Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹56.4 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹58.4 L+₹2.0 L (3.57%)Rejected-Finance | L2 | Rejected-Finance L2 Bidder | |
| 3 | L3₹60.8 L+₹4.4 L (7.86%)Rejected-Finance ASWATHY NIVAS MAMPAZHAKARA PERUMPAZHUTHOOR NEYYATTINKARA P O THIRUVANANTHAPURAM 695126 | THIRUVANANTHAPURAM | KERALA | 695126 | L3 | Rejected-Finance L3 Bidder | |
| 4 | L4₹60.9 L+₹4.6 L (8.08%)Rejected-Finance | L4 | Rejected-Finance L4 Bidder | |
| 5 | L5₹61.6 L+₹5.2 L (9.22%)Rejected-Finance | L5 | Rejected-Finance L5 Bidder |
Tender Value
₹61.6 L
EMD Value
₹50,000
Closing Date
30 Oct 2019, 3:00 pmClosed
The Managing Director, INKEL Limited
2nd Floor, Ajiyal Complex, Kakkanad, Cochin, Pin 682030
SITC of point wiring, Distribution Boards, LT Cabling and Termination, ELV Cabling and fire alarm works
2019_INKEL_308234_1
NIT/INKEL/ALP/2019-20/096 dated 11/10/2019
Open Tender
Electrical Works
Item Rate
180 days
Alappuzha
As detailed in tender document
11 documents required · 11 mandatory
₹2,975
Online
₹50,000
16 Jan 2020
11 Oct 2019
31 Oct 2019
11 Oct 2019
30 Oct 2019
18 Oct 2019
11 Oct 2019 - 26 Oct 2019
Amount
CONDUITING & WIRING
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 2.50 sq.mm 3 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 1.50 sq.mm 3 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 1.50 sq.mm 2 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 1.00 sq.mm 2 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 4.00 sq.mm 3 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 6.00 sq.mm 3 Run
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 32 mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 40 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 150 mm X 150 mm X 60 mm deep
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 200 mm X 300 mm X 60 mm deep
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 2 way 5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) 6A universal socket
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Telephone socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required. Upto 450 mm sweep
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 6 Module (200mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 8 Module (125mmX125mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 12 Module (200mmX150mm)
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing of following sizes of medium class Oval PVC conduit along with all accessories in surface and making good the same as required. 20 mm
Supplying and fixing of following sizes of medium class Oval PVC conduit along with all accessories in surface and making good the same as required. 25 mm
S & F Motor starters of the following ratings Single phase DOL starters for 0.25HP to 3HP motor
S & F Motor starters of the following ratings Three phase DOL starters for 0.25HP to 7.5 HP motor
DISTRIBUTION BOARDS
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4+12), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4+12), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4+18), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4+24), Double door
Supplying and fixing following way prewired SP&N MCB distribution board of steel sheet for 240 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/Isolator) 2+4 way, Double door
Supplying and fixing following way prewired SP&N MCB distribution board of steel sheet for 240 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/Isolator) 2+8 way, Double door
Supplying and fixing following way prewired SP&N MCB distribution board of steel sheet for 240 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/Isolator) 2+12 way, Double door
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall ,making good the damages, colour washing etc. as required. 6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
Energy Meter Cubicle Fabrication, Supply, Installation, testing & Commissioning of Lockable type energy Meter cubicle made out of 16 SWG CRCA sheet with view glass and consisting of following (Complete with all interconnections and powder coated painting - to be fixed outside the building) : a. Separate chamber for 3-Ph energy meter with provision for fixing CTs, Cutouts etc. b. 3 Nos.125A Open Type bakelite cutout fuse unit with 125A HRC fuses & Fuse Holders. NOTES: Liasoning and Submission of Documents for getting power connection & Load Regularisation from KSEB/EI is under the scope of contractor. Neccessary statuatory charges will be reimbursed upon the submission of orginal challan/Payment Receipts.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
Supplying and fixing following rating 25A, FP, 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating 32A, FP, 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating 25A, double pole, (single phase and neutral), 240 V, RCBO,having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating 32A, double pole, (single phase and neutral), 240 V, RCBO,having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating 32A, FP, 415 V, RCBO, having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5A to 32A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing 5A to 32A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
Supplying and fixing 40A to 63A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
CABLES & TERMINATIONS
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx70sq.mm Al Cable
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) ammended upto date. 4cx35sq.mm Al Cable
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) ammended upto date. 4cx16sq.mm Al Cable
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) ammended upto date. 4cx10sq.mm Al Cable
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) ammended upto date. 3cx10sq.mm Al Cable
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor, AXFY power cable confirming to IS 7098 (part 1) ammended upto date. 3cx04sq.mm CU Cable
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 70 sq. mm (38mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 35 sq. mm (32mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 X 10 sq. mm (22mm)
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3C X 04 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Upto 35 sq. mm.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
EARTHING
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 3.15 mm copper conductor ( 10 SWG)
CABLE MANAGEMENT SYSTEM
Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required (including all accessories like Flat Angle, Tees, bends, Internal Coupler, Cross, End caps, cable retainer etc........... as required and directed by Engineer in charge) . 50x50mm Cable Management System with base and lid
Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required (including all accessories like Flat Angle, Tees, bends, Internal Coupler, Cross, End caps, cable retainer, cable divider, Module mounting Box, adopter etc........... as required and directed by Engineer in charge) . 100x50mm Cable Management System with base and lid.
Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 63/50 mm or nearest size
MISCELLANEOUS
Supply and providing First Aid Box.
Supply and providing laminated First Aid chart duly framed and placed in a conspicuous location for clear vision.
Supply and providing 6mm Thick MS chequered plate including cutting, welding, painting etc. as required for cable duct covering etc.
Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand for 2 nos of fire buckes, or , duly painted over a coat of primer.
Fabrication and installing of MS supports & other steel works associated with electrical works completion and required as per site conditions using structural steel work (riveted, bolted or welded) in built up sections, including angle, channel, I section, necessary nut and bolt and all required accessories including cutting, hoisting, fixing in position and applying 2 coats of zinc chromate primer and 2 coats of synthetic enamel paint of approved quality and colour as directed by engineer in charge.
Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors,suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, bends, Tees, Reducers etc. as required and directed by Site incharge. 150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors,suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, bends, Tees, Reducers etc. as required and directed by Site incharge. 300 mm width X 50 mm depth X 1.6 mm thickness
FIRE ALARM SYSTEM
Providing, fixing, testing and commissioning of EN / LPCB approved Optical Multi-criteria detectors complete i/c accessories, 12 / 24 volt D.C, with dual LED with 360 degrees view, blink in normal conditions & steady Red in case of Fire/ Fault conditions.
Providing, fixing, testing and commissioning of resettable type manual Call station with Fire written on the front side capable of giving individual address.The manual pull station should have an indicator, which should "blink" green in case of normal condition and become steady Red in case of Operation.
Providing, fixing, testing and commissioning of electronic Strobe hooters housed in Polymer housing suitable for wall / ceiling and surface mounting including making connections with wires complete in all respects and as per specifications.
Providing, fixing / laying, test and commission 2Core x 1.5 mm2 FRLS Armoured Cables with Red Colour, as per Technical Specifications.
ELV SYSTEM
Supply, Laying & Termination of 2Cx1.5sq.mm FRLS type,flexible copper cable for PA System.
SITC of 6U Wall Mount Rack with power distribution unit, cable managers, fans and other accessories.
SITC of 9U Wall Mount Rack with power distribution unit, cable managers, fans and other accessories.
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 1 run of Cable.
Supplying, fixing testing & commissioning of CAT-6 information oultets and accessories.
Supply & Laying of Outdoor O. F. Cable 6core SM.
Supplying,Installation, testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 Amp, for mounting height up to 2.8 Mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming and site etc. complete as required Make: Lutron, Philips, Wipro, GE, Honeywell
Supplying, installation, testing and commissioning of Astronomical time switch capable of following output in feeder pillars/ Lighting DBs for automatic switching On &OFF of street lights at sun set & sun ruse or twilight override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete ad required 2 output per phase and suitable for single phase supply. Make: Lutron, Philips, Wipro, GE, Honeywell
MISCELLANEOUS CIVIL WORKS
Demolishing brick/ block work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge-In cement mortar
Core cutting for following sizes of Pipes, in following Structures, including grouting the holes with GP2 Conbextra or approved equal. In floor/roof slab, thickness 120mm.(approx.) 63mm. O.D.
Core cutting for following sizes of Pipes, in following Structures, including grouting the holes with GP2 Conbextra or approved equal. In floor/roof slab, thickness 120mm.(approx.) 110mm. O.D.
Earth work excavation in all kinds of soil for foundation, trenches, grade beams, etc including strutting, shoring and packing cavities wherever required, bailing /pumping out water from any depth, if required and getting out the excvated soil and back filling the soil as required in layers not exceeding 20 cm in depth, consolidating each layer by watering, ramming etc and disposing of surplus excavated earth, stacking of serviceable stones, disposal of unserviceable materials away from site with initial lead upto 50m and lift upto 1.5m including breaking clods, watering, ramming and sectioning of soil bank etc complete as directed by the Engineer-in-charge.
Providing and laying 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 40 mm nominal size) machine mixed and properly consolidated with hand rammers, including the cost and conveyance of all materials, labour, centering and shuttering, curing, lead lift etc complete at all levels, including anchor bolt fixing, making good surfaces etc and as directed by Engineer-in-charge: for machine foundation bases, pedestals etc....
Reinforcement steel - Providing and fixing reinforcement for RCC work with Thermo-Mechanically Treated (TMT) bar of various diameters and grade of steel as specified below confirming to IS 1786 in grade Fe-415 or higher grade BS specification including cutting, bending, hoisting, fabricating and placing in position according to drawings and binding the reinforcement with galvanised annealed binding wire of double fold of 18 guage and providing PVC cover blocks for placing the reinforcement in position and for maintaining the cover specified and or according to relevant IS or equivalent BS code. Note: Unless noted otherwise the measurements in accordance with IS1200 or equivalent BS shall be provided. Cover block, wastage and binding wire will not be measured and shall be included in the quoted rates.
Masonry with solid concrete blocks above plinth, blocks of size 30x20x15cm, grade D of block density not less than 1800 kg/cum and average compressive strength of 4 N/mm2 and minimum strength of individual blocks 3.2 N/mm2 (as specified in IS 2185 part I 1979 Grade C) blocks constructed with cement mortar 1:6 for 20cm thick walls including cost and conveyance of all materials to site, labour charges, hire and labour for scaffolding, curing etc complete;
Internal plastering with cement mortar 1:5, 12mm thick one coat over the surfaces of cement block work /brick work including providing ckicken mesh or PVC net making plaster grooves where ever necessary in all heights including cost and conveyance of all materials, labour charges, curing scaffolding etc complete in all floors.
Delstar a Grade Electrical contractors
FI-TEC POWER SOLUTIONS PVT LTD
P V Electricals
POWERON ENGINEERS
TG Thadevoos, windtech
POWERSKILL ENGINEERING SOLUTIONS PVT LTD
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .