Design, Engineering, Supply, Installation, Testing and commissioning of Non Clog type Centrifugal Pump Set for effluent with accessories and allied Electro-Mechanical and Instrumentation and SCADA work at Vilayat Pumping Station.
300964
E-Tender Notice No. 01 of 2026-27 Sr. No. 15
Open
Mechanical Works
Works
Bharuch
2 documents required · 2 mandatory
₹4,248
Executive Engineer, GIDC, Bharuch
₹1.5 L
4 May 2026
4 May 2026
4 May 2026
18 May 2026
4 May 2026
Name of Work: Design, Engineering, Supply, Installation, Testing and commissioning of
"Non Clog type Centrifugal Pump Set for effluent" with accessories and
allied Electro-Mechanical and Instrumentation and SCADA work at
Vilayat Pumping Station.
Item Description Qty Unit Rate W/O Amount W/O
1 MECHANICAL WORKS: 2 Set 7,99,518.02
SUBMERSIBLE CENTRIFUGAL NON CLOG
Supply, installation, testing &
commissioning of Effluent submersible,
non clog type suitable for working on
three phase, 50 Hz ± 3%, 415 V ± 10%, AC
supply, 1450 RPM synchronous speed
with 3 core flat copper cable from pump
to starter panel with cable end
terminations, all supports, clamps, pipe
fittings along with mechanical seal,
bearing bush, strainer etc. complete set &
following M.O.C: Casing: CI, Impeller: SS
CF8M, Wearing ring & Bearing bush:
Bronze, TC mechanical seal, CS / SS
bearing, SS shaft with sleeve, SS strainer
& MS motor body
Pump Capacity: 313 m3 / hr.
Motor Rating: 45 kW min. (or higher
rating as per pump manufacturer
recommendation)
Starting method: DOL / SD / VFD
(or higher rating as per pump
manufacturer recommendation)Selection
of motor kw rating if not available in this
rating, next higher rating will be consider
2 Design, Engineering, procurement, 2 Nos. 37,962.87
Installation, Testing and commissioning
of required size double flanged Dual
Plate Check Valve (DPCV) - (PN 1.6) -
mm dia (At Pump Discharge) Flanged
Dual Plate Check Valve (NRV) conforming
to API 594 / 598 PN 1.6 with Cast Steel
body, withSS 410 hinge ring and wearing
ring of CF8 all necessary hardwares,
complete as per data-sheet &
Signature of Contractor Executive Engineer (M&E)
specification. Size : 300 mm dia( PN 1.6)
flanges machined faced and drilled to IS :
1538 / 1976 Part-IV/VI. Hydraulic tests
certificate & certificate of material of
construction of parts shall be submitted
before despatch of valves as per design
with required acessories, erection
hardware, necessary mounting supports
etc. complete. 300 mm dia for various
3 Supply, installation, testing & 2 Nos 10,908.00
commissioning of flange ends Expansion
Bellow as per EJMA standards of overall
length of minimum 300 mm, designed for
15 mm axial compression and 5 mm axial
extension with tie rods etc. of following
MOC & pressure ratings.MOC: Bellows: SA
240 Gr. 304; Internal Sleeve: SA 240 Gr.
304; Weldends: IS 2062 Gr. B; Flanges: IS
2062 Gr. B (Drilling as per IS 1538 / IS
6392 ) & Limit Rods & Nuts: CS - IS
PN Rating 1.6, 300 mm Dia.
4 SITC of Cast Steel D/F Electric Actuator 2 Nos 9,30,800.00
operated Sluice Valve of following size as
per API-600/598,Class 150 with Electric
Actuator with integral starter & IP-68
enclosure, body, bonnet and wedge of
Cat Steel Gr. WCB with Body & Seat ring
of ASTM A 216 Gr CF8M, spindle of SS
410, flanges drilled to ANSI B 16.5 of
following diameter along with all other
necessary hot dipped galvanised
hardwares, bolts, nuts & washers, gaskets
including all taxes, insurance,
transportation, freight charges,
Inspection Charges, loading unloading,
conveyance to pump house, stacking,
security with required plain cement
concrete (PCC) support for Valves etc.
within pump house for fixing valve etc.
complete as per Specification and IS.
Size : Dia. 300 mm
5 Provide and supply CI Temper Proof Air 1 Nos 49,161.75
Valves with SS 304 Float Gun Metal
Nozzle of approved make and quality of
following dia of 1.6 PN rating given rate
including all taxes, insurance,
transportation, freight charges,
inspection charges, loading and unloading
conveyance to departmental store/site
Etc.with Isolating Suice Valve.
Size : 300 mm NB
6 SITC of suitable size of above pipes of 100 Kg 58.58
flanged end type fabricated DI/CI Specials
like tee, bend, duck foot bend, tapper,
Signature of Contractor Executive Engineer (M&E)
distance pipe piece, blank flange,
dismentling joint, bolts, nuts, washers,
rubber packing etc.nut bolts etc for
delivery header, rising main and suitable
for above pumps as per actual site
conditions & requirement qty. of specials
mentioned as per deisng requirement
with required acessories, erection
hardware, necessary mounting supports
300 mm dia- Drilled
7 Supplying and fixing Steel chequered 20 Sq. Mtr 5,780.23
plates having 12 mm thickness, duly
painted with two coats of black Japan
colour. (Average Wt 200.3 kg / Sq.Mtr.)
8 Supply, cutting, welding, installation, 8 Rmt 1,235.23
connection with main header, testing and
commissioning Making of Flanged joint to
flanged DI/CI pipes of all classes/ Special
etc. including all taxes, insurance,
transportation, freight charges,
inspection charges, loading and unloading
conveyance to departmental store/site
Size: 300 mm dia.
9 Single Girder EOT CraneSupply, 1 Set 5,11,312.50
installation, testing & commissioning
single girder type fully electrically
operated EOT crane with electrically
operated hoist, class II duty, geared
travelling trolley with seven meter lift
complete with long travel rail track (40
mm sq. bar), moving or cross girder, all
three motions electrically operated by
suitable rating motor IP 54, control panel
& down pendant control block, brake,
safety device, cables form motor to
starter panel & other required
accessories & tested as per IS
Specifications.Capacity- 2 T, Span- 6-9
Mtr, Long Travel- 12 Mtr, Lift 6-10 Mtr
10 SITC Chain Pulley block of 2 ton capacity, 1 Nos 17,574.00
lift as per site condition with gantry
girder, erection hardware, necessary
mounting supports etc complete.make as
11 DEWATERING PUMP 2 Nos 1,47,811.48
Supply, erection, testing and
commissioning of non clog submersible
Drain Pump with CI casing & CF8M
impeller,including necessary accessories
and hardwares, etc., 15m cable for motor
to starter panel, suitable for 3Phase,
V, 50 Hz AC supply and min. 2.2 kW
motor, Switch-Starter panel with suitable
Signature of Contractor Executive Engineer (M&E)
inter lock for winding protection, min.
m long required size cable to supply
power to control panel from nearby
power source, moisture controlar along
with level switches for dry run protection
for auto stop facilities, cable termination
junction box of required terminal size,
supporting arrangement for pump and
other required accessories,
Capacity : 10 - 15 m3 / hr.
( to be installed in dry well drain pit.)
12 PORTABLE DEWATERING PUMP / 1 Nos 1,94,690.63
Supply and testing of Submersible non
clog Portable Dewatering Pumpset with
C.I. casing & CF8M impeller, 25 m flexible
PVC delivery hose pipe of pump delivery
size, rated for 6.0 kg / cm2 presure,
mtr SS lifting chain, 20m pair of cable for
motor to starter panel, suitable for
3Phase, 415 V, 50 Hz AC supply and min.
5.5 kW motor, min. 10 m long required
size cable to supply power to control
panel from nearby power source, Switch-
Starter panel with suitable inter lock for
winding protection, moisture controlar &
dry run protection auto stop facilities,
SS/CI pump stool and other required
accessories for wet well.
Capacity : 50 m3 / hr.
Motor Rating: Mini. 5.5 kw
13 MISCELLANEOUS: 800 Kg 65.49
Providing, Supply of Structure Steel at
site of work with freight, loading,
unloading carting, etc. including all taxes
and duties complete such as joints,
channels, angles, plates, iron rails,
ISA/ISMC/ISMB/MS flat, plate (below
10mm thickness) etc. required for
support structure of Elecrto-Mechanical
equipments etc. for support on floor /
wall / beam / brackets etc. as per tender
14 Labour Charges for lowering, laying, 1 MT 11,478.65
Fixing with fabrication various size
section of MS such as joints, channels,
angles, plates, iron rails,
ISA/ISMC/ISMB/MS flat, plate etc
Complete with two coats of red oxide and
two coats of approved colour shade of
epoxy paint as per relevant IS and as per
Signature of Contractor Executive Engineer (M&E)
15 Tools as per Annexure (M) and as 1 Lot 2,50,000.00
recommanded by manufacturer.
16 ELECTRICAL WORK 1 Nos 37,601.29
TPN MCCB (For LT Service Obtaining
SITC of 200 A TPN microprocessor MCCB
with O/L, S/C & E/F protection with
Extended rotary handle, Terminal
spreader, Auxiliary change over & Trip
contact, with Outdoor Enclosure with
canopy 2mm thick , Single/double door &
Wall mounted/ stand mounted as per site
requirement (with incoming & outgoing
cable entry at bottom )with Cable end
boxes with RYB indicating lamp, Digital
voltmeter, VSS, ON,OFF & Trip indicating
lamp etc as per Power supply company
requirements & location. Including all
civil works for fixing of panel on wall.
(Wall mounted at Location as per PSC
17 LV APFC PANEL 1 Set 1,89,950.70
Supply, installaton, testing &
commissioning LV APFC panel consisting
of required capacitor banks for
continuous duty to improve P.F. 0.85 to
0.99 in required steps enclosed in dust &
vermin proof compartment, indoor type,
fabricated from CRCA sheet steel with
minimum thickness of 3 mm for base
frame / channel / gland plates, 2.0 mm
for load bearing members / doors &
mm for internal partitions, minimum
degree of protection - IP 42, busbar
chamber, required size of Al bus bar /
terminals, minimum 10 stage APFC relay,
metering, indicating lamps, push buttons
complete as per IS: 16636-2017 with
latest ammendment & detailed technical
specification and
data sheet as under
Above 50 & up to 100 KVAR: APFC panel
consisting following items.
a) 250 A, 50 kA for 1sec. TP, TM based
MCCB with spreader terminals & rotary
b) 0-250 A range analogue ammeter of
x 96 mm size with selector switch
c) 3nos. 250 / 5A, 10 VA CL-1.0 cast resin
type current transformer
d) Suitable rating of MCCB / MCB &
Contactors for each capacitor bank
e) Suitable rating APP type capacitor
banks (vacuum impregnated with non-
Signature of Contractor Executive Engineer (M&E)
PCB / non toxic oil, internally delta
connected with built in internal fuses
complete with discharge resistances &
terminal cover) of approved make in
required steps with well suited detuned
reactor is placed in series with each
capacitor step. ( e.g. 100 KVAR capacity
will be provided in steps of 2 nos x
KVAR, 2 nos x 10KVAR, 2 nos x 15 KVAR
& 2 nos x 20 KVAR)
f) Enclosre dimensions: 2100 (H) x
18 Design, Supply, Installation, Testing and 1 Nos 3,44,504.94
Commissioning of Power cum Motor
Control Centre of 200 A, 415, TPN, Power
Cum Motor Control Centre (PCC) cubical
having depth not less than 750 mm
throghout the required length &
detachable, fabricated from 2 mm CRCA
sheet steel, free standing, floor mounted,
compartmentalized, extensible, dust and
vermin proof enclosure, duly painted
provided with required rating switch
gears and shall be complete with (a)
required size of TPN Electrolyte 100 A
Copper bus bar having cross section not
less than 1.6 Amp per 1.0 Sq. MM, (b)
Nos. - 100 Amp capacity of 4 pole-
microproccessor based MCCB with
computer interface (2 Nos. for incomer +
1 No. as Bus Coupler) (c) 3 Nos. -
Amp capacity of 4 pole - microproccessor
based MCCB computer interface - All
release of all MCCB should have in built
power meter/ analyser having, 3 phase,
V, KW, I, KVA, KVAh, KVArh, PF,
Frequency, harmonic analysis up to 30th
harmonic and last ten faults history.with
computer interface facility and all other
required protection etc., complete. ,The
PCC shall be supplied as per detailed
specifications & single line diagram (SLD)
complete and the instruction of Engineer
19 Microprocessor Based LV Variable 2 Nos 1,11,862.55
Frequency Drive
Suppl, installation, testing &
commissioning of 415 V Fully automatic
microprocessor based Variable
Frequency drive for pump control
application as per general specification as
The VFD unit shall have modular
construction, 6 Pulse Bridge rectifier,
speed control by means of sensorless
Signature of Contractor Executive Engineer (M&E)
vector control (open loop), high torque at
low frequencies, locking at high and low
frequency settings, In-built PID control,
frequency accuracy of ± 0.1 % (min),
frequency resolution of ± 0.1 Hz (min),
protections against; a) overload (motor
and drive), b) short circuit, c) ground
fault, d) input / output phase loss (open
circuit), e) stalling, f) input / output
undervoltage (momentary power loss
restart), g) input / output overvoltage, h)
over-frequency, i) Input surge, j) over
temperature of heatsink, k) loss of remote
speed signal etc. The VFD shall also have
user friendly programming software & it
shall be capable of at least two level
parameter setting with password lock for
critical parameters, programming for
I/Os, speed search function, copy
parameters (upload / download) to other
identical unit, tuning to energy saving
mode (maximum efficiency), event / fault
recording (last 5 faults in non-volatile
memory) & RS 485 communication port
(MODBUS RTU protocol) with required
software. for 55 Kw
20 SITC of Lighting Distribution Board (LDB) 2 Nos. 20,998.91
SITC of 3 Phase 4 Wire 4P, double door
Prewired LDB each for Indoor Lighting &
Outdoor Lighting Suitable to house :
Incoming: 200A FP, ELMCB (30mA)
Outgoing: 63A SP MCB (9 nos.) & 63A SP
21 3 Phase 4 Wire TPN, 8 way Pre-wired- 1 No. 8,876.89
aux. Load for Auxiliary accessories Load
power supply (For 1no.EOT Crane at P.H.,
1no.WR-DB at P.H.maintenance floor,
1no. WR-DB at P.H Pump Floor, 1no. WR-
DB at LT Room, 1 no. WR-DB at Inlet
chamber & rest spare) Incoming: 20A 4P,
MCB 'C' Curve Outgoing: 8 nos. 20A 4P
22 SITC of LCS pushbutton station ON & OFF 4 Nos 2,384.61
(E-stop) set complete with Enclosure,
necessary mounting/ fixing arrangement
on wall / pipe support etc. to be installed
near motors for remote operation, etc. as
per IS and specifications. (including
structural steel) (For 4 nos. for Pump )
23 SITC of Local Control Station with 4 Nos 2,736.09
pendant type Open_Stop_Close
pushbutton set and with Open, Close, Trip
& Local / Remote Indicating Lamps
complete with Enclosure, necessary
Signature of Contractor Executive Engineer (M&E)
mounting/ fixing arrangement on wall /
pipe support etc. to be installed near
motors for remote operation, etc. as per
IS and specifications (including structural
24 LOW VOLTAGE (LT) CABLES 180 Mtr 135.34
Supply, laying, testing and commissioning
of 1.1 kV, A2XFY(X)/2XWY(X) XLPE
insulated (IS 7098) AL stranded
conductor, Extruded innersheath cables
as per specification & IS. The cable when
laid outside the building shall be laid
underground in trench with brick & sand
protection/in DWC pipes as per specified
method and shall be laid in prepared
trench/ on cable tray when laid inside
SITC of 3.5C x 16 sq. mm. A2XFY(X) Cable
25 3C x 16 sq. mm. A2XFY Cable 180 Mtr 90.90
26 4C x 10 sq. mm. A2XFY Cable 120 Mtr 97.97
27 4C x 16 sq. mm. A2XFY(X) Cable 120 Mtr 109.08
28 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable 50 Mtr 70.70
29 5C x 1.5 sq.mm. 2XWY(X) Cable 50 Mtr 150.00
30 12C x 1.5 sq.mm. 2XWY(X) Cable 50 Mtr 320.00
31 2C x 2.5 sq. mm. 2XWY(X) Cable 50 Mtr 49.00
32 Single core 95 sq. mm. PVC insulated 20 Mtr 919.10
circular unsheathed copper conductor
flexible Cable (For Power supply
Metering Panel to I/c MCCB Unit)
33 CABLE END TERMINATION AND 32 Nos 161.60
SITC of Double compression Ni-Plated
brass cable glands and crimping type
Bimetallic lugs / sockets with necessary
tools and equipments as specified in
specifications and IS. The glands and
lugs / sockets shall be suitable for cable
size and type mentioned below & as per
specifications.
1) Earthing the glands and armouring
with earthing clamp and jumper and also
connecting to common earth bar.
2) The job also includes, if necessary,
supply & fixing of extension busbar of
same material on MCCB or panel board
terminal / connector to connect more
Signature of Contractor Executive Engineer (M&E)
than one no. of parallel cables or to
connect higher size cable to lower size
unit. The job also includes earthing the
glands and armour of the cable with
common earth bar or flexible copper
mesh.(Cable termination qty. shall be as
per site requirement)
3.5C x 16 sq. mm. A2XFY(X) Cable
34 Do as Above 3C x 16 sq. mm. A2XFY Cable 32 Nos 158.57
35 Do as Above 4C x 10 sq. mm. A2XFY (X) 32 Nos 129.28
36 Do as Above 4C x 16 sq. mm. A2XFY(X) 32 Nos 163.62
37 Do as Above 4C x 2.5 sq. mm. 20 Nos 93.93
2XWY/2XFY(X) Cable
38 Do as Above 5C x 1.5 sq.mm. 2XWY(X) 10 Nos 128.00
39 Do as Above 12C x 1.5 sq.mm. 2XWY(X) 10 Nos 218.00
40 Do as Above 2C x 2.5 sq. mm. 2XWY(X) 10 Nos 49.00
41 Single core 95 sq. mm. PVC insulated 10 Nos 213.11
circular unsheathed copper conductor
flexible Cable (For Power supply
Metering Panel to I/c MCCB Unit)
42 CABLE TRAY 80 Mtr 391.88
SITC of G.I. (Hot dip galvanised ) Ladder
type medium duty (2mm thick) Cable
Tray with necessary bends, tees,
reducers, covers and clamps for fixing. All
material shall be Hot dip galvanised as
per Specification. And including all
accessories. 300 x 75 mm - Ladder type
43 150 x 50 mm - Ladder type 200 Mtr 339.36
44 Cable Trench, Laying & Installation of 80 Mtr 55.55
Cable: Making cable trench in soft soil of
suitable width of 90cms deep for laying
cable, Sand cushioning and brick
protection on sides and on top all over
the run and back filling the same and
making the surface as normal ground as
per IS & Specification. (For laying of LT
cable in ground)
45 CHEMICAL EARTHING SYSTEM 4 Set 10,593.89
SITC of Maintenance free chemical
earthing (copper) with earthpit of
minimum bore size dia. 225mm Safe
Earthing Electrode consisting Pipe-in-
Pipe Technology as per IS-3043:1987
/Tech spec. made of corrosion free Pipes
having Outer pipe dia of 48 mm having
Signature of Contractor Executive Engineer (M&E)
250 Micron copper plating, Inner
corrosion free Hot dip galvanised (80 to
100 micron) pipe dia of 26 mm with
copper flat strip type connection
terminal 14mm dia with constant ohmic
value surrounded by highly conductive
corrosion resistant chemical compound
with high charge dissipation suitable for
electrical installation & of 3Mtr. length of
Pipe with two nos. 25Kg. bag of Back
filling compound.. (2nos for PLC earthing,
2nos for DG neutral earthing)
NOTE: Earthing Resistance value & date
shall be painted on the chamber cover.
46 SITC of Maintenance free chemical 6 Set 7,095.25
earthing with earthpit of minimum bore
size dia. 225mm Safe Earthing Electrode
consisting Pipe-in-Pipe Technology as per
IS-3043:1987 /Tech spec. made of
corrosion free Hot dip Galvanised (min
150 Microns) Pipes having Outer pipe
dia of 76 mm , Inner corrosion free Hot
dip galvanised (80 to 100 micron) pipe
dia of 26 mm with copper flat strip type
connection terminal 14mm dia with
constant ohmic value surrounded by
highly conductive corrosion resistant
chemical compound with high charge
dissipation suitable for electrical
installation & 3Mtr. length of Pipe with
two nos. 25Kg. bag of Back filling
NOTE: Earthing Resistance value & date
shall be painted on the chamber cover.
47 SITC of pipe type earthing having 150 6 Nos 368.65
cms long and 2.5cms dia. Galvanised iron
pipe with coupling and buch buried in
specially prepared earth pit complete
with necessary 8 SWG earth wire
48 SITC of 50mm(w) x 6mm(T) etc. sizes as 276 Kg 77.77
required, HOT dip galvanized GI Strip
including supply & fixing using GI
spacers, saddles when laid inside the
building and inclusive of excavation &
refilling of earth when laid outside the
building & interconnection with earth pit
& all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m,
49 Supply, laying and erection of 25mm(w) x 60 Kg 77.77
3mm(T) etc. sizes as required, HOT dip
galvanized GI Strip including supply &
fixing using GI spacers, saddles when laid
inside the building and inclusive of
excavation & refilling of earth when laid
Signature of Contractor Executive Engineer (M&E)
outside the building & interconnection
with earth pit & all electro-mechanical
equipments. (25X3 G.I Strip, 0.6 Kg/m,
50 Supply, laying and erection of 40mm(w) x 38 Kg 794.87
6mm(T) etc. sizes Copper Strip including
supply & fixing of bolts, saddles when laid
inside the building and inclusive of
excavation & refilling of earth when laid
outside the building & interconnection
with earth pit & Tr. neutral. (40X6 Cu.
Strip, 1.88 Kg/m, 1.88 x 20mtr.=38Kg.)
Copper Bolt,Nuts ,Washers shall be used
for Connecting Earth electrode to
individual eqp. Bitumen shall be used at
the place of joint/welding.
51 Supply, laying and erection of 25mm(w) x 15 Kg 794.87
3mm(T) etc. sizes Copper Strip including
supply & fixing of bolts, saddles when laid
inside the building and inclusive of
excavation & refilling of earth when laid
outside the building & interconnection
with earth pit & PLC panel. (25 X3 Cu.
Strip, 0.761 Kg/m, 0.761 x
20mtr.=15.22Kg.)
Copper Bolt,Nuts ,Washers shall be used
for Connecting Earth electrode to
individual eqp. Bitumen shall be used at
the place of joint/welding. (PLC Panel
52 SITC of HOT Dip Galvanized iron strip 10 Kg 77.77
wire 8 SWG (For LDB, LCS, etc.)
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x
53 INTERNAL WIRING 150 Mtr 82.82
SITC of Mains & outlet points wiring with
1.1 kV grade FRLS PVC insulated ISI
marked flexible stranded copper
conductor wires with medium class min.
25mm. dia. Electrical grade PVC pipe and
accessories to be erected concealed in /
to be run on surface / wall / ceiling with
following sizes as mentioned below. The
unit rate wirings shall be with connector,
PVC junction box, wires, holder, ceiling
rose, angle holder, switch, sockets, switch
board, brass chromium / cadmium plated
machine screws, phase and neutral wires,
green Earth continuity wires etc. as
required to complete wiring from LDB
panel to the final outlet termination
points. The wiring shall be as per
IS:732, IS:4648 and as per tender
specification / IS.
(a) SITC of Mains wiring with 3 wire
Signature of Contractor Executive Engineer (M&E)
54 SITC of Mains wiring with 3 wire 2.5 100 Mtr 102.01
sq.mm as per tender specification & IS.
55 SITC of Mains wiring with 4 wire 1.5 100 Mtr 90.90
sq.mm as per tender specification & IS.
56 SITC of Mains wiring with 4 wire 2.5 80 Mtr 126.25
sq.mm as per tender specification & IS.
57 SITC of Point wiring for Light / fan / Bell 37 Nos 354.51
/ Primary Point with 2nos. 1.5 sq. mm &
earth wire of 1.5 sq. mm (green) both are
of ISI marked 1.1 kv grade FRLS PVC
insulated multistrand copper wires , pipe
to be erected concealed in flushed on
wall / ceiling, complete with 6A Tissino
Type ISI marked flush type switch / bell
push & accessories erected on metal /
PVC Box covered with 3 mm thick PC
(Polycarbonate) / Acrylic sheet with
necessary lamp holder / ceiling Rose / H.
D. connector as directed with medium
class Rigid PVC pipe & accessories.
58 SITC of 6A independent Plug with 2nos. 6 Nos 313.10
1.5 sq.mm Cu. Mains size wiring &
earthwire of 1.5 sq.mm (green) both are
of ISI marked 1.1 KV grade FRLS PVC
insulated multistrand copper wires with
medium class Rigid PVC pipe and
accessories to be erected on wall / ceiling,
complete with ISI marked 3 / 5 Pin socket
and tissino type switch erected with earth
continuity connection erected on Metal /
PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
59 SITC of 6/16A independent Plug with 6 Nos 607.01
2nos. 4 sq.mm Cu. Mains size wiring &
earthwire of 2.5 sq.mm (green) both are
of ISI marked 1.1 KV grade FRLS PVC
insulated multistrand copper wires with
medium class Rigid PVC pipe and
accessories to be erected on wall / ceiling,
complete with ISI marked 3 / 5 Pin socket
and tissino type switch erected with earth
continuity connection erected on Metal /
PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
60 SITC of Single Phase 20A 3 Pin Metal clad 4 Nos 820.00
Industrial Type Socket with plug top and
20A SPMCB, suitable for flush mounting,
in 16 SWG MS box of suitable size and
covered with 3 mm thick electrical grade
hylam sheet or equivalent ISI marked
Electrical grade Bakelite sheet and
earthing with 2.5 sq.mm insulated copper
Signature of Contractor Executive Engineer (M&E)
wire run inside the conduit including
interconnections etc. complete as
61 LED LIGHT FIXTURES & LIGHTING: 25 Nos 589.84
SITC of Indoor wall mounting 20Watt or
up to 25% higher wattage LED 4 feet
Tube Light indoor fittings with LEDs of
wattage 0.2 Watt to 0.5 Watt assembled
on single MCPCB, with housing used as a
heat sink shall be made of thick sheet
Steel conforming to IS: 513/CRCA
polyester powder coated and high U.V. &
corrosion resistance with diffuser and/or
Polycarbonate optics with company
120 to 300 V,Power Factor more than 0.9,
CCT 4000 K to 6500K, Uniformity ratio
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80
Tube Light with integral / non-integral
driver, Surge-4KV,IP-20, 4 feet, Cat-III
62 3 watts LED Lamps integral type,cool 4 Nos 273.71
white with PC diffuser suitable for B22
63 SITC of 380mm sweep 1400 R.P.M 2 Nos 3,082.52
exhaust fan, capacitor type, having double
ball bearing, M.S.blades, mounting frame,
forearms, suitable to operate on 230V,50
HZ AC supply conforming to IS: 2312.Fan
shall be painted with epoxy grey colour
controlled by one 6 A flush type switch on
board and 6A plug point near Ex. fan.
64 SITC of 40W LED Surface / Wall mounted 3 Nos 5,194.43
LED Flood Light fittings with High power
White LEDs wattage of 1Watt and above
assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free
High pressure die cast aluminum housing
with smooth finish powder coated and
heat sink extruded aluminium with
diffuser and Polycarbonate optics/ lenses
with company mark/name engraved or
120 to 300 V,Power Factor more than
Uniformity ratio >0.45, Luminaries
efficacy> 85 lumens/watt . LED driver
efficiency > 85 %.
( Each fittings required LM-79 & LM-80
(IP-65), Surge -4KV Cat-III
Signature of Contractor Executive Engineer (M&E)
For Indoor use: (3 nos. at Pump House)
65 SITC of 'B' class galvanised iron pipe 32 11 Nos 558.53
mm outside dia 45 cms long duly welded
on 20 cms x 20 cms x 3 mm thick M.S.
base plate, erected on wall or corner for
mounting luminaries with necessary
hardware materials duly painted for wall
mounting indoor flood light fixtures on
Wall of Buildings & post top lantern.
66 EXTERNAL LIGHTING (Flood LIGHT): 4 Nos 6,088.28
SITC of 70W LED Wall mounted LED
Flood Light fittings with High power
White LEDs wattage of 1Watt and above
assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free
High pressure die cast aluminum housing
with smooth finish powder coated and
heat sink extruded aluminium with
diffuser and Polycarbonate optics/ lenses
with company mark/name engraved or
120 to 300 V,Power Factor more than
Uniformity ratio >0.45, Luminaries
efficacy> 85 lumens/watt . LED driver
efficiency > 85 %.
( Each fittings required LM-79 & LM-80
(IP-65), Surge -4KV Cat-III
For Outdoor use:
67 SITC of 40watt, Cat-III Post Top Lantern 2 Nos 4,819.72
LED fitting comprises of 650 MM TOP
Diameter, 120 degree beam angle with
Supporting Ribs and with 0.5mt. G.I.
fitting pipe (for Gate light)
68 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos 10,178.78
SITC of Street Light Pole, steel tubular
swaged type, 7.5 meter long with single
arm & M.S.base plate with pipe cap and
over hung 1.5 m long having dia to suit
the socket of 240V LED street light
fixtures. Street light pole unit rate shall be
with (i) IP 65 SMC box of size 20 x 15 x
15 cms. with MCB & terminal strip inside
the box with hinged/sliding door (ii)
50mm dia, B class GI pipe bracket
min.1.5mtr long for Incoming & outgoing
cable (iii)MS Cable Clamp of 25 x 3mm
(iv)SITC of 1.5 Mtr.single Arm bracket of
medium duty MS pipe of 4.2 cms. Out
side dia complete with suitable sleeve
tubing 45 cms. long of required size of
pole top etc. and having spread of 1.5.mtr.
Signature of Contractor Executive Engineer (M&E)
length with 110 deg.(v) Complete painted
with one coat of Red oxide / PU base
primer and two coats of Aluminium / PU
paint for Pole,Arm, pipe etc.
69 SITC of 70 W LED Street light fittings with 4 Nos 5,976.17
High power White LEDs wattage of 1Watt
and above assembled on single MCPCB,
efficiency more than 130 lm/w and
corrosion free High pressure die cast
aluminum housing with smooth finish
powder coated and heat sink extruded
aluminium with diffuser and
Polycarbonate optics/ lenses with
company mark/name engraved or
120 to 300 V,Power Factor more than
Uniformity ratio >0.45, Luminaries
efficacy> 85 lumens/watt . LED driver
efficiency > 85 %.
( Each fittings required LM-79 & LM-80
Street Light (IP-65), Surge -4KV, 70 watt
70 SITC of M-20 / 1:2:4 cement concrete 4 Nos 1,292.80
foundation for Street light pole & 70 %
PCC from bottom including excavation for
the pole of size 60 x 60 x 120 cms. Deep in
below ground level with plinth of 45 cms
x 45 cms(or 45 cms dia x 45 cms) high
upper ground level with necessary curing
and finishing in approved manner.
71 DIESEL GENERATOR SET 2 Each 7,20,245.14
SITC of 75 kVA or higher standard rating,
415 V,50 Hz, 3 Phase, 4 wire Diesel
Generating Set. Diesel engine shall be
complete with necessary controls and
safety devices confirming to relevent
ISS/BSS with latest amendements, DG
controller unit with kWH meter. Diesel
Engine shall be suitable for continuous
operation of generator set duty inclusive
of fly wheel, air cleaner, radiator. fan with
guard, fuel pump, fuel filter, Electronic
governor, auto main fail starting,
electrical starting system with starter,
12V battery, voltage regulator,
instrument panel, Exhaust silencer,
protections against low lubrication oil
pressure,high water temperature.
Alternator shall be 415V, 3 phase, 50 Hz,
4 wire, 0.8 power factor, self excited,self
regulated,brushless type,drip proof
confirming to IS:4722 with latest
Signature of Contractor Executive Engineer (M&E)
The engine and alternator shall be
coupled over a sturdy common base
frame. Floor mounted,dust & vermin
proof, indoor type control panel shall be
consisting of Thermal magnetic MCCB of
suitable normal current rating,with
combined overload and earth fault
protective relays/release, voltmetre with
selector switch,ammeter of suitable range
with selector switch, frequency meter,
Energy meter, CTs, indicating lamps with
fuse and switch control, complete & with
necessary interconnections,fuses,lables
and other accessories.Day fuel tank with
necessary fuel hoses to the engine,all as
per detailed specification and complete in
all respect as required.
72 SITC of Acoustic enclosure suitable for 75 2 Each 1,92,414.09
kVA DG set, made out of 18 SWG, CRCA
Sheet, Sound absorbing matewrial
Rockwood of 64 density & 100 mm thick
conforming ti IS:8183. The resin boinded
Rockwood covered from inside level not
more than 75 dB at a distance of 1 mtr, as
PVCT / CPCB norms, on provided
73 Providing & laying of 50 MM Nominal OD 50 Mtr 62.62
Doubled Walled Corrugated Pipes (DWC)
of polyethylene (conforming to IS 14930 -
II) with necessary connecting accessories
like coupler, Tee, L - Bow, etc. of same
material at required depth (90 cms)
including excavation for laying of cable
below ground/ road surface for enclosing
cable and back filling the same to make
ground as per original & as per
instruction of Engineer Incharge -
74 Lightning Protection system for highest 1 Nos 60,760.00
building at plant area by air terminal
woith rod and GI strip conductor test link
to earth electrode as per requirement
75 SAFETY ACCESSORIES 2 Nos 8,671.86
SITC of following safety accessories
complete with necessary fixing brackets,
other accessories and tools etc. as
required to complete the job. Supply &
Erecting carbon dioxide (CO2) fire
extinguisher of 6.5kg capacity with
necessary clamps made from 50 x 6 mm
M.S. Flat with nut & bolts grouted in wall
(For 1 no. for LT Room, 1 no for DG set)
Signature of Contractor Executive Engineer (M&E)
76 Supplying & erecting D.C.P. type fire 2 Nos. 2,226.04
extinguisher for following capacity
cartridge type with gun metal cap
gram CO2 gas cartridge, powder and
brackets confirming to IS 2171 1985 and
complete erected with necessary clamps
made from 50 x 6 mm MS flat with nuts
and bolts grouted in wall complete, 10 kg
77 Supplying of standard first AID box with 1 Nos 299.97
antiseptic cream, medicine for use on
wounds due burn, crepe bandage, guage
bandage, medicated ready to use bandage
(Band-aid) adhesive tape for medicinal
user, scissors, antiseptic solution (Savlon
or similar) etc. (All above contents shall
be of standard makes)
78 Supply & fixing of printed instruction 1 Nos 130.29
(First Aid) Chart both in English and
Gujarati and duly framed with front
glasses, for treatment of person suffering
from electric shock.
79 Supplying & fixing of floor mounting 1 Nos 1,798.81
stand for keeping four nos. of FIRE
buckets comprising 1500 mm in length,
900 mm height frame made out of 30mm
X30 mm X 4 mm angle iron with cross
supports for legs, welded with 4 hooks
and duly painted with one coat of red
lead and two coats of approved
enamelled silver paint. ( 1 set for Dg set)
80 Supply and fixing of 20 W fluorescent 17 Nos 2,540.00
lamp operated emergency light with
maintenance free battery for 3 hours
operation during mains power failure.
81 Supply and laying of Synthetic Insulating 4 Sq.mtr. 1,027.17
Mat of Class - A of min. thickness 2mm as
per IS:15652 and with good electrical
insulation property for 1.1KV/3.3KV as
per site requirement. (For LT Panel)
82 Providing pair of rubber hand gloves ISI 1 Nos 214.12
make suitable for working on 22 KV
83 LIASONING CHARGES FOR OBTAINING 1 Nos 10,000.00
Power Liasoning Charges for obtaining
N.O.C from Electrical Inspector /
Statutory authority for Power / Ele.
Installation. (Fees shall be paid by
tenderer for obtaining N.O.C. from
Electrical Inspector / Statutory authority
on behalf of client and shall be
reimbursed on submission of original
receipt to Client).
Liasoning Charges shall include preparing
Signature of Contractor Executive Engineer (M&E)
required attested documents & drawing
for obtaining NOC on behalf of client
(Applicable Fees / deposits shall be
reimbursed by Client).
84 INSTRUMENTATION WORK 5 Nos. 1,426.12
PRESSURE MEASURING SYSTEM:
SITC of 0- 10 kg / cm2 - 150 mm dia, size
Pressure Gauge Design, Supply,
Installation, Testing, Commissioning of
Bourdon Type Pressure Gauge, ±1%
accuracy, Direct bottom 1/2" NPT (M)
process connection, IP 67, Glycerine
filled, SS304 Case with Bayonet Type
Bezel, SS316 L Bourdon Tube, SS
Movement material, Aluminium dial with
black graduation on white background,
Micro Zero adjustable pointer, neoprene
gasket, Blow out disc, shatter proof glass,
SS tag plate etc as per IS
85 Supply, installation, testing and 5 Nos. 29,438.47
commissioning of Pressure Transmitter
with local display along with two valve
manifold, required fittings, tubing (all
valves, fittings, tubings, etc. shall be in SS
316 only), all accessories, hardware, etc.
complete in all respects as per
specifications and having following
measurement ranges: Range : 0 -
4Kg/cm2 (at each pump delivery side and
86 LEVEL MEASURING SYSTEM FOR SUMP 5 Nos. 60,030.36
Supply, installation, testing and
commissioning of Ultrasonic type Level
Transmitter with remote type
transmitter with 20 meter cable between
Sensor and Transmitter along with all
required accessories, Weather proof
enclosure for transmitter for outdoor
application, mounting stand , etc.
complete in all respects as per
specification and having following
measurement ranges for liquid (Effluent)
Meas. Range: upto 10 m
87 Supply, installation, testing and 2 Nos 12,930.02
commissioning of Displacer type Level
Switch SS Float for dry run protection of
pump through relay multiplication in
PLC), etc., complete in all respects and as
per specification.
Meas. Range: upto 10 m
88 ELECTRO MAGNETIC FLOWMETER 3 Nos 1,49,342.84
Supply, installation, testing and
Signature of Contractor Executive Engineer (M&E)
commissioning of Full Bore
Electromagnetic flow meter comprising
of IP-68 Sensor with PTFE liner
Hastelloy-C Electrode, IP-66 transmitter
with 20 m cable between sensor and
transmitter along with all mounting
accessories, Weather proof enclosure for
transmitter, hardware, mounting stand,
etc. as per specification and to complete
the work in all respect as per site
condition necessary connection with
pipe and shall have following size. PN 1.6.
Meter Size : 300 mm NB
89 PLC BASED CONTROL PANEL 1 Nos 3,50,000.00
Supply, Installation, Testing &
Commissioning of PLC Based Instrument
control Panel with 10" color touch screen
HMI, 4G GPRS modem with (ethernet port
+ SIM slot) with SIM Card for Remote
data transmission to TEPS for monitoring
and control the EPS from TEPS,
Communication port for MFM , PLC with
Conformal Coating with ISA-S71.04
severity level G1;G2 as a min., Power
Surge Protection device in Incoming 230V
AC Power supply to UPS, 1 no. Spilt type
Air Conditioner (2 Ton 5 start rating )
Instrument Control Panel '(PLC Enclosure
/ Panel ) with necessary PLC based logic
and wiring , Min. 1 kVA online UPS (with
60 min backup alongwith filter for
harmonic, suitable rating SMF inbuilt
batteries alongwith battery charger and
all other accessories as per standard), etc.
complete in all respects and as per specs
with PLC having minimum I/O count of
70DI /30DO / 12AI /4 AO. These are the
minimum IO requirement if any other
IO,s required to complete the work
contractor shall be provide the same
without any extra cost.
90 INSTRUMENT CABLE & ACCESSORIES 80 Mtr 144.00
'Supply, Laying, Installation, Connection,
Termination, Testing & Commissioning of
Instrument Cables as per specs.The unit
rate shall include
a)Supply, loading & unloading of the
cable at site from store.
b)Shifitng of cable from site store to place
of installation.
c)Fixing of cable clamps, brackets,
supports, route markers etc. where ever
required to fix the cables safely.
d)Excavation, back filling and levelling of
Signature of Contractor Executive Engineer (M&E)
ground alongwith laying of fine sand,
protection bricks and other necessary
civil material for laying cables outside the
f)Testing and submission of sketches &
reports of all the cables laid.
91 SIGNAL CABLE 80 Mtr 118.00
92 CONTROL CABLE 80 Mtr 270.00
93 INSTRUMENT CABLE TRAY 80 Mtr 832.00
Supply and installation / erection of
Perforated type cable tray of galvanized
mild steel sheets of 2 mm thickness with
required, hardware, fitting and support
structral asccessories . All material shall
be Hot dip galvanised as per IS 2629 and
tray hardware shall be in GI. Support
structutre shall be of structral steel for
mounting the cable tray on wall / cable
trench or as per site condition,
600 X 25 mm - Perforated type
94 200 X 25 mm - Perforated type 80 Mtr 322.00
95 50 X 25 mm - Perforated type 80 Mtr 107.00
96 CABLE END TERMINATION AND 20 Nos 136.00
'Supply, fixing, connection, testing and
commissioning of double compression
brass cable glands and crimping type
Bimetalic lugs / sockets with necessary
tools and equipments as specified in
specifications and IS complete in all
respects. The glands and lugs / sockets
shall be suitable for cable size and type
mentioned above. The job also includes
earthing the glands and armour of the
cable with common earth bar or flexible
copper mesh as applicable.
97 SIGNAL CABLE 24 Nos 136.00
98 CONTROL CABLE 38 Nos 296.00
99 IoT Based Dual Protocol (GSM + LAN) 1 Nos 19,500.00
Gateway for Centralise Monitoring and
Data Connectivity to GPCB and CPCB.
Cloud Software Charges.
Signature of Contractor Executive Engineer (M&E)
100 Cloud Software Platform and IIoT Sensors 1 Nos 45,50,000.00
for Predictive Maintainanace and AI
Powered Electrical Signature Analysis for
Electrical Pumps.
Total Amount Without GST in Rs.
Total Amount Without GST in Rs.
*The rate shall be Exclusive of all taxes (Excluding GST)
I/We agree to carry out above work at __________ % above the estimated Rate put to tender
Percentage in words ( _______________________________)
I/We agree to carry out above work at __________ % below the estimated Rate put to tender
Percentage in words ( _______________________________)
Estimated Amount put to Estimated Amount put to
Tender Rs. 1,45,30,488.00 Tender Rs.
Add % Above Rs.____________ . Deduct % Below Rs.____________
Net Amount Rs.____________(In figures). Net Amount Rs.____________(In figures)
I/we have read the condition mentioned in this tender and agree to abide by the sam
IMPORTANT NOTE:
The rate of each items should be offered inclusive of Excise duty, packing, forwarding, insurance,
loading, unloading, shifting & transportation at store/site except GST of work of the estates under
GIDC, Bharuch GST will paid extra Please note that the agency, in whose favour the tender is
finalized by the competent authority, should have to submit the document like insurance of the
staff engaged RPFC No., Labour license etc.
1. I / we agree to supply the above materials at the rate mentioned above.
2. I / we have read the conditions mentioned in this tender & agree to abide by the same.
3. GIDC will not issue any tax exemption form i.e. ‘P’, ‘C’ or ‘D’. The tenderer may quote
rates accordingly.
4. The agency in whose favour tender is finalized has to enter into B1 agreement and
conditions and clauses of the agreement shall be binding to the agency. If agency desire
to study, the same is available from Engineer in Charge during working days and office
5. The tendered has to inspect the site and found out the quantum of repairs/overhauling
service work involved before quoting the rates.
6. Labour work required for handling, lifting lowering, shifting, loading, unloading,
transportation etc. of any pumps & allied equipments with tools & tackles shall be
arranged by the tenderer.
Signature of Contractor Executive Engineer (M&E)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Bank Guarantee.pdf
Modified schedule.pdf
Volume - I (PQ).pdf
Volume - II (Technical bid).pdf
Price bid.pdf
B1 Agreement - Part 1.pdf
B1 Agreement - Part 2.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .