Dual 11 KV UG cable drawing work form 110 KV Gvr s/s to Pavarty border area under Electrical Section Pavarty
2026_KSEB_871777_2
73/EE/PMU-TSR/26-27/22-09-2026
Open Tender
Electrical Works
Percentage
Pavaraty
Please refer Tender documents.
4 documents required · 4 mandatory
₹5,900
₹50,000
29 Sept 2026
29 Sept 2026
5 Nov 2026
1 Oct 2026
31 Oct 2026
3 Oct 2026
29 Sept 2026 - 31 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling. | 2 | No | 1,086.23 | ₹2,172.46 |
| 2 | Fitting one Additional 2.4m/3m Channel cross arm (100x50x6mm), in existing 11kV DP including conveyance of materials. | 40 | No | 564.55 | ₹22,582 |
| 3 | Providing additional HT stay on existing stay rod for Making “V” stay. | 2 | E | 664.75 | ₹1,329.5 |
| 4 | Fitting and erecting one HT Double Pole Structure usingPSC pole in position including fitting 2 channel cross arms, digging and back filling pit in ordinary soil, drawing sufficient length of GI earthing leads through all cross arms to the ground for earthing (excluding provision of earthing). | 1 | No | 8,735.82 | ₹8,735.82 |
| 5 | Fitting and erecting one HT PSC Single Pole in position, including fitting cross arm,digging and back filling pit in ordinary soil (as per standards), drawing sufficient length of GI earthing leads from F clamp through V cross arm to the ground for earthing (excluding provision of earthing). | 1 | No | 3,274.36 | ₹3,274.36 |
| 6 | Labour charges for loading HT PSC pole from the stacking place and unloading the same at work site (transportation by any vehicle). | 3 | No | 762.14 | ₹2,286.42 |
| 7 | Charges for HDD including survey of site information collection regarding underground Utilities, pit marking, pilot drilling Pre- reaming pulling 110 mm dia HDPE pipe uncoiling & Laying 11kV XLPE UG 1no 3x300sqmm cable dept. supply thro installed HDD pipe directed by dept. officer CEA std across the road depth more than (1.2m to 2m) GL ( includes cost of HDPE pipe,110mmPN6 configur &PE grade 80, temporary restoration charge for HDD pit with 1:3:6 CC etc.) | 5,500 | m | 2,200 | ₹1,21,00,000 |
| 8 | Doing straight joint on HT XLPE UG cables of sizes beyond 3x185 sqmm and upto and including 3x300 sq mm using the cable jointing kit supplied departmentally as per specification after providing proper traffic signalling and caution board fencing etc. wherever necessary, including charges for cable jointer and other sundries etc. as per the direction of departmental officers at site. | 12 | No | 3,229.41 | ₹38,752.92 |
| 9 | Fitting one set AB switch on existing DP, giving connection and drawing sufficient length of GI earthing leads to the ground for earthing, excluding provision of earthing. | 3 | No | 2,795.55 | ₹8,386.65 |
| 10 | Drilling hole of various sizes on existing Channel/Cross Arm. | 120 | No | 16.73 | ₹2,007.6 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
tenderdocument.pdf
Tender Documents • 1.70 MB
NIT.pdf
Other Document • 0.35 MB
BidFormandQuestionnaire.pdf
Other Document • 0.29 MB
BOQ_1482686.xls
BOQ • 0.23 MB
Tenderclarificationnotice.pdf
PDF • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .