisfy the requirement of latest NBC 2016 Part 4 for Fire & Life Safety guidelines for 120 minutes Fire Rating. The Prototype sample of the door must carry a prior test evidence as per IS 3614 part-2 / BS 476 Part 20 & 22 . The manufacturer must submit the copy of test evidence prior to start of production .The offered test certificate should either carries it's Validity or certificate must not be older than 5 years from CBRI / NABL Accreditated Lab i.e Spectro / International Lab i.e Exova / TBW/equivalent etc . Recommended fire door must also been certified by a third party evaluation program from approved International agency like IFC/ Intertek/ Certifire/equivalent and must carry a lable on all doors . All doors should be finished with Powder coating in desired regular RAL Shades. Door frame shall be Single/double rebate profile of approved section made out of 1.6mm thick galvanised steel sheet with a factory pre-punched groove so as to accomodate Fire & smoke seal size 10x4mm . Frames should be butt jointed and field assembled with bolting system for proper strength .Frames should be provided with back plate for anchor fasteners for installation on a finished plastered wall opening. The Air gap between Wall and frame can be filled with fire retardant sealant. Door leaf should be minimum 46mm thick fully flush double skin door. Door leaf must be manufactured from 1.2 mm (18 guage) thick galvanised steel sheet. The door should be provided with reinforcement pads to receiving appropriate Hardwares of Becker Fire Solutions/Assa Abloy/Yale/Coburn/Geze or Equivalent make. The Shutter shall be filled with Honeycomb paper core, mineral wool infill material with Proprietary insulation. For Double leaf doors; astragal has to be provided on meeting stile for both active and inactive leaf. Vision panels wherever required should be of 120 minutes fire rating and should be of non-wired type having 20mm thick black border. All glavanised steel must be zinc coated not less than 120 kg/cum. All approved FR rated hardwares - tower nolts,FR glass, D- handle(SS finish), Concealed Automatic Flush Bolt, Panic bar with external trim, SS ball bearings, FR glass,Fastener with PVC caps, cylindreical/dead/mortice latch lock,etc complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Structural Glazing shall be designed for minimum wind pressure @ 200Kg/ Sqm for straight glazing..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Providing and fixing Structural Glazing consisting of fixed panel as per the elevation drawings enclosed, fabricated out of colour coated heavy duty aluminium extruded profiles anodized (25micron) as per approved shade. All aluminium members & profiles shall be of AC 25 grade as per specification. The Aluminium members shall be protected with Masking Tapes all around the profiles for safety against external scratches at site (Masking Tapes shall be removed only at the time of handing over as per the instructions of Project Manager). The wind pressure mentioned above is minimum design pressure. Incase the design wind pressure required as per the NBC for the zone of the building or site condition or due to building profile is higher, then the Contractor shall design the Structural Glazing for higher wind pressure. The Contractor must quote rates accordingly. No extra claims shall be entertained at any stage for change in aluminum profile wall thickness, size & dimensions. The anchoring/ bracing of the glazings to the RCC slab/ beams/ columns shall be done with required no. of Stainless Steel extended brackets of approved design with approved dash fasteners of minimum 12mm dia and depth of minimum 100mm in the concrete and Stainless steel bolts including providing and fixing of aluminium shims of various thickness to adjust the beam level & line variations. The anchoring system shall be designed to withstand the dead load of the Structural wall as well as stresses due to wind pressure etc.
The glazing frame shall be aligned for each vertical mullion for the entire height and for each Transom for the entire width horizontally by lazer beam equipment to ensure 100 percent 'X' axis and 'Y' axis alignment. To make the joints water & air tight, the glazing framework shall be provided with approved in-built ventilation and drainage system. All the joints of the Structural Glazing system & the perifery of glass & Inner side frame with walls / column shall be properly sealed with specified weather silicon . The details for in-built ventilation & drainage system to be submitted by the contractor and got approved by the Project Manager. The Structural Glazing system should also provide for pressure equalisation. The details for pressure equalization to be submitted by the contractor and got approved by the Project Manager. EPDM gaskets of suitable profiles to accommodate glasses in all the vision areas shall be provided at all glazing area to make the glazing water & air tight including providing & fixing of pressure plates & cover plates. The contractor shall provide the connectivity for Lighting Protection system in the Structural glazing as per the International Standard and shall also give the requirement of earth pits for the Lighting protection. Structural Glazing as above with single panels of 8mm thick synergy clear glass of approved make duly toughened. Rate inclusive of all material (Only Plain Area to be measured & paid and nothing shall be paid extra )
Providing and fixing in position 25 x 25mm Aluminium L-shaped corner guard, Powder Coated finish in Customer upto ceiling from FFL, fixing to be done as per vendor drawing .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Kiosk Counter made of block work partition wall finish with subway tile at front & corian stone at top & internal side commercial tile . Rate inclusive of all required material Labour, Griding buffing polishing, edge moulding, fixing arrangeent complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing making & fixing Sinage Board as per Design or as per approved by Architects Made of MS Frame work including civil work i,e Excavation, PCC, RCC, MS Frame work, Cutting, Welding & finally finished with paint of Approved make Complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing making & Fixing Fountain as per design or as per approved by Architects including civil ,Plumbing work, or Reuired mortor for fountain Etc including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & Fixing Stone Statuo as per design or as per approved by Architects including all fixing arrangement including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Expension Joint Treatment for floor for 100mm Gap Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Material shall confirm to ASTM 6063).
Expension Joint Treatment Straight / L- Type for walls Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-InCharge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge (Material shall confirm to ASTM 6063).
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density) including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Providing and laying design mix cement concrete of M-30 grade, Pavement quality concrete (PQC) in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 20 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars 25mm dia 300mm spacing with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel for work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg. (Item of joint fillers, sealants, to be paid separately).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Note:- Cement content considered in M-30 is @ 340 kg/Cum. Excess/ less cement used as per design mix is payable/ recoverable separately.Cement concrete prepared with batch mixing machine
Providing and fixing in position pre-moulded joint filler in expansion joints. .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying in position bitumen hot sealing compound for expansion joints etc..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Using grade ‘A’ sealing compound.
Providing and applying 2.5 mm thick road marking strips (retro- reflective) of specified shade/ colour using hot theRmtoplastic material by fully/ semi automatic theRmtoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge) including carriage of material by mechanically & manual upto all lead & lift and as perdirection of Engineer incharg.
Construction of granular sub-base by providing close graded Material conformingto specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in unifoRmt layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
With material conformingto Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30
Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conformingto IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/Cum, optimum moisture content to be deteRmtined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 10x10x7.50 cm Granite stone block hand cut and chisel dressed on top, for paving in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints 10mm wide filled with same mortar including ruled pointing etc. complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing stone textured concrete paver tiles (M-40 grade) of approved size and approved sample, for paving in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints 10mm wide filled with same mortar including ruled pointing etc. complete .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
(40 to 80 )mm thick Grey/Beige or any approved shade / thickness and shade as per approved by architect.
Providing, laying and fixing of precast suacer drain (solid) of size 600x300x70/100 mm (thickness 70mm at curve portion in centre & 100mm at both side) jointed with 1:3 cement mortar (1 cement : 3 coarse sand )over the base of 20mm thick cement mortar 1:4 ( 1 cement : 4 coarse sand) in slope, line & level as shown in drawing and manufactured by M-30 grade of concrete by vibro compaction process using joint less FRP moulds so as to achieve shuttering finish etc. all complete under instruction of engineer-in-charge..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing, laying and fixing of precast suacer drain (Perforated with 4 holes) of size 600x300x70/100 mm (thickness 70mm at curve portion in centre & 100mm at both side) jointed with 1:3 cement mortar (1 cement : 3 coarse sand )over the base of 20mm thick cement mortar 1:4 ( 1 cement : 4 coarse sand) in slope, line & level as shown in drawing and manufactured by M-30 grade manufactured with M 30 grade of concrete & reinforced with 8 mm dia steel at 100 mm c/c bothways by vibro compaction process using joint less FRP moulds so as to achieve shuttering finish etc. all complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing PVC Drain Cover as per approved sample for Swimming Pool Drain including all fixing arrangement including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing peRmteability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product perfoRmtance shall carry guarantee for 10 years against any leakage.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
For vertical surface two coats @ 0.70 kg per Sqm
For horizontal surface one coat @1.10 kg per Sqm.
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge (i) Ist course of applying cement slurry @ 4.4 kg/Sqm mixed with water proofing compound conformingto IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. (ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per Sqm of area. (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to Each other with bitumen @ 1.7 kg/Sqm).
Providing and fixing 24gauge x 19 mm size galvanized chicken wire mesh to junctions of concrete and masonary work and other locations where called for including cutting to required sizes side laps of minimum 75 mm and fixing in position with necessary clips and U shaped glavanised wire nail etc.complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing certified restroom cubicle system of approved make comprising of green guard certified solid compact laminated water proof board, 18-12 mm thick made as per IS: 2046 (phenolic core board) and as per BS-476/97 for fire retardant for toilet showers, water closet etc . The board shall be manufactured under high pressure and temperature by impregnating kraft papers and outer decorative papers with theRmtosetting phenolic/ melamine resins (low VOC). The cubicle system shall be resistant towards water, chemical, scratch, impact and heat and shall be anti bacterial, colour fast and shall have accessories like door knob, Gravity/ auto return hinges, privacy thumb turn with occupancy indicator, coat Hook, etc all in SS 304. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. The hardware and fixings includes anchoring of all fixed front panel to floor with SS 316 L brackets/ base plates with a clearance height 100 mm to 150 mm, and covered with SS 316 Shoe box plates, wall and corner joineries (brackets and channels) shall be SS 304 grade, SS 304 screws, rubber noise reduction tape . The cubicle unit shall be installed in approved finish, shades and colours as per specifications and directions of Engineer-In-Charge, including minimum 5 (five) years warranty against any moisture related damages to all inteRmtediate panels, doors, hardqwares etc. Standard dimension of the cubicle system shall be of approx. 2100 mm Height (overall) x 1500mm Depth and 900 mm to 1100 mm Width which includes minimum 600 mm door size width.
18mm thick front panel including door and all necessary accessories, fittings and hardware etc.(measured from floor to top rail)
12mm thick divider / intemediate panel including all necessary accessories, fittings and hardware etc.(measured from floor to top rail)
Seed Grassing with Special Grade -1 grass including watering and maintunance of the lawn for 30 days or more till the grass form a thick lawn free from weeds and fir for movoing including supplying good earth /manure needed including carriage of materail in all ledas and lifts as per the direction of Engineer in Charge.(in Row 5 cm aprat)
Planting permanent hedges including digging of trenches, 60 cm wide and 45 cm deep, refilling the excavated earth mixed with farmyard manure, supplied at the rate of 4.65 cum per 100 metres and supplying and planting hedge plants at 30 cm apart complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Sprinklar system all around the ground including entire carriage of materials within all leads and lifts and as per drawings and technical specifications as per the direction of Engineer-in-Charge including all pipes or incidentals.The rates are inclusive of octroi, royality, malkana, toll tax, sale tax, GST or other taxes imposed by the Government.
Providing and laying Royal Palm Tree including entire carriage of materials within all leads and lifts and as per drawings and technical specifications as per the direction of Engineer-in-Charge including all incidentals.The rates are inclusive of octroi, royality, malkana, toll tax, sale tax, GST or other taxes imposed by the Government.
SANITARY INSTALLATIONS Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100mm sand cast P or S trap, 10 Litre low level P.V.C. flushing cistern with manually controlled device(handle lever) conformingto IS:7231, with all fittings & fixtures complete including cutting and making good the walls and floors wherever required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
White vitreous chinaOrissa pattern W.C. pan of size 580x480mm with integral type foot rests.
Providing and fixing P.V.C waste pipe for sink or wash basin including P.V.C waste fitting complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .Flexible pipe
40 mm dia
Providing and fixing 100mm sand cast iron grating for gully trap.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 1200x1500mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make (Jaquar or equivalent)
Providing and fixing 600 x 120 mm glass shelf with CP brass brackets and guard rail complete, fixed to wooden cleadts with CP brass screws.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make (Jaquar or equivalent)
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent aRmt complete, including cost of cutting and making good the walls and floors ..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge 100 mm inlet and 100 mm outlet.
Sand cast iron S&S as per IS: 3989
Supply, installation and commissioning of 'FLORANTINE- WALL HUNG WC, CISTERN AS PER WC Model No; FLS-WHT-5953- JPPSM- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of 'BUILT IN BATH TUB Model No; JBT-WHT-FONT170FX:- with drain pipe & filter Model: JWA-CHR-132201:Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''HEALTH FAUCET Model No;ALD-587- Jaquar or equivalent. Item includes all hardware required for installation. .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''FUSION- SPOUT Model No;FUS-29231- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''CP WASTE JALI Model No;ALD-729- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''BOTTLE TRAP (WITH INTERNAL PARTITION) 32 MM SIZE WITH 250 MM & 190MM LONG WALL CONNECTION PIPES Model No;ALD-769L250x190- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''ANGULAR STOP COCK WITH WALL FLANGE Model No;VGP-81053- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''SOAP DISPENSER WITH GLASS BOTTLE Model No;AKP-35735P- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''GRAB BAR Model No;ACN-1101SP- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''TISSUE PAPER HOLDER Model No;ACN-1121BN- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''TOWEL RING Model No;ACN-1121BN- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''FLUSH PLATE Model No;JCP-CHR-152415- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''COAT HOOK Model No;ACN-1161N5- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''EXPOSED PARTS OF FLOOR MOUNTED SINGLE LEVER BATH MIXER Model No;OPP-5121KPM- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''UNDER COUNTER BASIN, Model No;CNS-WHT-701- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''QUARTER TURN PILLAR COCK, Model No;VGP- 81001- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''WALL HUNG WC, Model No;FLS WHT-5953PPSM- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''URINAL, Model No URS-WHT-13261- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''URINAL PARTITION, Model No 1810-UC / 1110 UC- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation and commissioning of ''HAND DRYER, Model No HDR-SSF-AK-2807- Jaquar or equivalent. Item includes all hardware required for installation..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing C.P. bass angle valve for basin mixer and geyser points of approved quality conformingto I.S:8931 a) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. 15 mm nominal bore
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand), R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation in cement concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design :.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Inside size 90 x 80 cm and 45 cm deep including C.I. cover with frame (light duty) 455 x 610 mm internal dimensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg). .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge . With common burnt clay F.P.S (non - modular) bricks of class designation 7.5
Extra for depth for manholes With common burnt clay F.P.S (non - modular) bricks of class designation 7.5 .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Size 90x80 cm
Providing and constructing brick masonry chamber for undergroundCI inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) R.C.C. top slab with 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design :Inside dimensions 455x610 mm and 45 cm deep for single pipe line :With common burnt clay F.P.S (non - modular) bricks of class designation 7.5 .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge . :- Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 deep for pipe line with one or two inlets :
Providing and constructing brick masonry chamber for undergroundCI inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) R.C.C. top slab with 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design :Inside dimensions 455x610 mm and 45 cm deep for single pipe line :With common burnt clay F.P.S (non - modular) bricks of class designation 7.5 .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge . :- Inside dimensions 600x 850 mm and 45 cm deep for pipe line with three or more inlets :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth beyond 45 cm of brick masonry chamber:For 455x610 mm size With common burnt clay F.P.S (non - modular) bricks of class designation 7.5 including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
For 500x700 mm size With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
For 600x850 mm size With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 Rmt depth below ground level.Rocky strata including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Boulders 300 mm dia
Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RmtS) pipes with ribs, conformingto IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths,including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
150 mm nominal size dia
Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer,for all leads & lifts, all complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Providing, fixing, testing & commissioning uPVC SWR pipes (Type-B) for soil, waste and vent conforming to IS 13592-1992 along with all required fittings like tees, bends, cowls, crosses with or without access doors jointed with approved solvent cement fixed to walls and ceilings including angle supports with clamps complete including cutting holes in R.C.C/brick work (slab/beam/wall) and making good the floors, beams and walls with cement mortar where required complete of outer diameter.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
75 mm (OD) SWR Pipe
110 mm (OD) SWR Pipe
160 mm (OD) SWR Pipe
Providing, fixing & testing of UPVC pipes (IS : 4985- latest, class-3, 6 Kg/cm2 pressure) including injection moulded fittings (heavy duty) (plain or door) e.g. bends, junction, cowls, tees, offsets, access pieces etc. Clamps/Supports jointing with rubber ring/solvent cement joints including cutting chase or holes in walls and floors and making good as required at Site.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (For Kitchen) make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
Providing and fixing uPVC inlet fitting (Hopper) maximum 3 inlets 32, 40 or 50 mm size fabricated from 110 OD uPVC pipe fixed to uPVC trap jointing with solvent cement joint and set in a cement concrete 1:2:4 mix complete including cost of cutting and making good the walls and floors wherever required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing UPVC, P or S trap of self cleaning design with / without vent arm setting in cement concrete 1:2:4 mix complete including cost of cutting & making good the wall / floors wherever required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
110 mm inlet & 110 mm outlet
Providing, fixing, testing and commissioning of uPVC cleanout plug conforming to IS:14735 – 1999 complete with all fitting, accessories and civil works.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing, fixing & testing uPVC pipes, conforming to IS 4985 class 5 (10 kg/cm2) including injection moulded fittings, jointing with solvent cement, cutting and making good the floors and walls and jointing to trap/waste pipe, complete of outer dia.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
40 mm dia.
50 mm dia.
63 mm dia.
Providing and fixing uPVC floor drain with uPVC reducing elbow including all fitting and accessories fixed in cement mortar complete in all respect.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
110 mm x 63 mm
Providing & fixing 1 mm thick stainless steel grating with rim of approved design including setting in floor with cement mortar.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (For Trap and Floor Drain)
125 mm dia
100 mm dia
Providing and fixing in position stainless steel cockroch trap consisting of 0.45 mm thick inner and outer cup and 1.00 mm thick top grating (Jali) with ring to be fixed inside C.I. or uPVC ‘P’ traps with cement concrete. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying cement concrete 1 : 2 : 4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) 75 mm in bed and alround uPVC soil & waste pipes including excavation, refilling where required complete in all respect as per standard design.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Pipe 90 to 160 mm OD
Pipe 32 to 63 mm OD
Providing and fixing straight/offset type Macfit single body push fit type WC Pan Connector with factory supplied spring loaded seal guard with integrated single mould sealing fins made of flexible EVA Body, including bush/adaptor for use with CI Pipe as supplied with Pan Connector including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.(For European water closet)
Providing, fixing & testing of UPVC rain water pipes (IS : 4985-1983 class-3, 6 Kg/cm2 pressure) including injection moulded fittings (heavy duty) (plain or door) e.g. bends, junction, cowls, tees, offsets, access pieces etc. Clamps/Supports jointing with rubber ring/solvent cement joints including cutting chase or holes in walls and floors and making good as required at Site.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
160 OD (with excavation)
Providing and fixing of C.I. Grating including all fitting and accessories and cutting and making good the walls, floor and R.C.C. work complete (For Balcony & Terrace Rain Water Pipes).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm x 150 mm, 10 mm thick
Providing and laying cement concrete 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate, 20 mm down gauge) 75 mm thick in bed and all around UPVC Rain water pipes burried under floor, including shuttering and centering for complete in all respects (For Burried Rain Water Pipes/Connection to CB)..including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing & commissioning of GI pipes and fittings conforming to IS : 1239 (heavy class) with fittings, union, makes chases in wall and making good the same in cement mortar 1 : 2 (1 cement : 2 coarse sand) as directed by Project manager, complete in all respects including painting with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including all steel work.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Drainage/Sewage Sump Riser)
Providing and constructing oil and grease separator chamber 1500x 900mm with required depth inside with 75 class designated brick work in cement mortar 1:6 (1cement : 6 fine sand) with 560mm dia C.I double seal medium duty manhole cover (2Nos.) top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20mm nominal size) with minimum 1.5% reinforcement foundation concrete 1:5:10 (1cement: 5 fine sand and 10 graded stone aggregate 20mm nominal size including two brick masonry baffle walls, with necessary excavation, back filling and disposal of surface earth compete with inlet, outlet, PVC coated foot rest.
Supply, installation, testing and commissioning of HDPE Pipe PE-100 Material grade, PN 6 (6.00 Kg/cm2) pressure rating conforming to IS : 4984 - 1995/ISO : 4427-1996 (E) including heavy duty Electro welded fitting such as reducers, tees, bends, flange, clamps including sand Bed of 150 mm thick laid as per manufacturer recommendation etc. (STP Bypass to authority Sewer)
Providing & fixing thermal insulation on hot water pipes a flexible elastomeric foam of closed cells structure having thermal conductivity of 0.038 W/M.K at 40o C, water vapour permeability fire propagation including all accessories e.g. adhesive and ape on joint complete as per specification. All joints shall be sealed with adhesive & cotton tape.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
15 mm (6mm thick insulation)
20 mm (6mm thick insulation)
25 mm (6mm thick insulation)
Providing & fixing thermal insulation on hot water pipes, a flexible elastomeric foam of closed cells structure having thermal conductivity of 0.038 W/M.K at 40o C, water vapour permeability fire propagation including all accessories complete as per specification. All joints shall be sealed with adhesive & cotton tape, shall be applied to give uniform appearance & finished with polished protective coating.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
15 mm (9 mm thick insulation)
20 mm (9 mm thick insulation)
25 mm (9 mm thick insulation)
32 mm (9 mm thick insulation)
40 mm (9 mm thick insulation)
50 mm (9 mm thick insulation)
20 mm (13 mm thick insulation)
25 mm (13 mm thick insulation)
32 mm (13 mm thick insulation)
40 mm (13 mm thick insulation)
50 mm (13 mm thick insulation)
65 mm (13 mm thick insulation)
80 mm (13 mm thick insulation)
Making khurras with average minimum thickness of 5 cm cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1m x 400m, finished with 12 mm cement plaster 1 : 3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges, making and finishing the outlet complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Khurras with CI grating, Size :300 x 300 mm
Providing and fixing CPVC (Chlorinated Poly Vinyl Chloride) pipes conforming to CTS-SDR 11.0 OR SCHEDULE 80 complete with CPVC fittings e.g., couplings, elbows, tees, crosses, union, transition union,reducers, SCREWED metal end fittings/adopters, powder coated metal strap claps etc. including necessary cutting of pipes, jointing with CPVC solvent cement conforming to ASTM-493 including cutting and making good the walls, floor etc. complete with testing, commissoining and disinfection of pipe lines.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
15 mm nominal bore
20 mm nominal bore
25 mm nominal bore
32 mm nominal bore
40 mm nominal bore
50 mm nominal bore
65 mm nominal bore (Schedule 80)
80 mm nominal bore (Schedule 80)
100 mm nominal bore (Schedule 80)
Providing and fixing forged brass nickel plated lever operated ball valve (PN 10) of full flow with forged brass hard chrome plated ball. Lever should be anti rust coating, complete in all respects including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.(For Domestic, HWS/ROWS Application).
15 mm dia
20 mm dia
25 mm dia
32 mm dia
40 mm dia
50 mm dia
Providing and fixing cast iron double flanged butterfly valve (PN 10) complete with 2 nos. matching flanges, bolts, nuts, 3.0 mm thick compressed asbestos gasket.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
65 mm dia
80 mm dia
Disinfecting water mains by domestic & Flushing with water containing Bleaching Powder at 0.5 gm per liter of water and cleaning the same with fresh water, operation to be repeated three times including getting the samples of water from disinfected main tested in the municipal laboratory.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing dual plate wafer type C.I. non-return valve conforming to IS: 5312 rated to PN 1.6. with bolts, nuts, 3mm thick gasket and matching flanges as per table 'E' complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
50 mm dia
65 mm dia
80 mm dia
Providing, fixing and calibration of PRV including Ball valve with piping and fittings. Gunmetal or brass pressure reducing valve of approved model on inlet line of each toilet and kitchen inside the shaft on appropriate location as specified in drawing including all type of fittings such as reducers, enlarger, nipples, unions,etc complete in all respects. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
20 mm dia
25 mm dia
32 mm dia
40 mm dia
50 mm dia
Providing and fixing gunmetal non-return valves vertical or horizontal tested to 15 Kg/cm2 as per IS:778.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
15 mm dia
20 mm dia
25 mm dia
32 mm dia
50 mm dia
Providing and fixing forged brass auto air vent valve PN 10 rating including all fitting & accessories.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
15 mm dia
Providing, fixing testing & commissioning of IP 67 (Weather Proof /Aluminum casing with positioner to indicate the valve position with key type manual overdrive) motorized Butterfly/ Ball valve (with by pass line) with float type sencors suitable for 240 volt with working pressure rating not less than 5 Kg/cm2 with control panel and sensors to open valve when water level is low in tanks and to close when water level is high in water tanks including necessary cables,conduits upto junction box,pipe butterfly/ball valves etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Size of valve 40 mm
Size of valve 50 mm
Providing & fixing digital type water meter with direct reading dial in KL all internal parts in gunmetal or brass, butterfly valve, strainer, flanged distance piece for easy removal in future, Bourden type pressure guage and isolation cock including necessary test certificate for the meter from local municipal authorities.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
25 mm dia
32 mm dia
Providing and fixing cast iron double flanged butterfly valve (PN 16) complete with 2 nos. matching flanges, bolts, nuts, 3.0 mm thick compressed asbestos gasket.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
65 mm dia
80 mm dia
100 mm dia
Providing, fixing, testing and commissioning of cast iron dual plate type check valve PN 16 rating (16 kg/cm2 pressure rating) conforming to IS :5312 complete with 2 nos. matching flanges, bolts, nuts, washers 3 mm thick insertion neoprene gasket. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm dia
Making connection to existing city water main including excavation, bailing out water and filling back the excavated earth & C.I. water meter chamber cover, cutting & threading the pipe etc. getting approval from concerned authorities. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Hydro dynamically balance Flow meter/multi-jet magnetic drive (turbine type) water meter conforming to IS : 2373/ECC/ISO Standard with direct reading dia in Kilo-liter with all internal part in Gun metal or brass, strainer, flanged distance pieces for easy removal, 100 mm dia burden type pressure gauge with isolation cock complete including necessary test certificate for the meter from local municipal authorities.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
80 mm dia
Providing, fixing, testing & commissioning of Forged Brass air release valve including all fitting & accessories.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
25mm dia
Providing, laying and jointing light duty non-pressure NP2 class S/S R.C.C. pipes with collars jointing with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including curing, testing of joints etc. complete in all respects.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
200 mm dia
250 mm dia
300 mm dia
Providing and laying 150 mm thick cement concrete 1:5:10 mix ( 1 cement : 5 coarse Sand : 10 graded stone aggregate 40 mm nominal size) alround RCC pipe including bed concrete 150 mm as per standard design.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm dia
200 mm dia
260 mm dia
300 mm dia
size, filling in recharge pit 300mm thick of 40-65mm nominal size graded stone aggregate, 300mm thick small stone 5-10mm and 300mm thick sand layer respectively as mention in detail drawing, 160mm dia uPVC slotted pipes 6kg/sq cm working pressure i/c fittings with a minimum depth as mensioned in recharge pit standard detail drawing. fillling around the slotted pipes and packing 3mm to 6mm sized graded and screened rounded pea gravel duly washed fabricating and placing grating at the mouth of pipes, 300mm thick brick bat layer at bottom of desilting chamber, placing 560mm dia SFRC manhole cover with frame etc. i/c all necessary materials and equipments required for all relevent operations as shown in the drawing.
size, filling in recharge pit 300mm thick of 40-65mm nominal size graded stone aggregate, 300mm thick small stone 5-10mm and 300mm thick sand layer respectively as mention in detail drawing, 160mm dia uPVC slotted pipes 6kg/sq cm working pressure i/c fittings with a minimum depth as mensioned in recharge pit standard detail drawing. fillling around the slotted pipes and packing 3mm to 6mm sized graded and screened rounded pea gravel duly washed fabricating and placing grating at the mouth of pipes, 300mm thick brick bat layer at bottom of desilting chamber, placing 560mm dia SFRC manhole cover with frame etc. i/c all necessary materials and equipments required for all relevent operations as shown in the drawing.
Making connection of storm water line with external (Trunk line) manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1cement: 3 Coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete.
Providing & laying UPVC pressure pipes of 10 Kg/Sq.cm pressure rating class V (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead up to 100m complete, compaction and consolidation Including sand bedding all around UPVC pipe & fittings and thrust blocks at bends as per standard design.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.make( Finolex, Diplast, supreme, Astral or approved by Engineer incharge )
Providing and fixing forged brass body quarter turn lever operated ball valve with forged brass hard chrome plated ball, disc & gland packing shall be PTEF tested to 25 Kg/Sq.cm pressure including GI nipple and threaded hose receiver complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
25 mm nominal bore
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910 on 12 mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30 x 20 x 15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing and commissioning of DWC HDPE SN-4 Pipe (Nominal size) IS:16098 part-2 for Storm water Drainage jointed by click ring & sealing ring/ solvent cement joint including testing of joints, setting right the leaking of joints etc. complete as per instructions of the Engineer-In-Charge.
150 mm dia
200 mm dia
Making connection of Sewer water line with external (Trunk line) manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1cement: 3 Coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Excavating trenches of required width for pipes, cables, etc including excavation for sockets also including for cement concrete cradles, and dressing of sides, ramming of bottoms, depth up to 1.5m including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer with minimum 95% by ramming, watering etc. and disposing off surplus excavated soil .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing & commissioning of R.O. unit of 500 LPH (net output) capacity as per following specification :- Input Water Quality : Total Dissolved Solids (TDS) : 500-2000 mg/l, Total Hardness (as CaCO3) [After Filtration & Softening] : 150 mg/l as CaCO3, Residual free chlorine : Nil, Iron (as Fe) : 0.044 mg/l,Chlorides (as cl) : 78 mg/l,Iron (as Fe) : 0.044 mg/l, Fluorides : Nil, Output Water Quality : Total Dissolved Solids (TDS) : < 150 mg/l, Total Hardness (as CaCO3) : 50 mg/l as CaCO3, Turbidity : < 1, System Recovery > 60-70%. Pump, Equipment, Piping & Accessories :- Micron Cartridge Filter, Antiscalent Dosing System,SMBS Dosing, Sodium Hypochlorite Dosing, Acid Dosing, R.O. High Pressure Pump, "R.O. Modules (R.O. membrane + R.O. pressure tube), R.O. Cleaning System, Instrumentation & Electrical work, Low Pressure Side Piping, Valve & Accessories. High Pressure Side Piping, Valve & Accessories. RO water storage tank of capacity 1000 liters. Supplying complete testing kit with all chemicals complete suitable for conducting test on water quantity. The test kit shall be suitable for measuring, TDS, PH, hardness, iron content etc.
RO FEED PUMPS: Supply, Installation, Testing & Commissioning of Single Stage/Multi stage Horizontal / Vertical centrifugal monobloc pumping set with delivery SS 304 body and SS 304 impeller, shaft of stainless steel SS 316 and SS shaft sleeve C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, level controller, vibration eliminating pads as required, M.S fabricated base plate bolted to cement concrete foundations complete.Duty Parameters of RO Feed Pump:Capacity/Flow Rate - 1000 l /hour (Each)Pumping Head - 15-20 m,1 Set = 2 Nos. pump (1 working+ 1 standby), Motor kW - 1.5 KW (Approx) or as per manufacture recommendation, Location - terrace, Type of Pump - Horizontal/Vertical Centrifugal monoblock pump. The system will include 1000 Ltrs SS tank and all interconnecting piping.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
HOT WATER SYSTEM Supply, Installation, testing and commissioning of hot water generator shall be Air to water heat pump Model no.CAHP-120-C-12 as manufactured by A.O Smith water products company or equivalent. Heat pumps shall be rated at 2.25 KW of input power and 8 KW of output energy with 12 KW standby source of heating, with 445 liters of integrated storage tank. Heat pump shall have LED display wired remote with built in diagnostic and troubleshooting information. Internal surface of the tank exposed to water shall be glass-lined with an alkaline borosilicate composition that has been fused to steel by firing at a temperature range of 760⁰C to 860⁰C. It shall have internal and external two stage coil condenser. Refrigerant used environment friendly R-134a. Heat pump should heat water up to 65⁰C on heat pump mode. It shall have silent operation and the sound level should not exceed 59 dB.Hot Water outlet connection - 20mm diameter,Cold Water Inlet connection - 20mm diameter,Hot Water Return Inlet Connection - 20mm diameter,MS construction with glass lining,Mineral wool insulation with cladding,Incoming pressure - 3.5 kg/cm2,Supplying, storing, handling, shifting, insatallation, testing and commissioning of 2 Nos.(1 working + 1 standby) hot water reurn circulating pump (Grundfoss make) in SS304 (0.5 LPS @ 15m head), all interconnecting pipes, valves, accessories, pressure guage, brackets fixed to expansion fasteners with M.S. nuts and bolts, insulation with cladding complete including cutting and making good the walls wherever requiredControl panel for automatic operation with sequential running of pumps including cabling, earthing, cable tray etc.complete as per design and drawing.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Design, supplying, installing, testing & commissioning of Sewage Treatment Plant for treatment of 70 KLD Domestic waste & 10 KLD Food Court Kitchen waste water including Electro-Mechanicals of STP i.e BAR SCREEN,Raw Sewage Transfer Pumps,Sludge Re-circulation Pumps / Disposal Pump,Sludge De-watering System,Air diffusion system,CPVC & MS Pipeline Air Grid (heavy Class),Air Defuser,Irrigation Water Transfer Pump,Filter Feed Pumps,Flushing Water Transfer Pump for Hotel Block and food court,Dual Media Filter,Activated Carbon Filter,Plumbing & Interconnecting Pipeline,MBBR Media Make : Biotech / PP Aqua / Febtech,Tube Settler Media,ultraviolet dis-infection unit,chlorine dosing system ,Sump Pit Pump (Sewage transfer to Collection Tank),INSTRUMENTATION,ULTRA FILTRATION SYSTEM,ELECTRICAL INSTALLATION FOR STP,Provision of one incoming feeder, Bus bar, Outgoing feeders for all pumps,EFFLUENT TREATMENT PLANT (ETP) 10 KLD,Anticipated effluent parameters before treatment:,Effluent discharge standard after treatment ,Pre-Fab Structure,modular type Oil & Grease Trap,Effluent lifting pumps,Horizontal centrifugal non clog water pumps,Air Blower for Coagulation,Lime dosing system ,Alum dosing system,Poly dosing system,Tubedeck media , fixing all piping,level controller for water pumps,motors control panel.,all cable wiring with cable tray and including all civil work ( i.e. R.c.c & excavation etc.) as per design and drawing completed.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing & Commissioning of Single Stage/Multi stage Horizontal/Vertical centrifugal monobloc pumping set with CI body and SS impeller, SS shaft and SS shaft sleeve, mechanical seal, connected to a TEFC induction motor (Min IE2) suitable for 415±10% volts, 3 phase 50 cycles A.C. supply with pressure gauge with gunmetal isolation cock, Isolation Valves, NRV, fabricated MS C class suction and delivery headers, vibration eliminating pads as required, M.S fabricated base plate bolted to cement concrete foundations complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Filter Feed Pumps : Capacity /Flow rate : 8 M3/ Hr each pump Pumping Head : 25 - 30 m Power Requirement (HP) : 2 HP or as per manufacturer Location : Pump Room 1 Set = 2 Nos. Pump (1 Working+1 Standby) Make: Kirloskar / Lubi / Wilo
Domestic Water Transfer Pumps to OHT (Food Court) : Capacity /Flow rate : 7.5 M3/ Hr each pump Pumping Head : 35 m Power Requirement (HP) :2 HP or as per manufacturer Location : Pump Room 1 Set = 2 Nos. Pump (1 Working+1 Standby) Make: Kirloskar / Lubi / Wilo
Raw Water Transfer Pumps to STP : Capacity /Flow rate : 7.5 M3/ Hr each pump Pumping Head : 25 m Power Requirement (HP) : 1.5 HP or as per manufacturer Location : Pump Room 1 Set = 2 Nos. Pump (1 Working+1 Standby) Make: Kirloskar / Lubi / Wilo
Filteration (Domestic Water): Supplying, installing, testing and commissioning of MSEP vessel filter fabricated from MS sheet as per IS:2825 with all necessary accessories. Filter shall be suitable for working pressure of 4 kg / cm2 and shall include MS 'C' Class frontal piping & valves, back wash system & filter media etc. complete with standard fittings like manhole cover, pressure gauges, sampling cocks, rinse drain valve, air vent valve with piping, bolts, nuts & rubber gaskets etc. The MS sheet thickness for tank shall be min. 6mm and for dishess shall 8mm. The internal surfaces of tank shall be treated with epoxy coating and external surface with primer and anticorrosive enamel paint (Min. 2 coats) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.. Make : Fabricated
Dual Media Filter in Pump Room: Flow rate : 8 Cum/hr Filteration Rate : 18 cum/hr/sqm Filter Diameter : 800 MM HOS : 1500 MM Shell Thickness: 6 mm Dish Thickness: 8 mm
Activated Carbon Filter in Pump Room: Flow rate : 8 Cum/hr Filteration Rate : 18 cum/hr/sqm Filter Diameter : 800 MM HOS : 1500 MM Shell Thickness: 6 mm Dish Thickness: 8 mm
Water Softener in Pump Room: Supplying, installing, testing & commissioning of MSFRP water softening plant fabricated as per IS:2825 (suitable for 4 Kg/Sqcm working pressure) complete with MS 'C' Class frontal piping, standard fittings like manhole cover, pressure gauges, sampling cocks, rinse drain valve, air vent valve with piping, bolts, nuts & rubber gaskets, initial charge with NA Resin, Butterfly valve with built in ejector for controlling all operations, regeneration system and HDPE Brine tank with motorised SS Agitator, pressure gauge at inlet/outlet. Softener shall be suitable for the following duty: including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make : Fabricated Flow Rate : 8 Cum/hr at 12 hrs operation Inlet hardness : 300 - 400 PPM (Expected) Outlet hardness : <50 PPM Working pressure : 3.0 Kg/cm2 Test pressure : 4.5 Kg/cm2 OBR : 96 m3 Suggested dia : 800 mm Height : 1800mm Brine Tank Capacity 500 ltr with Agitator for salt mixing Resin make - Ion Exchange / Doshion, Vessel make : Fabricated, MOC- MSFRP, Dish-8mm, Shell-6mm and FRP-3mm, Outer Vessels 2 Coat of enamel paint. Purpose: For removal of hardness from water including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Ultravoilet Disinfection Unit: Supply, installation, testing and commissioning of ultraviolet dis-infection unit. The unit shall have over 99% bacterial reduction from inlet to outlet. The Disinfection chamber shall be constructed of SS316L on all wetted parts. The UV lamp shall be of low pressure mercury vapour type with hard glass enclosure, the sockets shall be water tight & vibration resistant. The lamp life shall be rated for 6000 hours. UV system shall be designed for treatment of domestic water of 8 M3/Hr including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make: Alfa/Trozan/Wedico/Infilco
Supply, Installation, testing & commissioning of submersible non clog pumps for suitable rating with CI body, CI impeller, SS shaft , including Isolation valve, NRV on delivery line connection, delivery header with complete fittings etc as required, Pump should be capable of operation on 415 Volts ± 10 % 50 HZ A.C 3 phase supply. Quoted price shall be inclusive of Starter panel with auto/manual function to operate the pumps & protection from dry run, power cables from pumps to panel, level controller, control cables etc complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Drainage Sump Pump with Panel (For Pump Room): Capacity: 15 m3/hr each pump Head : 10-12 Meter Solid Handling Capacity - Upto 15-20 mm size 1 Set includes 2 Pumps - 1W+1S 3 HP or as per Vendor specifications. Make : Kirloskar / KSB / WILO
Supply, installation, testing & commissioning of chlorine dosing system consisting of one chemical grade HDPE tank of 100 liters capacity with displacement diaphragm dosing pump having variable flow rate of (0-5 LPH). The motor shall be suitable for operation at 240V/ single phase/50 Hertz supply. The pump shall be supplied complete with necessary polypropylene piping, valves, strainers & injection fittings for complete automatic dosing. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Make: Pentair/ E-Dose/ UPC
Supply, installation, testing & commissioning of UPVC (Schedule 40) pipe of Suitable sizes (Min 50mm) for interconnecting the electro-mechanicals, tank drain and overflow connection with standard Fittings of elbow, socket, flange, Butterfly Valves, NRV, etc. Cost should be inclusive of all supports/clamps / brackets, fastener etc. as required. Suction and Delivery headers of all the pumps shall be fabricated from MS heavy duty pipes. WTP vendor scope of pipeline at battery limit inside of the pump room only.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Pipe & Fittings Make : Ajay / Supreme / Astral, Butterfly Valve & NRV Make : Zoloto/Inter Valve/Castle
Supply, installation, testing & commissioning of Cast Iron double flange suction "Y" strainer fabricated Stainless Steel sheet with suitable dia. perforation holes including nuts, bolts and 3 mm thick rubber insertion complete & tested. Size as per site or site in charge instructions. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make : Emerald/ Zoloto / Castle
100 mm nominal bore (For Filter Feed, Domestic & Raw Water Transfer Pumps)
150 mm nominal bore (For Filter Feed, Domestic & Raw Water Transfer Pumps)
Water Level Controller Supply, assembly, erection, testing and commissioning of water level controller for the performance of the system complete with sensing probes including providing and fixing wiring from control junction box near the UG tank to probes of required length, interconnection wiring between level controller and the concerned contactor in the starter panel as required. The level controller shall perform the following functions.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make: Cirrus / Aditya / Technika
a) To switch ON the pumps (2 nos. filter feed pumps) when the water level in raw water tank is high & domestic tank is low. To Switch OFF the pumps when the water level in the raw water tank is low or domestic tank is high. b) To switch ON the pumps (2 nos. Domestic water transfer pumps to OHT) when the level of water in the Domestic water tank is High & in Overhead tank is low and switch OFF the pumps when the level of water in the domestic water tank is low OR in overhead tank is high. c) To switch OFF the pumps (2 nos. Raw water transfer pumps to STP) when the level of water in the Raw water tank is Low.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing & commissioning of water level indicator 4-5 level of domestic water tank, raw water tank, Fire tanks (2 Nos.) with complete cabling and panel connection . including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make: Cirrus / Aditya / Technika / Minilec
Supply, installing, testing and commissioning of Pressure switch for automatic operation of domestic water transfer pumps to OHT including necessary wiring upto control panel including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.. Make: Potter/Danfoss/Switzer
Fire-Fighting Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conformingto IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
150 mm. Dia
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conformingto IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Single headed Gunmetal
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conformingto IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conformingto IS 13095 of following sizes as required : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
100 mm dia
150 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conformingto IS 636 (type-A) as required : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conformingto IS 884 complete with the following as required; -20 mm nominal internal dia water hose theRmtoplastic (Textile reinforced) type -2 as per IS: 12585 -20 mm nominal internal dia gun metal globe valve & nozzle. -Drum and brackets for fixing the equipmets on wall. -Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diaRmt size nozzle conformingto IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Gun Metal
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alaRmt, bronze seat clapper, clapper aRmt and hydraulically driven mechanical gong bell to sound continuous alaRmt when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required :including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge .
150 mm dia
Supplying, installation, testing and commissioning of Electrical driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required:(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.(e) Suitable cement concrete foundation duly plastered with anti vibration pads. 2280 lpm @ 70 m Head including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
(a) Supplying, installation, testing and commissioning of diesel enginedriven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Diesel Driven Pump). (b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event fault with audio indications, painted with post office red colour etc. as required. (d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. (e) Suitable cement concrete foundation duly plastered and with anti vibration pads. 2280 lpm @ 70 m Head including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
(a) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump). (b) Horizontal type, multistage, centrifugal pump of cost iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS: 1520. (c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS: 325. (d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (e) Suitable cement concrete foundation duly plastered and with anti vibration pads. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
180 lpm @ 70 m Head
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc, and fixing the pipe on the wall/ ceiling with suitable clamp/ support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
80 mm dia.
100 mm dia.
150 mm dia.
200 mm dia.
250 mm dia.
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
65 mm dia.
80 mm dia.
200 mm dia.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
65 mm dia.
100 mm dia.
150 mm dia.
200 mm dia.
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm dia.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc. as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm dia
Providing, installation testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing, fixing, testing & commissioning of 15 mm dia quartzoid bulb type sprinklers with required accessories: including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Pendent / Upright Sprinkler 79°C (Quick Response)
Supplying and fixing of fire brigade connectiion fo cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as required for suitable dia MS pipe connection conforming to IS 904 as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2 way-100 mm dia M.S. Pipe
4 way-150 mm dia M.S. Pipe
Pressure Vessel for Fire Pump Supply, Installation, Testing & Commissioning double flanged vertical air vessel fabricated from 10mm M.S. plate with dished ends from 10mm M.S. plate, outside with one coat of primer and two coats of synthetic enamel paint of approved shade, complete with approved quality and sufficient number of pressure switches, air release valve, tripod type stand, pressure gauge with ball valve, drain ball valve of 50mm dia with 2.0 meter long GI (Heavy Duty ) piping complete as required and all other required accessories to operate commonly main fire pump, diesel fire pump and Jockey pump at drop of pressure, automatically at required pressure setting;including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing flanged flexible Ruber bellow of rating PN 1.6 or equivalent, to provide stress relief for suction/delivery of pumps, complete with standard flanges, nuts, bolts etc.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150mm dia (min.150 mm length)
80mm dia (min.150 mm length)
65mm dia (min.150 mm length)
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required . including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
80 mm dia
100 mm dia
Providing, fixing, testing & commissioning of water flow meter with bypass arrangement complete with piping and fittings for flow indication, monitoring & testing of fire pumps.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm dia ( working pressure 10.00 Kg/cm2)
Providing, fixing, testing & commissioning of M.S. class 'C' diesel pump exhaust pipe including all fittings like bends, tee, clamps/structural steel support of suitable dia for the engine. The pipe shall be provided with 12 mm thick Supercera Ceramic Fibre rope.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm dia
Providing and fixing of Standard Fireman's Axe with heavy insulated handle.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Weather proof standard fire hose cabinet (750 mm x 600 mm x 300 mm deep) made of 16 SWG powder coated M.S. sheet having single or double opening glazed (4.0 mm thick glass) shutter including necessary locking arrangement by allan key, stove enamelled Fire red finish (as per IS : 5, shade no. 536) with " Fire Hose" marked on front, suitable for housing 2 nos. 15m long 63 mm dia Hose pipe, 1 No. branch pipe & nozzle spanner (For Terrace Hydrant & External).including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing fire authority approved weather proof M.S. fire hose door (size 900 (L) x 2100 (H)) made out of 16 gauge M.S. sheet Angle frame capable of accommodating fire hose reel, fire hydrant, hose pipe, fittings & accessories. The box shall have a single or double glazed front glass door (with 4 mm thick glass) with lock & key arrangement & shall be painted with Fire red as per IS:5, shade no. 536. Drain arrangement shall be provided by Contractor.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (For Internal Hydrant)
Providing and fixing brass/bronze lever operated ball valves of full flow with stainless steel ball (AISI 304 and spindle AISI 401) with settling and gland of superior quality and having minimum working pressure of 15 Kg/cm2.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
25 mm dia
Providing and fixing cast iron air release valve of 25 mm dia including 25 mm dia Ball valve with fittings etc. as per the requirement.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing Bourdon type Stainless Steel dial type pressure gauge with brass isolation valve and pipe.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (For each internal Fire hose cabinet)Dial Diameter : 100 mm Caliberation : 0-15 Kg/cm2
Providing and making drainage provision for the wet riser with 40 mm dia MS (heavy duty) pipe, ball valve, fittings etc. as required maximum length of pipe 6 mtr.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 25 mm dia inspection & testing assembly with gun metal Gate valve, gun metal sight glass, drain valve (Ball valve 50mm dia) & connection to drain.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and Fixing of Dry Chemical Powder based Portable Fire Extinguisher, filled with DCP (ABC) MAP-90% (Mono-Ammonium Phosphate) Powder, Stored Pressure Type, UGTS Pressure Gauge, CE Marked Valve with NRV, fitted with EPDM Rubber Hose, fixed to wall with brackets including all necessary accessorises, Applicable on Class A,B & C and Electrically-Started-Fire, IS 15683:2018 Marked.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Capacity 6 Kg.
Providing and Fixing of Co2 (Carbon Dioxide) based Portable Fire Extinguisher, Valve shall be to IS 3224 Marked, PESO Approved Cylinder and shall be IS 7285 Marked on Body, fitted with High Pressure Wire Braided Hose & Flat Horn with Diffuser, fixed to wall with brackets including all necessary accessorises, IS 15683:2018 Marked.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Capacity 4.5 Kg.
Capacity 22.5 Kg. (IS 16018:2012 Latest Trolley Mounted)
Providing and Fixing of Wet Chemical (K Type Kitchen) Portable Fire Extinguishers, Capacity 6 Litre, body made of SS 304-L, Squeeze Grip NRV Valve, UGTS Pressure Gauge EPDM Hose with Nozzle, Pressureized with Dry Nitroge and mainted as per IS 2190:2010 Revision Fourth.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
a) Capacity 6 Ltr.
Supply and Fixing of Fire Buckets Stand complete with 4 Nos 9 Ltr Fire Bucket, Buckets shall be painted red from outside and with handle at the bottom for easy operation and handling.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & Fixing of Floor Mounted SS Stand (MOC:SS-304, Outside Mirror Polished) to accommodate Extinguisher where could not installed on wall / column.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc. as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
80 mm dia
Electrical works : - Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required..Make :-Anchor (Roma classic ),L&T(Entice),Legrand(Myrius) or its equivalent including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Group B
Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
TV cable in existing conduiting: Supply & drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in existing surface/ recessed steel/ PVC conduit as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following sizes of heavy class PVC conduit having wall thickness 2.0mm along with accessories insurface/recess including painting in case of surface conduit, or cutting the walland making good the same in case of recessed conduit as required.Diplast/BEC/Polyfit.or its equivalent including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
TV socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of modular Blanking plate on the existing modular plate & switch box including connections but excluding modular plate etc. as reqd.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1 or 2 Module (75mmX75mm)
4 Module (125mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. 6 Module (200mmX75mm)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
8 way , Double door
12 way , Double door
16 way , Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
6 way (4 + 18), Double door
8 way (4 + 24), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is noRmtally used where 3 phase outlets are required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
8 way (4 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Single pole
Triple pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying & Fixing of following rating four pole (three phase and neutral) 415 volts, Residual Current Circuit Breaker (RCCB), having a sensitivity current upto 300 milli-amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing M.V. danger notice plate of 200x150mm ,made of mild steel at least 2mm thick ,vitreous enameled white on both sides ,and with inscription in single red colour on front side as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays bends with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays tees with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays cross members with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Providing and fixing 16 mm M.S. Fan clamps of standard shape and size in existing R.C.C. slab, including cutting chase, anchoring clamp to reinforcement bar, including cleaning, refilling, making good the chase with matching concrete, plastering and painting the exposed portion of the clamps complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 Each. blades, 30 cm long down rod, 2 Each. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1 run of cable
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Each. 3 pin 5/6 A modular socket outlet and 2 Each. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Each. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Rmt long etc. with charcoal/ coke and salt as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Rmt long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 Rmt below ground as strip earth electrode, including connection/teRmtinating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 Rmt below ground as strip earth electrode, including connection/ teRmtinating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Upto 35 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal foRmtation including excavation, sand cushioning, protective covering and refilling the trench etc as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe/existing open trence/as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Upto 35 sq. mm (clamped with 1mm thick saddle
Supplying and making end teRmtination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2 X 6 sq. mm (19mm)
2 X 10 sq. mm (19mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 150 sq. mm (45mm)
3½ X 240 sq. mm (62mm)
4 X 10 sq. mm (25mm)
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm dia
150 mm dia
300 mm dia
Supplying and laying of following size DWC HDPE pipe ISI markedalong with all accessories like socket, bend, couplers etc. conformingto IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) includingexcavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
63 mm dia (OD-63 mm & ID-51 mm nominal)
Supply of following sizes of XLPE insulated Copper ARMOURD cable, overall PVC sheathed 1.1 KV grade cables conformingto relevant IS code and technical specifications including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2CX 2.5 SQMM AL ARMOURDCABLE
2CX 4 SQMM AL ARMOURDCABLE
2CX 6 SQMM AL ARMOURDCABLE
Supplying & laying 1.1 kv grade ISI marked synthetic rubber mats as per specifications of chief electrical inspectorate including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying & fixing of shock treatment chart printed in hindi and english fitted in wooden frame and glass at front side and hard board at back side including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying & fixing in position 1.1 kv rubber hand gloves including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying of first aid box as approved by St. John Ambulance Brigade/Indian Red Cross conformingto IS : 2217 - 1963 including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying of basic Electrical and mechanical maintenance tool kit including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conformingto MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net Rmting facility, necessary rotections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conformingto IS 4286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 VAC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total haRmtonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories.
d) Fixing of Array junction box & Main junction box with IP 65 protection and teRmtination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade aRmtoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V Rmts operating at 240 Volt AC Supply complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all heRmtetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5.
Supply, Installation, testing and commissioning including vacCumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Thickness 0.63 mm sheet
Thickness 0.8 mm sheet
Thickness 1.0 mm sheet
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Thickness 0.63 mm sheet
Thickness 0.8 mm sheet
Thickness 1.0 mm sheet
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Fire Damper
Actuator
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Canvass Connection Providing and Fixing Canvas Connection of Fire Retardant and non porous double layer material between Each indoor units and ducts including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply Instalaltion, testing & commissioning of Y-joints including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of intelligent analog addressable phototheRmtal detector complete with mounting base complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of intelligent addressable theRmtal detector with rate of rise Cum fixed tempreature theRmtistor complete with base as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of addressable manual call point complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of addressable horn Cum strobe complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying & laying of 2x1.5 Sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire aRmtouring & FRLS outer sheath complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Providing and fixing heavy duty copper armored cables 1.1 KVA grade including necessary support clamps at ceiling level and connection thimbles and double compression glands,complete in all respects.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Control cable 6 core 2.5 Sq.mm
Control cable 4 core 1.5 Sq.mm
Control cable 2 core 1.5 Sq.mm
Providing and fixing heavy duty Aluminum armored cables 1.1KVA grade including necessary support clamps at ceiling level, connection thimbles and double compression glands, complete in all respects.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Power cable 3 core 6 Sq.mm
Power cable 3 core 10 Sq.mm
Power cable 3 core 16 Sq.mm
Power cable 3 core 50 Sq.mm
Power cable 3 core 70 Sq.mm
Wiring for group controlled (looped) light point/fanpoint/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.Group-B
Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit asrequired including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2 X 4.0 sq. mm + 1 X 4.0 sq. mm earth wire
2 X 6.0 sq. mm + 1 X 6.0 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Bell Push
RJ 45 Jack
Supplying and fixing Ding Dong bell suitable for single phase, 230 volts, complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
12 way (4 + 36), Double door
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
8 Module (125mmX125mm)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Double Pole
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
750 mm width X 62.5 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays bends with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
750 mm width X 62.5 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays tees with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
750 mm width X 62.5 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays cross members with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
750 mm width X 62.5 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%,in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and fixing of following sizes of heavy class FRLS PVC conduit having wall thickness 2.0mm along with accessories insurface/recess including painting in case of surface conduit, or cutting the walland making good the same in case of recessed conduit as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge..Diplast/BEC/Polyfit.or its equivalent
Supply, installation, testing and commissioning of 20 kVA modular type UPS system with True Online configuration , double conversion type , Modular & Scalable UPS with hot swappable Power Modules of 10 kVA . STS Module & Independent rectifier, inverter& Control for each modules , 3 phase (415 V + 15%) Volts input & 3 phase output (400 V + 1%), 50 Hz, for balance supply and unbalance loads,true on line with double conversation VFI type, TVSS at incoming of UPS, VFD topology with pure sine wave input , Communication Port , Static By Pass switch , Isolation Transformer , Digital Signal processor (DSP )100% IGBT inverter & converter, Input harmonic Current THD 3% typical at 100% load, 6% maximum at 50% load and 15 min battery backup Sealed Maintenance Free lead acid Batteries complete with intercell connectors & copper cables, battery breaker, battery stand / Cabinet with adequate supports to carry the load of the batteries and complete in all respect Cost to include battery stand/rack, interconnecting cables etc.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Design manufacture, supply installation testing and commissioning of 6.0 KVA UPS system 1 phase (220 V + 15%) Volts input & 1 phase output (220 V + 1%), 50 Hz , pure sine wave output , 100% IGBT Inverter & Converter with battery bank with back up of minimum 15 minutes duration including, SMF batteries, battery chargers, rectifiers, transformers, controls, protection and instruments etc. complete as required. Cost to include battery stand/rack, interconnecting cables etc. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Design manufacture, supply installation testing and commissioning of 10.0 KVA UPS system 3 phase (415 V + 15%) Volts input & 3 phase output (415 V + 1%), 50 Hz , pure sine wave output , 100% IGBT Inverter & Converter with battery bank with back up of minimum 15 minutes duration including, SMF batteries, battery chargers, rectifiers, transformers, controls, protection and instruments etc. complete as required. Cost to include battery stand/rack, interconnecting cables etc.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Note :- Both UPS shall be synchronized and suitable controllers etc shall be included in the rates quoted
Fabricating supplying to site of installation, installation on ceiling/ surface 1.6 mm thick MS Powder coated receways of height 50 mm and 2.0 mm thick openable cover, totally enclosed, the joints between two lengths of channels or between channel and junction box shall be joined together with 3 mm thick GI. Powder coated coupler plates to make it dust and water proof. The cost shall including all supporting and fixing accessories including dash fasteners. (Blue colour for data and Orange colour for power) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
300 mm (wide) x 50 mm (height)
200 mm (wide) x 50 mm (height)
150 mm (wide) x 50 mm (height)
Supplying and fixing of USB Charging socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing and commissioning of Din Rail 20A DP Contactor in existing DB including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing and commissioning of one way MCB enclosure ( 4 Module) with out MCB ( For food court Shops & for HVAC Fans local isolation) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2 X 16 sq. mm (22mm)
3½ X 300 sq. mm (70mm)
3 X 4 sq. mm
3 X 6 sq. mm
3 X 10 sq. mm
3 X 16 sq. mm
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) includingexcavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
160 mm dia (OD-160 mm & ID-135 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as per IS 7098 (Part-2) 1985 with the latest ammendments of following sizes as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply,Erection,Installation and commissioning of true power maintenance free chemical earthing system consisting of environment friendly ground enhancing compound 'G.E.C' 25kg or as required at site having anticorrosive and hygroscopic properties to replace excavated soil. It should consist of true power G.I.chemical earthing, as per site conditions and soil resistivity at various depth levels and different terrains. The electrodes should have 2 meter length,50 mm diameter,terminal joint 200X25X6mm GI Strip with exothermic welds. The electrode should be duly tested and certified by CPRI for 30kA short time current test for 1 sec rms. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply,Erection,Installation and commissioning of Uniearth maintenance free chemical earthing system consisting of environment friendly ground enhancing compound 'G.E.C' 50kg or as required at site having anticorrosive and hygroscopic properties to replace excavated soil. It should consist of Uniearth copper bonded electrodes, as per site conditions and soil resistivity at various depth levels and different terrains. The electrodes should have coating of 250 microns of molecularly bonded pure electrolytic copper(99.9%) in 2 meter length,17.2 mm diameter,terminal joint 200X25X6mm Cu Strip with exothermic welds. The electrode should be duly tested and certified by CPRI for 30kA short time current test for 1 sec rms. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2CX6 SQMM AL ARMOURED CABLE
2CX10 SQMM AL ARMOURED CABLE
2CX16 SQMM AL ARMOURED CABLE
4CX 6 SQMM AL ARMOURED CABLE
4CX16 SQMM AL ARMOURED CABLE
3.5CX25 SQMM AL ARMOURED CABLE
3.5CX35 SQMM AL ARMOURED CABLE
3.5CX50 SQMM AL ARMOURED CABLE
3.5CX70 SQMM AL ARMOURED CABLE
3.5CX95 SQMM AL ARMOURED CABLE
3.5CX120 SQMM AL ARMOURED CABLE
3.5CX150 SQMM AL ARMOURED CABLE
3.5CX185 SQMM AL ARMOURED CABLE
3.5CX240 SQMM AL ARMOURED CABLE
3.5CX300 SQMM AL ARMOURED CABLE
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
2CX6 SQMM AL ARMOURED CABLE
2CX10 SQMM AL ARMOURED CABLE
2CX16 SQMM AL ARMOURED CABLE
4CX 6 SQMM AL ARMOURED CABLE
4CX10 SQMM AL ARMOURED CABLE
4CX16 SQMM AL ARMOURED CABLE
3.5CX25 SQMM AL ARMOURED CABLE
3.5CX35 SQMM AL ARMOURED CABLE
3.5CX50 SQMM AL ARMOURED CABLE
3.5CX70 SQMM AL ARMOURED CABLE
3.5CX95 SQMM AL ARMOURED CABLE
3.5CX120 SQMM AL ARMOURED CABLE
3.5CX150 SQMM AL ARMOURED CABLE
3.5CX185 SQMM AL ARMOURED CABLE
3.5CX240 SQMM AL ARMOURED CABLE
3.5CX300 SQMM AL ARMOURED CABLE
Supply of following sizes of XLPE insulated Copper Armoured cable, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
4CX 6 SQMM Cu ARMOURED CABLE
4CX 10 SQMM Cu ARMOURED CABLE
4CX 16 SQMM Cu ARMOURED CABLE
3CX 4 SQMM Cu ARMOURED CABLE
3CX 6 SQMM Cu ARMOURED CABLE
3CX 10 SQMM Cu ARMOURED CABLE
3CX 16 SQMM Cu ARMOURED CABLE
Supplying of following sizes of XLPE aluminium conductor, corss linked polythylene, individual core screwed, flat steel strip armoured, PVC sheathed cable of 11KV grade (earthed) comforming to IS: 7098 (Part 2),with uptodate ammendment complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
3 C x 240 Sq.mm XLPE HT cable
Supplying and installation of outdoor type junction box in Polycarbonate enclosure ( IP 66 ) suitable for 3 Core 16sq. Mm / 10 sq/ mm Al armoured incoming cable and 3 Runs of 2.5 Sqmm FRLS wire as outgoings including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying and installation of outdoor type box ( IP 55 ) with terminals for external lighting connections suitable 2.5sq. mm / 1.5 sq. mm incoming & outgoing wires including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply & laying and drawing of 1 Pair X 1.5 sqmm 300/500 V grade Plain stranded Copper , Stranded Circular conductor PVC insulated ,Extruded PVC Type inner sheath , Galvanised Steel armouring , Extruded FR-LSH PVC Type outer sheath(Blue) , Aluminium mylar tape colllective screen material speaker armoured cable exposed on wall / ceiling including terminations all labour and material etc complete including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of digital audio amplifier 480 Watt, 25V rms operating at 240 volt AC supply complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Ten Loop Panel.
Supplying, installation, testing & commissioning of addressable fire control module complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supplying, installation, testing & commissioning of fault isolator complete with base as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing and Commissioning of Intelligent Addressable Multi-Sensor (Optical Smoke + Heat) detector with base. . Multi-sensor detector shall have a configuration mode that gives separate alarms for smoke detection and heat detection and shall indicate the cause of alarm (smoke or heat). Also the multi-sensor shall have combined configuration mode of smoke and heat detection that gives only one evaluated alarm from a multi-sensor detector in case of a fire event.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing and Commissioning of Intelligent Addressable, Supervised Monitor Module monitoring Potential-free, Normally Open Dry Contact input including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply and Installation of addressable power supply unit ( PSU ) for powering the hooters including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing and commissioning of plug-in type addressable Detector with sounder base . The item shall also include the cost of base plate, mounting accessories etc. and complete as required. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation testing and commisioning Standalone IVR 80 Ch IVR with 8HDD : Support corresponding channel of face comparison at the same time, Support on-site photo, batch import, export face database, Support face recognition black and white list classification, H.265/H.264 dual stream decoding, embedded Linux operating system, Support synchronous recording, remote monitoring, backup; up to 213CH 1080P video synchronous playback and multi-channel backwords playback, Standard ONVIF, SLINK, RTSP protocol, Support DDNS, EMAIL, UPNP, NTP, P2P and other functions, Support WEB, mobile phone monitoring, client, VMS monitoring, Support external alarm; Two-way audio intercom, Support our Smart IPC: Target Count,Object Le/Lost, Electric Fence, Line Crossing, Face Grouping List, Face Detection, Humaniod Detection, Retrograde Detection Leave Position Detection, Support IPC centralized management, including IPC parameter configuration, information export and import, real-time information acquision and upgrade, etc., Support network monitoring: network traffic, network delay packet loss test, network packet capture backup. Honey well WD101PURP EQUIVALENT IN OTHER MAKES LIKE SONY/ CP Plus.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, Testing and commisioning of Hard Disks of Suitable capacity for 30 days storage as per above cameras.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. ( The rate is inclusive of all hard disks etc required in NVRs etc for all above cameras storage )
Supply, installation testing and commisioning PC with Processor Intel ® i7, 2.0GHz with internal memory of 32 GB RAM with 2 TB HDD .Operating system Windows® 7 Professional 64-bit. Dual or compatible pair of NICs, 1 Gbps. NVIDIA 4 GB dedicated Graphic Card .including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply , Installation,Testing &Commisioning of 12 port POE Access Switches : 180 W, 12 X 10/100/1000 POE Port Layer 2 Switch with 2 x 1 G uplinks & Stacking module, cable and all other accessories and 3 year support.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 24 port POE Access Switches : 370 W, 24 X 10/100/1000 POE Port Layer 2 Switch with 2 x 1 G uplinks & Stacking module, cable and all other accessories and 3 year support including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply , Installation,Testing &Commisioning of 48 port POE Access Switches : 740 W, 48 X 10/100/1000 POE Port Layer 2 Switch with 4 x 1 G uplinks & Stacking module, cable and all other accessories and 3 year support.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
CAT6 UTP 24 AWG Patch Cord - 1 mtr with cross separator Factory crimped multistranded copper patch cord with tensile strength of > 50N. Conforming to the following standards like EN 50173, ISO/IEC 60603-7 & 11801/IEC 60332-1, UL VW-1 with tensile strength >50N, Number of Insertion upto 2500 Duty Cycle , Color BLUE /GREEN - Data (USER / RACK SIDE) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, testing and commissioning of 24 Port jack Panel including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 19'' 15 U Wall Mount Rack ( with front Glass Lockable Door with PDU) and all other required accessories including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 19'' 6 U Wall Mount Rack ( with front Glass Lockable Door with PDU) and all other required accessories including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 19'' 9 U Wall Mount Rack ( with front Glass Lockable Door with PDU) and all other required accessories including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 1U, Single-sided horizontal cable manager, finger-duct style including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of Cat 6 UTP RJ 45 Connectors for Wi-Fi and CCTV/ACS (USER SIDE) - Pack of 100 Connectors including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply and fixing of 6 core indoor/outdoor OM3 Multimode Optical Fiber of size 50/125μm. Indoor/outdoor rated with U/V stabilized sheath, Tight buffered construction, Attenuation (of cable with fibers) - IEC 60793-1-40 Maximum value of cable at 850 nm ≤ 3.0 dB/km, IEC 60793-2-10 category A1a.2; EN 60793-2-10: ITU Recommendation G.651 , TIA/EIA-492 AAAB, EN 50 173:2002 category OM3 ISO/IEC 11801:2002 category OM3. IEEE 802.3-2002 incl. amendment 802.3ae - 2002. through existing GI/HDPE/ Hume pipe or on cable trays inside the cable duct including all necessary fixing accessories e.g. cable ties, hardware etc including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
VRF ODU Panel -1(Hotel Block) - 16 kA (Out Door Type with Double Door and Canopy) ;- Incoming: 1 No. 315 amps 16 kA 440 volt FP MCCB with Micro processor based overcurrent , short circuit & Earth Fault releases ,Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF-Trip indication Lamps , R-Y-B indication lamps with MCBs, Bus Bar: 400 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 5 Nos. 63A FP MCB ( Motor Duty) + 63A FP RCCB 300mA,7 Nos. 40A FP MCB ( Motor Duty) + 40A FP RCCB 300mA,3 Nos. 32A FP MCB ( Motor Duty) + 32A FP RCCB 300mA,1 Nos. 63A FP MCB ( Motor Duty) ,1 Nos. 40A FP MCB ( Motor Duty) ,2 Nos. 32A FP MCB ( Motor Duty) ,VRF ODU Panel -1 ( Hotel Block) as described above complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
VRF ODU Panel -2 (Hotel Block) - 16 kA (Out Door Type with Double Door and Canopy):- Incoming: 1 No. 315 amps 16 kA 440 volt FP MCCB with Micro processor based overcurrent , short circuit & Earth Fault releases ,Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF-Trip indication Lamps ,R-Y-B indication lamps with MCBs, Bus Bar: 400 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 1 No. 125 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link ,6 Nos. 63A FP MCB ( Motor Duty) + 63A FP RCCB 300mA,3 Nos. 40A FP MCB ( Motor Duty) + 40A FP RCCB 300mA,5 Nos. 32A FP MCB ( Motor Duty) + 32A FP RCCB 300mA,1 Nos. 63A FP MCB ( Motor Duty) ,2 Nos. 32A FP MCB ( Motor Duty) ,VRF ODU Panel -2 (Hotel Block) as described above complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Hotel Main MDB :- Incoming: 1 No. 400 amps 16 kA 440 volt FP MCCB with Micro processor based overcurrent , short circuit & Earth Fault releases ,Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF indication Lamps ,R-Y-B indication lamps with MCBs, Bus Bar: 500 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 3 No. 125 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link .3 No. 160 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link ,1 No. 63 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link ,12 No. 40A FP MCB (Type C),1 No. 63A FP MCB (Type C),Hotel MDB as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
First Floor - MDB ( Hotel):- Incoming: 1 No. 125 amps 16 kA 440 volt TPN MCCB with Thermal Magnetic based overcurrent and short circuit releases , Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF indication Lamps , R-Y-B indication lamps with MCBs,Earth Fault Module. Bus Bar: 150 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 2 No. 40A FP MCB (Type C) ,2 No. 40A DP MCB (Type C), 12 No. 32A DP MCB (Type C), First Floor MDB ( Hotel )as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Second Floor - MDB ( Hotel) :- Incoming: 1 No. 160 amps 16 kA 440 volt TPN MCCB with Thermal Magnetic based overcurrent and short circuit releases ,Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF indication Lamps ,R-Y-B indication lamps with MCBs,Earth Fault Module. Bus Bar: 200 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 3 No. 40A FP MCB (Type C),1 No. 40A DP MCB (Type C),19 No. 32A DP MCB (Type C), Second Floor MDB ( Hotel ) as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Third Floor - MDB ( Hotel):- Incoming: 1 No. 125 amps 16 kA 440 volt TPN MCCB with Thermal Magnetic based overcurrent and short circuit releases ,Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs,Breaker ON OFF indication Lamps ,R-Y-B indication lamps with MCBs,Earth Fault Module. Bus Bar: 150 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 3 No. 40A FP MCB (Type C),15 No. 32A DP MCB (Type C). Third Floor MDB ( Hotel ) as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Controller for parallel genset operation (similar to InteliGen 200 of CompAp or equal) Nos. Cast resin CTs Of ratio 800 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA.R-Y-B indication Lamp , Trip Circuit Healty and Breaker ON-OFF - Trip Indication Lamp , Over Voltage relay (59) And Under Voltage relay (27) with time delay, 1 Nos. Reverse power relay, Underpower Relay with Timer - 1 Set,Phase Sequence Relay - 1 Set,Multi Function meter having 30 Days Memory,Trip Circuit Supervision Relay ,Master Trip Relay,Shunt trip coil. - 1 Set,240 V AC under voltage release. - 1 Set,Surge protection device ,Breaker control switch (TNC),Auxiliary contacts required for necessary interlocking of breakers.( 6 No + 6 NC ),Annunciation with test and reset for fault indication with buzzer,Engine cranking relay- 1 Set,Microprocessor based engine control automatic failure stand by relay including all accessories,Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.One 16 amp automatic Battery charger with inbuilt facility of trickle / boost & consisting of :DC Ammeter (0-30) Amp.DC Voltmeter.(0-30) Volt.Charger ON, OFF indications .DG start / Stop push buttons (Illuminated Type) Emergency Stop Push Button Suitable to accept 3 Nos. 3.5C-240sq. mm Al Arm Cable 500 KVA DG # 2 INCOMER 800 amps 4 pole EDO type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting and with following accessories: Controller for parallel genset operation (similar to InteliGen 200 of CompAp or equal) 3 Nos. Cast resin CTs Of ratio 800 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA. R-Y-B indication Lamp , Trip Circuit Healty and Breaker ON-OFF - Trip Indication Lamp Over Voltage relay (59) And Under Voltage relay (27) with time delay 1 Nos. Reverse power relay Underpower Relay with Timer - 1 Set Phase Sequence Relay - 1 Set Multi Function meter having 30 Days Memory Trip Circuit Supervision Relay Master Trip Relay Shunt trip coil. - 1 Set 240 V AC under voltage release. - 1 Set Surge protection device Breaker control switch (TNC)
Auxiliary contacts required for necessary interlocking of breakers.( 6 No + 6 NC ) Annunciation with test and reset for fault indication with buzzer Engine cranking relay- 1 Set Microprocessor based engine control automatic failure stand by relay including all accessories Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’. One 16 amp automatic Battery charger with inbuilt facility of trickle / boost & consisting of : DC Ammeter (0-30) Amp. DC Voltmeter.(0-30) Volt. Charger ON, OFF indications . DG start / Stop push buttons (Illuminated Type) Emergency Stop Push Button Suitable to accept 3 Nos. 3.5C-240sq. mm Al Arm Cable. BUSCOUPLER#2 1000 amps 4 pole EDO type air circuit breaker with-out releases and with following 6 Nos. NO/NC contacts for remote opening & closing Red/Green / Amber / ON/OFF / Trip indicating lamps with 2A SP MCB as backup protection.Backup MCB and terminal blocks as required. TNC Breaker Control switch Required Interlocking with other incomers & Bus Coupler to be provided as per Schematic Diagram SOLAR INCOMER 1 No. 160 amps 25 kA MCCB with Thermal magnetic release unit for short circuit and over current protections. Bus Bar I: 1000A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings section-I : 3 No. 400 amps 25 kA 440 volt TP MCCB with microprocessor based overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 315 amps 25 kA 440 volt TP MCCB with microprocessor based overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 250 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 3 No. 100 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs
2 No. 63 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs Bus Bar II: 1000A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 25 kA. Neutral busbar shall be of 100% capacity. Outgoings section-II : 2 No. 400 amps 25 kA 440 volt TP MCCB with microprocessor based overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 315 amps 25 kA 440 volt TP MCCB with microprocessor based overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 200 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 2 No. 160 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 125 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs 1 No. 63 amps 25 kA 440 volt TP MCCB with Thermal Magnetic overcurrent , short circuit and Earth Fault releases with heavy duty solid detachable neutral link and complete with on-off-Trip indications lamps , Multi function meter with CTs and Control MCBs
Food Court Shop Panel :- Incoming : 1 No. 400 amps 16 kA 440 volt FP MCCB with Micro processor based overcurrent , short circuit & Earth Fault releases Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs Breaker ON OFF indication Lamps R-Y-B indication lamps with MCBs Bus Bar: 500 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 2 No. 40A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required 8 No. 32A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required 8 No. 63A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required 1 No. 100 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link with dual type energy meter and complete with control MCBs and CTs as required 1 No. 80 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link with dual type energy meter and complete with control MCBs and CTs as required 1 Nos. 63A FP MCB ( Motor Duty) 1 Nos. 40A FP MCB ( Motor Duty) 1 Nos. 32A FP MCB ( Motor Duty. Food Court Shop Panel as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Food Court Common Services Panel:- Incoming : 1 No. 250 amps 16 kA 440 volt TPN MCCB with Thermal Magnetic based overcurrent and short circuit releases Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs Breaker ON OFF indication Lamps R-Y-B indication lamps with MCBs Earth Fault Module Bus Bar: 300 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 5 Nos. 63A FP MCB ( Motor Duty) + 63A FP RCCB 300mA 2 No. 100 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link 2 No. 63 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link 2 Nos. 63A FP MCB ( Motor Duty) 6 Nos. 40A FP MCB ( Motor Duty) 1 Nos. 40A DP MCB ( Motor Duty) . Food Court common services Panel as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Food Court Shop Panel :- Incoming: 1 No. 400 amps 16 kA 440 volt FP MCCB with Micro processor based overcurrent , short circuit & Earth Fault releases .Metering, Indication & Protection: 1 Nos. Multi Function Meter with 3 Nos. Cast Resin CTs and MCBs.Breaker ON OFF indication Lamps .R-Y-B indication lamps with MCBs. Bus Bar: 500 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings: 2 No. 40A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required .8 No. 32A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required .8 No. 63A FP MCB( Type-C) with dual type energy meter and complete with control MCBs and CTs as required .1 No. 100 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link with dual type energy meter and complete with control MCBs and CTs as required .1 No. 80 amps 16 kA 440 volt TP MCCB with Thermal Magnetic based overcurrent and short circuit releases with heavy duty solid detachable neutral link with dual type energy meter and complete with control MCBs and CTs as required .1 Nos. 63A FP MCB ( Motor Duty).1 Nos. 40A FP MCB ( Motor Duty).1 Nos. 32A FP MCB ( Motor Duty).Recreational Block Panel as described above and complete as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
EXTERNAL LIGHTING FEEDER PILLAR INCOMER: 1 No. 63 amps 16 kA 440 volt TPN MCCB with Thermal based overcurrent and short circuit releases with heavy duty solid detachable neutral link complete with R-Y-B indication Lamp and MCCB ON-OFF Indication Lamp Multi function meter having 30 Days Memory and MDI Bus Bar :- 100 A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 16 kA. Neutral busbar shall be of 100% capacity. Outgoings : 2 No. 40 amps 4P MCB (10KA) 1 No. 40 Amps 4P MCB (10KA) with 40A FP contactor, 0-24Hr astronomical timer 2 No. 25 amps 2P MCB (10KA) 1 No. 40 Amps 4P MCB (10KA) with 3 Nos. 40A DP RCCB (100mA), 40A DP contactor, 0-24Hr astronomical timer and 21 No. 10 A SP MCB as outgoings (7 Nos./Phase- Total 21 O/G) and neutral link. External Feeder Pillar as described above complete as required including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, Installation, testing & commissioning of HVAC dedicated VFDs suitable for the following Fan motor capacity (The integration of the VFD with Motor is included in this item) with IP-21 enclosures with Mains disconnect, complying with the tender specifications and having: 'Built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. 'Built-in EMC Filters (electromagnetic compatibility filters) for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution): 2004 Category C 1, for required length of cable between motor & VFD. 'Three-feedback PID (Propotional integrated derivative) controller having capability to simultaneously accept 3 feedback signals from temperature sensors for process optimization and accordingly regulate the speed of the AHUs.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. 'Automatic Energy Optimization for maximum energy savings. 'The VFD shall be compatible with BMS. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, erection, testing and commissioning of the following in polycarbonate IP 65 Enclosure including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
63A FP RCCB( 300 mA)
40A FP RCCB( 300 mA)
25A FP RCCB( 300 mA)
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Thickness 1.25 mm sheet
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Mid Static Ductable units (minimum 45 pascal external static pressure) 4.0 TR
INDOOR UNIT - HIGH WALL TYPE Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply, installation, testing and commissioning of Gl volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Gl volume control duct damper
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Air Cooled Split Units Supply , Installation , testing and comissioning of Air Cooled Split airconditioners each comprising an outdoor unit consisting of hermetic scroll compressor, air cooled condensing unit, Condenser fan etc. with outer casing and indoor fan coil unit(s) consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with remote control etc. both inter connected with copper refrigerant pipe and drain pipe of required length as given, cabling and wiring (priced separately in Electrical Tender), insulation with Closed Cell nitrile foam, full charge of refrigerant gas and oil, M.S. base frame, supports etc. complete as per specifications and drawings. The cost shall also include angle iron stands for outdoor units. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Hi Wall Type
1.5 TR Unit ( 1 working + 1 standby with duty timer for duty cycling)
1.0 TR Unit
1.5 TR Unit
Treated Fresh Air Hnadling Unit with DX ODU (6 Row Deep Cooling Coil)(Thermal Break Profile)(with rain water canopy) Floor Mounted Type - Hotel Block Kitchen Supply , Installation , Testing And Commissioning of Floor Mounted Type air unit double skin type of extruded aluminium section with 0.6 mm preplasticized/precoated GI sheet outside and 0.6 mm plain Galvanized sheet inside, complete with 25 mm thick insulated panels pressure injected with PUF insulation of 40 kg/m3 density, forward curved blower, 6RD cooling coil section with DX coil, filter section with MERV 8 & MERV 13 Filters, fan motor, drive set, mounting base damper etc. suitable for outdoor application as per specifications and drawings.including all necessary fittings and accessories. The complete unit shall be installed on neoprene pad vibration isolators.
4500 CFM Ceiling suspended type AHU with 9.0 Sqft Filter Area at 30 mm Static Pressure(External) - 2.25 KW motor connected with 30 HP ODU ( quoted Seperately) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Kitchen Scrubber (Wet Type) (Motor shall be Suitable for VFD Operation) Supply,Installation,Testing and Commissioning of kitchen scrubber Double Skin floor mounted with 0.8 mm preplasticized/precoated GI sheet outside and 0.8 mm plain Galvanized sheet inside, 40 mm thick PUF insulation of 40KG/m3 , with having pre filter section for removal of oil grease, high pressure water atomisation section, mist eliminator and oulet cone section, fan section with DIDW Blower (Backward Curved blower) with motors, expansion chamber, nozzles, beltdrives with guard, gasket tight access door,4 bend PVC eliminators, water circulation pumps (1W+1STandby), valves including isolation valves for pumps, vibration isolators for blower, distribution piping & fittings etc complete as per specifications and drawings. The complete unit shall be installed on neoprene pad vibration isolators. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Outdoor Type Floor Mounted With Rain Water Protection Canopy.
15000 CFM ( with Forward Curved DIDW Blowers) 9.3 KW Motor ; SP 70 mm(Total) of wg; for Hotel Block Kitchen
Package Type Air Washers (Motor shall be Suitable for VFD Operation) Supply,Installation,Testing and Commissioning of Double Skin Packaged Type Air Washer with extruded aluminium section with 0.8 mm preplasticized/precoated GI sheet outside and 0.8 mm plain Galvanized sheet inside, 40 mm thick PUF insulation of 40KG/m3 , G.I. blower section, DIDW Blower (Backward Curved) with motors , base , drive arrangement ,Filter, cooling pad section, stainless steel 304 sump tank and housing, 4 bend PVC drift eliminators, water circulation pump (1W+1Standby), valves including isolation valves for pumps, piping & fittings etc. as per specifications and drawings . The complete unit shall be installed on neoprene pad vibration isolators.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Outdoor Type Floor Mounted With Rain Water Protection Canopy.
9000 CFM (with Forward Curved DIDW Blowers 5.5 KW Motor ; SP 50 mm of wg;for for Hotel Block Kitchen
Outdoor Air Processing Unit Supply , Installation, testing & commissioning of factory fabricated Outdoor Air Proceesing units of following capacities equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outer cabinet, drain pan, insulation, pipe connections, corded/ cordless remote control etc. of various capacities as per specifications and drawings. Rates of ODU's and interconnecting refrigerant piping to be quoted seperately. The unit shall be installed with Spring vibration isolators of suitable rating. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
1377 CFM (connected with 10 HP ODU )
635 CFM (connected with 5 HP ODU )
988 CFM (connected with 8 HP ODU )
Air Handling Unit with DX ODU (6 Row Deep Cooling Coil) Indoor Type Ceiling Suspended : Supply , Installation , Testing And Commissioning of Ceiling Suspended Type air unit double skin type of extruded aluminium section with 0.6 mm preplasticized/precoated GI sheet outside and 0.6 mm plain Galvanized sheet inside, complete with 25 mm thick insulated panels pressure injected with PUF insulation of 40 kg/m3 density, forward curved blower, 6RD cooling coil section with DX coil, filter section with MERV 8 & MERV 13 Filters , fan motor, drive set, mounting base damper etc. suitable for outdoor application as per specifications and drawings.including all necessary fittings and accessories. 6000 CFM Ceiling suspended type AHU with 12.0 Sqft Filter Area at 30 mm Static Pressure(External) - 3.75 KW motor connected with 20 HP ODU ( quoted Seperately) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Kitchen Scrubber (Wet Type) (Motor shall be Suitable for VFD Operation): Supply,Installation,Testing and Commissioning of kitchen scrubber Double Skin floor mounted with 0.8 mm preplasticized/precoated GI sheet outside and 0.8 mm plain Galvanized sheet inside, 40 mm thick PUF insulation of 40KG/m3 , with having pre filter section for removal of oil grease, high pressure water atomisation section, mist eliminator and oulet cone section, fan section with DIDW Blower (Backward Curved blower) with motors, expansion chamber, nozzles, beltdrives with guard, gasket tight access door,4 bend PVC eliminators, water circulation pumps (1W+1STandby), valves including isolation valves for pumps, vibration isolators for blower, distribution piping & fittings etc complete as per specifications and drawings. The complete unit shall be installed on neoprene pad vibration isolators. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Indoor Type Floor Mounted: 27000 CFM ( with Backward Curved DIDW Blowers) 15.0 KW Motor; SP 70 mm(Total) of wg; for Foodcourt Kitchen
9500 CFM ( with Backward Curved DIDW Blowers) 7.5 KW Motor; SP 70 mm(Total) of wg; for Foodcourt Kitchen.
Package Type Air Washers (Motor shall be Suitable for VFD Operation): Supply,Installation,Testing and Commissioning of Double Skin Packaged Type Air Washer with extruded aluminium section with 0.8 mm preplasticized/precoated GI sheet outside and 0.8 mm plain Galvanized sheet inside, 40 mm thick PUF insulation of 40KG/m3 , G.I. blower section, DIDW Blower (Backward Curved) with motors , base , drive arrangement ,Filter, cooling pad section, stainless steel 304 sump tank and housing, 4 bend PVC drift eliminators, water circulation pump (1W+1Standby), valves including isolation valves for pumps, piping & fittings etc. as per specifications and drawings . The complete unit shall be installed on neoprene pad vibration isolators.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Indoor Type Floor Mounted: 22500 CFM (with Backward Curved DIDW Blowers 11.0 KW Motor ; SP 50 mm of wg;for Foodcourt Kitchen
8500 CFM (with Backward Curved DIDW Blowers 5.5 KW Motor ; SP 50 mm of wg;for for Foodcourt Kitchen
7000 CFM; SP 20 mm of wg; Power 2.25 KW for Pump Room Exhaust / Fresh Air (Axial ) (Non Fire rated)
8000 CFM; SP 20 mm of wg; Power 2.25 KW for STP Exhaust (Axial ) Fire Rated with suitable ionisers/ chemical filters etc to make the exhaust air absolutey smell free
8000 CFM; SP 20 mm of wg; Power 2.25 KW for STP Fresh Air Pump (Axial ) (Non Fire rated)
Ducting (Exhaust)- MS Welded Construction- Site Fabricated : Supply, fabrication and erection of following gauges of MS ducting complete with welded drip proof seams and having access doors at every change in direction with maximum spacing of 6 meters in horizontal direction and maximun of 3 floors of vertical risers & elbows spliters, supports/suspenders bends, tees, vanes, double canvas connection of the equipment etc all complete as required. Duct shall be insulated 25 MM Thich High Density Rockwool Insulation 48 KG/m3 . The insulation material and its installation shall be in accordance with the specifications as provided. The entire insulation shall be covered with muslin cloth over which 2 coats of Star Bond / approved fire paint is applied to make the insulation hard and fire retardant.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
16 gauge (1.5 mm thick)
100 CFM at 10 MM ESP
150 CFM 10 MM ESP
200 CFM at 10 MM ESP
300 CFM 10 MM ESP
850 CFM 15 MM ESP
900 CFM at 15 MM ESP
1000 CFM at 15 MM ESP
1200 CFM at 15 MM ESP
Supplying, installing, testing and commissioning of direct drive industrial propeller fans. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Speed regulator and all other accessories required to complete the installation shall be included. The fan shall be of following rating:including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
300 dia, Noise level 38 DB at 3m,fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.
Drain Piping Supplying & fixing of 8 Kg/m3 density UPVC pipe (heavy duty) with 9 mm thick closed cell nitrile insulation (tube insulation) with protective coating as per the approved shop drawings and specifications.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
uPVC pipes of 25 mm dia
uPVC pipes of 32 mm dia
uPVC pipes of 40 mm dia
Supply, installation, testing & commissioning of powder coated extruded aluminium disc valves for toilet exhaust as per specifications including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
150 mm Dia
Louvers (Heavy Section) Providing and fixing of powder coated extruded aluminium exhaust air louvers/ fresh air louvers with bird screen and mounting arrangement as per specification and drawings. Free Area shall be more than 60% of gross area.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Fresh Air / Exhaust Air Louvers with Bird Screen Mesh
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. High Static Ductable units (minimum 110 pascal external static pressure).
Domestic Water Supply Boosting Pumps (Hydropneumatic Type VFD based) - Hotel Block including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Supply, Installation, testing and commissioning of packaged type skid mounted factory fitted and factory assembled hydropneumatic system with Variable frequency drive (on all Pumps) type comprising of :- Vertical, inline multistage centrifugal pumping set with stainless steel SS-304 stage casing and SS-304 impellers with stainless steel SS-316 shaft as per IEC standards and CI suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply, complete factory fitted and factory assembled Pressure vessel of suitable capacity, non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles.
Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump working sequence should change after every operation.Contactor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan.Pressure switches/transmitters bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class.Suction & Discharge Manifolds in MS CED Coated along with Valves,NRV, Pressure gauges, SS flanges, other fittings etc.Complete set system to be mounted on a common base frame and shall be following duty.Domestic water supply pumps (Location - Pump Room ), Flow Rate = 450 LPM of Each Pump, Head = 60 M, 1 Set includes 2 Nos. Pumps - (1Working+1Standby),Motor Efficiency Class - IE5, Make: Grundfoss/ Xylem/ Ebara
Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump working sequence should change after every operation.Contactor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan.Pressure switches/transmitters bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class.Suction & Discharge Manifolds in MS CED Coated along with Valves,NRV, Pressure gauges, SS flanges, other fittings etc.Complete set system to be mounted on a common base frame and shall be following duty.Domestic water supply pumps (Location - Pump Room ), Flow Rate = 450 LPM of Each Pump, Head = 60 M, 1 Set includes 2 Nos. Pumps - (1Working+1Standby),Motor Efficiency Class - IE5, Make: Grundfoss/ Xylem/ Ebara
Design, fabrication, assembling, wiring , supply , testing , Installation , commissioning, Delivery to site of 11KV / 415V, 1000 KVA outdoor type Unitized Compact Package Substation with facility for internal lighting, earthing, padlocks, Thermosatat, Exhaust Fan etc. Connection between VCB & Transformer will be by 11kV XLPE copper cable/Busbar and connections from Transformer to LT ACB shall be by busbar connections. Cable Termination kits for VCB and ACB etc. (within enclosure and conforming to latest IEC standards). The Complete Substation should be Factory Assembled with access to the Transformer Compartment from either side of the CSS. The Substation should have facility of Detachable Top for the Transformer Compartment to have access to Transformer, incase of any situation / requirement arising for removing the Transformer from the Top alone without disturbing the HT and LT Compartment. The Substation Enclosure should be Weather Proof made up of 2.0 mm (for load bearing members) thickness and 1.6 mm (for non load bearing members) Enclosure with the Base of 4.0mm thickness Hot Dip Galvanised Iron. The Substation should be adaptable for relocation without removing any of its components in case of any change in the Substation Location arising in the future. The Enclosure should be Tested for Internal Arc Withstand Capacity as per IEC Compact Substation to be dust and vermin proof, conforming at least to Ingress Protection degree, (outdoor) IP54 for LV/MV Chambers & IP23 for Transformer Chamber. Dual Earthing Bushes shall be provided for Neutral & Earth on either side of the CSS
Package Substation shall be complete with following : 1 No. 11 kV VCB for 1000 KVA Transformer and with following Static type Self Powered IDMT RELAY for Circuit Breakers. he Circuit Breaker shall be provided with Integrated Earthing Switches with Making Capacity T Live Cable Indicator Pressure Indicator Padlocking facility Powerpack ( 1W + 1S) complete with all accessories Transformer : 1000 KVA, 11 /0.415 KV, 3 phase, 50 Hz, delta/star connected, step down Oil Type transformers ( ONAN) vector group Dyn-11. On Load tapp changer , RTCC panel with all accesories as required on HV side shall be provided for variation from (+)5.0% to (-)10% in 12 steps of 1.25% each. Cable end box suitable for 3 core 300 Sqmm XLPE Al. conductor 11 KV grade cable on HT side and 6 Nos. 3.5 core 300 Sqmm XLPE Al. Armoured cables on LT side with all fitting and accessories, OTI , WTI alarm and trip wiring complete as required (The transformer shall be subject to all tests as required and test certificates shall be produced). LT Side : LT INCOMER CUM OUTGOING : 1600 A FP Manual Drawout ACB 35KA with microprocessor O/L , S/C and E/F Releases and complete with Multi function meter , CTs , Control MCBs , indication lamp as required suitable arrangement / Links shall be provided for 4 Nos. 3.5 core 300 Sqmm XLPE Al. Armoured outgoing cables 1000 kVA Package substation as described above including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Design, fabrication, assembling, wiring , supply , testing , Installation , commissioning, Delivery to site of 11 KV Compact 3 way RMU comprising of 2 No. 12KV, 800 A, 25.0 KA for 3 Sec. Mannual Load break switch module and 1 No. 12 KV, 800 A , 25.0 KA for 3 sec Compact Mannual type VCB as outgoing complete with earthing switch, bus bars, interlocking and earth bar and complete with following: 1 No. Multifunction meter having 30 days memory and parameters of KW, KWH, KVAH, KVARH power factor, frequency etc.(shall be provided with RS-485 and other communication ports) 3 Nos. double wound, dual ratio C.T.'s 75/5 A Core 1-15VA burden class 0.5 for metering. Core 2-15VA burden class 5P10 for protection 3 nos. line PT 11KV/ √3, 110V/ √3, 100VA class 0.5 epoxy cast resin type. Static type Self Powered IDMT RELAY ( Over current/earth fault relay 50 / 51 / 50N/51N ) for Circuit Breakers. One(1) No. Snap action mech. for manual operation One(1) No. Cable bushings suitable for 630 A One(1) No. Arc proof cable cover complete include interlocking The Ring Switches and Tee-Off Circuit Breaker are provided with Integrated Earthing Switches with Making Capacity Live Cable Indicator for ring switches Pressure Indicator ( Manometer) Padlocking facility HT Danger Plate 3 Way 11 KV RMU as described above complete in all respects and as per enclosed SLD including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
SITC OF 500 KVA DG SET : Providing, Installing, Receiving, unloading, shifting to Sub-Station, storing, handling, Testing and Commissiong of 'Silent Type' Diesel Generating set alongwith Prime Power Rating 500 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 433V suitable for 50 Hz, 3 phase system & for 0.80 Load Factor . DG set shall be as per latest CPCB norms ( CPCB- IV) DG Set shall consist of the followings: Diesel Engine: Diesel engine 4 stroke radiator Cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 50 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continous operation. The engine will be fitted complete with electronic Governer and all the required accessories. Engine mounted Instrument Panel fitted with and having digital display for following: (i) Start-stop switch with key (ii) Coolant temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication (vi) RPM indication (vii) Over speed indication (viii) Low lub. Oil trip indication (ix) Engine Hours indication (x) Engine protection unit and sensors for winding & bearing temperature monitoring (xi) Remote Monitoring Module Alternator Synchronous alternator rated at 500 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.80 lagging power factor at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having microprocessor based controller with BMS compatibility, SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class-F/H insulation. Cable termination Box suitable for 3 Nos. 3.5C-300 Sq. mm Al Arm Cable
Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and antivibration mountings arrangement as per recommendations of manufacturer.Fuel Tank: (External) Daily service fuel tank of suitable (900 Litre) capacity fabricated out of 3 mm thick M.S./CRCA sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor. Starting System: DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 2 x 65 AH, 12V capacity SMF lead acid type) as required as per specifications. Accoustic for weather and noice proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per CPCB-II Norm & technical specifications. Complete one Set Supply, installation, testing & commissioning of 990 litres capacity day oil storage tank fabricated from 6 mm thick MS plates. Tank shall include 450 mm ID manhole cover, level indicator with duly calibrated scale and flanged connection for inlet, outlet, overflow drain and probe provision for level controller & breather. Supplying and fixing Exhaust gas piping of 1x200 mm dia. welded black MS, B Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50 mm thick wire mesh & aluminum cladding etc., as required as per specifications.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
SITC LED light fixture (4000k) with fixing clamps,nuts,bolts and fixing arrangement as per required with complete accessories all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. Make Philips/Wipro or as per recommend or approved by architect.
12 WATT COB LED DIMMABLE SPOT LIGHT (TYPE-_01) as approved by architect.
12 WATT COB LED SPOT LIGHT TYPE-_02 as approved by architect.
12 WATT COB LED SPOT LIGHT TYPE-_03 as approved by architect.
HANGING-1 as approved by architect.
HANGING-2 as approved by architect.
LED STRIP as approved by architect.
NIGHT BULB as approved by architect.
SURFACE-1 (1200MM) as approved by architect.
SURFACE-2 (ROUND / SQUARE) as approved by architect.
LINIOS (1000MM) as approved by architect.
LINIOS (1800MM) as approved by architect.
LINIOS (2400MM) as approved by architect.
CONCEALED as approved by architect.
LIGHT (600X600) as approved by architect.
SPOT LIGHT-01 as approved by architect.
SPOT LIGHT-02 as approved by architect.
CHANDELIER_TYPE-01 as approved by architect.
CHANDELIER_TYPE-02 as approved by architect.
CHANDELIER_TYPE-03 as approved by architect.
CHANDELIER_TYPE-04 as approved by architect.
CUSTOMIZE LIGHT-01 as approved by architect.
CUSTOMIZE LIGHT-02 as approved by architect.
TRACK LIGHT as approved by architect.
Supply of 800 MM Long Decorative type C Type Diffuser IP65 LED Bollard 11 Watt 1100 Lumens 4000 K, PF ≥0.95, THD ≤10%, Housing made of extruded aluminium, Input Voltage Range 140-280 V, 3 KV Inbuilt Surge Protection. Ref Make : Wipro, Philips Color Kinetics, LT. including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 15 Watt IP65 with IK06 and toughend glass protection, housing made of Extruded aluminum housing duly pure polyester powder coated Dark gray color , Designed and manufactured to comply with IS 10322 part 5/Sec 1 2012 . Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 10 Watt , IP65 Bush Light 4000 K, PF ≥0.95, Housing made of Pressure die cast aluminium with toughend glass protection, Input Voltage Range 140-280 V, 3 KV Inbuilt Surge Protection. Beam Angle is 36 Degree.Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 60 Watt LED IP 66 Posttop made of pressure die cast aluminum housing, system efficacy 120 Lumen Per Watt, luminare should be dry sky certified, CCT 5700 K, Tempered Glass with polycarbonate lens for symmetric light distribution.Luminaire is dark sky certified.Surge Protection : 5 KV. Ref Make : Wipro , Philips, LT including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 40Watt LED Linear Washer 1000 MM Long IP66, IK06 Protection with Toughend Glass Protection, Extruded aluminum housing & PDC End cap duly pure polyester powder coated in dark grey (RAL7021), Beam angles – Symmetric & Asymmetric. CCT 3000 K. Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 20 Watt LED Linear Washer 500 MM Long IP66, IK06 Protection with Toughend Glass Protection, Extruded aluminum housing & PDC End cap duly pure polyester powder coated in dark grey (RAL7021), Beam angles – Symmetric & Asymmetric. CCT 3000 K. Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 250mm Dia X 90 mm Height 3000K LED Inground light with Non- Integral driver & completely made in India luminaire. The luminaire’s shall be made of Aluminum die cast housing duly Powder coated. The complete luminaire has IP67 & IK10 protection and it comprises of high purity integrated poly carbonate Lens.The LEDs shall have minimum CRI ≥80 (White LED) & shall have SDCM≤5. The luminaire shall have wattage 36W and shall deliver 1800 lumens. Beam angle of the Luminaire shall be 60 deg .Fixture shall operating temperature range of 0°C to 45°C. Input Voltage Range of 24V DC, Integrated DMX Decoder,No need to additional external decoder. The luminaire shall have declared life of 50,000 burning hours at L70. Luminaire and Driver must be made in India with same brand. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer along with technical bid. LM80 , RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire. Brand name shall be embossed / engraded on each an every light fixtures. Luminaire and Driver should be Made in India. Luminare, Driver and controller should be with same make. Wipro make - LI20-361-60-30-G2 . Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of Isolated, constant Voltage type 240 W LED Driver enclosure in Extruded Aluminium metal enclosure . Output voltage of the driver 24Vdc. Driver efficiency should be greater than 85% at full load, THD < 10%, PF > 0.95 with Under and Over Voltage Cutoff Protection and 440V withstand for 8 hours minimum & sould have large operating input voltage range of 140V to 300V AC(nominal rated voltage – 240V) with 5KV internal surge protection. LED driver shall have inbuilt output short circuit, over voltage protection, Thermal Shutdown protection. Ref Make : Wipro, Philips Color Kinetics, LT including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of 16mmX16mm of 5 meters length 3000K Flexible strip led light with Non- Integral driver.The luminaire’s shall be made of Silicon extrusion with high-efficiency, high grade appearance, soft bend flexibility & Option of Top bend , the same shall be so designed with completely made in India luminaire. The luminaire shall have silicon glue between optical cover & LED chamber to ensure proper IP67 protection. No need external decoder.The LEDs shall have minimum CRI ≥80 (White Light)& shall have SDCM≤5. The luminaire shall have system wattage of 14 Watt/meter and shall deliver 714 lumens. Fixture shall operating temperature range of 0°C to 45°C. The fixture shall have an Non integral driver with input voltage for 220-240 VAC, 50/60Hz. The luminaire shall have declared life of 50,000 burning hours. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer along with technical bid. Bidder shall submit the following reports along with technical bid LM79 report of the family of luminaire issued by NABL accredited lab, LM80 issued by LED manufacturer BIS certificate for LED Luminaire. Brand name shall be embossed / printed on each an every light fixtures. Wipro make - LF27-14-TB16-30-G1 Ref Make : Wipro,Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Supply of Isolated, constant Voltage type 120 W LED Driver enclosure in Extruded Aluminium metal enclosure . Output voltage of the driver 24Vdc. Driver efficiency should be greater than 85% at full load, THD < 10%, PF > 0.95 with Under and Over Voltage Cutoff Protection and 440V withstand for 8 hours minimum & sould have large operating input voltage range of 140V to 300V AC(nominal rated voltage – 240V) with 5KV internal surge protection. LED driver shall have inbuilt output short circuit, over voltage protection, Thermal Shutdown protection. Ref Make : Wipro, Philips Color Kinetics, LT.including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Dome Camera Supply, installation, testing and commissioning of IP based, 4 MP, FULL HD WDR IR DOME CAMERA - 30 RmtS, colour indoor verifical dome camera, 3.6 MM FIXED LENS, 1/3 ", 4 Mega Pixel PS CMOS Image Sensor, WDR (120 dB), Day/ Night (ICR), IR Range of 30 Rmts, IP67 and all ancillary equipments and all accessories including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. CP PLUS MAKE - UNC DD40L3-D OR EQUIVALENT IN OTHER MAKES LIKE SONY/ HONEYWELL.
Bullet Camera Supply, installation, testing and commissioning of IP based, 4 MP, FULL HD WDR IR bullet CAMERA - 40 RmtS, colour indoor verifical dome camera, 3.6 MM FIXED LENS, 1/3 ", 4 Mega Pixel PS CMOS Image Sensor, WDR (120 dB), Day/ Night (ICR), IR Range of 40 Rmts, IP67 and all ancillary equipments and all accessories including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge. CP PLUS MAKE - UNC TD40L4-D OR EQUIVALENT IN OTHER MAKES LIKE SONY/ HONEYWELL.
Supply, Installation, Testing and commisioning of 40" inches LED monitor make (sony or as approved by the engineer incharge) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
EV Charging Station Supplying, installing,testing and commissioning of Electic Vehicle Charging Station Kazam make Model Kazam 3.3, Product Dimensions 27 x 19 x 13.5 cm; 2.02 Kilograms, Item part number KZ001, Manufacturer Part Number KZ001, Material ABS PLASTIC, Colour White, Special Features Convenient to install, All weather and waterproof, Real time data analytics, IOT enabled charging, Wattage 3.3 KW, IP67 certified, Ip (max) 20 Amp, Vp(max) 280 Volts, Input voltage 1 Phase 230 V AC, Connectivity SIM Based, MCB & Fuse YES, Wire 3 wires ( live, neutral and earthing/ 2.5 sq mm), Output connector type 3 Pin socket, Output current 16A max, Output current 3.3KW, theft proof, B/W EVSE & CMS MQTT/TCP, All weather functionality YES Dust & water proof), Number of Outputs 1, Ambient Temperature -30C to 55C, Cooling: Natural including all civil work. (Kazam or equivalent ) including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.
Providing ,fixing , testing and commissioning of DC EV CHARGER 60KW As per Bharat EV Specification Connectors: CCS2 Number of plugs: 2 AC input voltage: AC380V±15% AC input frequency: 45-65Hz DC output power: 60KW DC output voltage range: 150 VDC – 1000 VDC DC output current: 0-250 AmpConnectivity authorization: RFID/NFC, App, VIN IP55 *1 year’s warranty *5m cable *4G/Ethernet/Wi-Fi*OCPP 1.6 *7-inch LCD screen/LED light complete in all respect including carriage of material by mechanically & manual upto all lead & lift and as per direction of Engineer incharge.( including all civil work)
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.47 MB
Drawings00to03.pdf
Tender Documents • 27.75 MB
Drawings04to06.pdf
Tender Documents • 32.55 MB
Drawings07to01.pdf
Tender Documents • 32.62 MB
Drawings7to73.pdf
Tender Documents • 20.46 MB
OtherDrawings.pdf
Tender Documents • 26.96 MB
TenderDocumentFinal.pdf
Tender Documents • 2.46 MB
BOQ_187925.xls
BOQ • 2.14 MB
Download all tender documents and submit your bid