Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.3 LAccepted-AOC | ₹12.3 L Quoted ₹13.9 L | L1 | Accepted-AOC ACEEPTED BEING LOWEST TENDER |
| 2 | L2₹14.2 L+₹30,305 (2.18%)Rejected-AOC SHOP NO 5 OPP SHANI MANDIR PROFESSOR COLONY DISTT YAMUNA NAGAR HARYANA 135001 | YAMUNANAGAR | HARYANA | 135001 | ₹14.2 L+₹30,305 (2.18%) | L2 | Rejected-AOC REJECTED BEING NOT LOWEST TENDER |
Tender Value
₹17 L
EMD Value
₹34,000
Closing Date
15 Aug 2022, 6:00 pmClosed
GE I RND DEHRADUN
GE I RND DEHRADUN DEAL RESIDENTIAL COMPLEX RAIPUR ROAD DEHRADUN 248008
REPAIR MAINT OF 11 KV FEEDER AND SWITCH GEARS, VCB RELAYS, HT/ LT UG CABLE, OH LINES, LT PANELS, FEEDER PILLAR BOX TRANSFORMERS AND CERTAIN ALLIED WORKS AT CQA (I) UNDER GE (I) RND DEHRADUN
2022_MES_539069_1
GE(I)RND/9149/E8/22-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DEAL DEHRADUN
Class E Category b (ii) FOR UNENLISTED CONTRACTOR (i) Enlistment criteria may be seen in Para 1.4 and 1.5 of section of Part I of MES Manual on contracts-2020 as available in all MES formations (ii) Copy of police verification /passport.
6 documents required · 6 mandatory
₹500
Yes
GE I R N D DEHRADUN
₹34,000
Yes
9 Sept 2022
18 Jul 2022
17 Aug 2022
18 Jul 2022
15 Aug 2022
1 Aug 2022
18 Jul 2022 - 1 Aug 2022
Amount
Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. including removing cable protection covers/ bricks complete all as specified and directed. Notes : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection. (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations
M&L for Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed.
M&L for Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed.
Material & labour for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed (NOTE : Thickness after punning shall be measured for payment)
Supplying & Laying un-reinforced pre cast flat concrete cable protection cover of class HV, type I, size 300mm x 180mm x 40mm, factory made, complete all as specified and directed .
Fixing / laying only old un-reinforced pre cast flat concrete cable protection cover of any description complete all as specified and directed . Note :- Old concrete cable protection cover retrived under item No.01 herein above shall be reused.
Supplying & Laying un-reinforced pre cast flat concrete cable protection cover of class LV type I, size 250 mm x 150 mm x 40mm, factory made, complete all as specified and directed .
Fixing / laying only old bricks of any description as obtained from dismantling of the cable complete all as specified and directed
Supplying, Laying, testing and commissioning in replacement of UNSV XLPE insulated, PVC sheathed (heavy duty) armoured shielded cable with aluminium conductor for working voltage upto 11KV (Earthed) ,conforming to IS 7098 Part-II amended upto date complete, having cross sectional area under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe including making necessary connection with VCB/OCB/ 4 pole/2 pole structure etc. complete all as specified and directed. Make :Havells/CCI/ICL/GLOSTER/Incab/Nicco/Polycab/Plaza) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and PCC protection shall be measured and paid separately )
95 Sqmm 3core
120 Sqmm 3core
Re-laying HT cable Obtained form Item No 1 ( Any size)
Supplying, Laying, testing and commissioning in replacement of UNSV XLPE insulated,IS 7098 (Part-I)-1988 marked screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor 1100V grade cross section area of the under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe including making necessary connection, with busbar/MCCB/DB's & testing complete, all as specified and directed by Engineer-in-Charge. Make:Havells/CCI/ICL/GLOSTER/Incab/Nicco/Polycab/Plaza) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and brick protection shall be measured and paid separately )
25 Sqmm 3½ core.
35 Sqmm 3½ core
50 Sqmm 3½ core
70 Sqmm 3½ core
95 Sqmm 3½ core
120 Sqmm 3½ core
150 Sqmm 3½ core
185 Sqmm 3½ core
240 Sqmm 3½ core
Re-laying LT cable Obtained form Item No 14( Any size)
Supplying, laying & jointing in replacement of UNSV GI water tubing, under mentioned bore, light grade as in sleeving etc laid in trenches / ducts etc. complete all as specified and directed. (MAKE : TATA/JINDAL/TT SWASTIK)
100 mm bore
80 mm bore
50 mm bore
Material & labourfor cutting chases in hard standing road/path/drain etc for passing cables/pipes etc. size of cutting 100mm wide and 200mm deep and removing the excavated materials and disposal at 50 metre distance and making good the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for indoor termination, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sq mm complete all as specified and ditected.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for outdoor termination, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sq mm complete all as specified and ditected.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for indoor termination, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sq mm complete all as specified and ditected.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for outdoor termination, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sq mm complete all as specified and ditected.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for straight through, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sq mm complete all as specified and ditected.
Disconnecting and taking out old Unserviceable HT joint complete and Supply , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for straight through, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sq mm complete all as specified and ditected.
Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables all as specified and directed by the Engineer-in-Charge. (MAKE : M.SEAL/DENSON/ MAHINDRA CHEMICALS/3M) :-
50 Sqmm 3½ core
70 Sqmm 3½ core
95 Sqmm 3½ core
120 Sqmm to 150 Sqmm 3½ core
185 Sqmm 3½ core
Dismantling & taking out unserviceable steel & iron items from poles i.e cross arms, bracing, supports, clamps and back plates etc. including nuts & bolts complete and Supply & fixing cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts & bolts , washers , welding bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
M&L in replacement of UNSV stay assembly for 11 KV comprising of 20mm dia, 1.80 mtr long galvanized stay rod , having stay bows of galvanished mild steel 400 mm long made out of 14 mm dia galvanized bars, 7 / 4.00 mm GI stay wire stranded and 300mm X 300mm X 6mm thick MS stay plate, complete all as shown on electrical plate No 1 of SSR, Part-I with and including all necessary fittings/accessories like loop type insulator with 90 mm height 140 mm dia clearance hole 25.5 mm , shackle & stay clamps, necessary excavation and earth work in any type of soil and PCC works in (1:3:6) type C-2 (using 40mm graded stone aggregate) and disposal of surplus soil to a distance not exc 50 m complete all as specified and directed . (Excavation and concrete measured separately)
M&L in replacement of UNSV stay assembly 300x300x3mm complete with accessories such as GI stay bow 20mm dia 400mm long, GI stay plate 300x300x3mm stay road 16mm dia 1800 mm long GI nuts, bolts loop insulator MS clamps,galvanized iron stranded stay wire of size 7/3.15 mm dia including necessary excavation PCC work ( PCC work MS clamp to pole excavation and earth work will be measured & paid separately) as shown in electrical plate No 1 complete all as specified and as directed.
Material,labour and erecting in replacment of UNSV Steel tubular swaged poles complete with cast iron base plate, final, taper plug bolt, nuts & screws of type 410 SP-55 (11 M long) complete, all as specified and direction by Engineer-in-charge. Note :- Earthwork, cement concrete in foundation, coping, cross arms ACSR conductors will be measured and paid separately under relevant items.
Material,labour and erecting in replacment of UNSV Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) complete,all as specified and direction by Engineer-in-charge Note :- Earthwork, cement concrete in foundation, coping, cross arms ACSR conductors will be measured and paid separately under relevant items
Supply , Install and testing in replacement of unserviceable insulators pin type porcelain, vitreous, white, brown or green insulators,for working pressure 11000 volts of size 150mm height and 150 mm dia including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, etc for HT lines fixed on poles complete all as specified and directed.
Supply , Install and testing in replacement of unserviceable disc type porcelain, vitreous, white, brown or green insulators,for working pressure 11000 volts of size 145mm height and 255 mm dia including two in series assembly for tension with tension clamps for conductors, etc for HT lines fixed on poles complete all as specified and directed.
Supply , Install and testing in replacement of unserviceable HT 11kV vertical swing triple pole gang operated air break switch (GOD) consisting of twelve insulator (3 insulators in each phase and one each for DO fuse). Mounted over the MS channel frame, operating mechanism, operating handle GI medium grade 25 mm bore, 5 mtr long with locking arrangement system connected with operating handle and 7 leaver lock of Godrej, moving and fixed jaws, copper jumpher strip etc suitable for 11000 volt 200 Amp current rating all as specified and directed at site.
Dismantling and taking down existing unserviceable lightning arrestor of any capacity and any description and Supply, fixing, commissioning & testing of distribution class lighting arrestor of rating 12 KV capacity and 10 KA NDC(Peak) confirming to to IEC-99.4 including brackets, clamps, bolts, nuts and washers complete all as specified and directed.
Supplying,Straightening and Stringing in replacement of UNSV aluminum conductor steel reinforced (ACSR) conductor off size including jointing the conductor with new conductor on existing HT/LT pole and binding to insulator with the new aluminium wire binding wire 2 mm dia making and connecting jumper connections etc including connecting commissioning and testing complete, all as specified and as directed.
Supplying, Straightening and Stringing in replacement of UNSV Guard/ cradles hexagonal/ rectangular, fabricated in replacement of UNSV galvanized steel wire 3.15 or 4mm dia . all as specified and as directed by Engr-in-Charge.
Restringing of HT existing over head line of ACSR conductor after disconnecting from the insulators & jumpers to the required tension & sag & binding up & connecting to insulators & jumpers properly testing complete, including chopping off tree branches (coming in the way line) all as directed.
Description all as per item No 31 above here-in before, but for GI wire complete, all as specified.
Notes:- For item No 30 & 31 (i) The quoted rate is inclusive of the cost of Setting /adjusting of cradles in positions. Adjusting & tighting of stay assembly where ever required. (ii) The quoted rate is inclusive of the cost of old serviceable jumper of ACSR conductor shall be reused and fixed. (iii) The quoted rate is inclusive of the cost of Cutting/trimming of tree branches along with the exisitng HT/LT overhead line 2 mtr clearence from all sides of ACSR conductor including removal from the site. (iv) Single conductor shall be considered for measurement in RM.
M&L in replecement of UNSV jumper with weasel conductor suitable for HT/LT, 11000 /1100 volts grade required at site with suitable size of luge on both end including proper crimpinf etc.complete, all as specified and directed.
Supply & fixing pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100mm height and 65mm dia suitable for working pressure upto and including 1100 volts grade for LT lines fixed on poles complete, all as specified and directed.
Supply and fixing shackle type porcelain vitreous, white, brown or green insulator for working pressure 1100V of 115mm dia and 100mm high including galvanized mild steel strip 31 x 3mm, insulator bolts 14mm dia washer and nut for LT lines fixed on poles complete, all as specified and directed.
M&L in replecement of UNSV the following LT PVC separator complete all as specified and as directed.
4 wire complete
2 wire complete.
S& F in replacement of UNSV lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop retuning, filling & making cable lead by providing Aluminium lugs lead including crimping with crimping tools in the existing LT cable including necessary connection etc,complete, all as specified and directed.
Up to 50 Sq mm
From 70 Sq mm to 120 Sq mm
From 150 to 185 Sq mm
From 240 to 300 Sq mm
Material and labour for cleaning and preparation of all existing steel surfaces of pole structure of straight steel tubular poles 11/ 09 mtrs long for painting including mild steel cross arms, clamps and anti clibing device,protection pipe etc and applying one coat of aluminium paint all round the exposed steel surfaces of existing steel tubular poles structure of any description and in any position above the height of 1.50 mtr from the plinth of the pole and applying one coat of synthetic enameled paint of different colours in strips of 150mm width upto the height 1.5 mtr from the plinth of poles including writing pole No and other sign works with white paint over black painted base in the pattern and style as approved. complete all as specified & directed. Note : Size of black painted base for numbering shall be 100mmx25mm and the size of numbers shall be not exceeding 10cm height.
M & L for PCC 1:2:4 type B2 with 40mm grade stone aggregate as in foundation for outstanding around pole near feeder pillar/LT panel foundation of stays, including form work, fair finishing to exposed surface complete all as specified and as directed.
M&L for PCC 1:4:8 type D2 with 40 mm graded stone aggregate as in foundation for hard standing around pole & near feeder pillar/LT panel foundation of stays, including form work, fair finishing to exposed surface complete all as specified and as directed.
M&L for PCC 1:3:6 type C2 with 40 mm grade stone aggregate for coping of poles,stays incl. form work complete all as specified and as directed .
M&L for Brickwork with subclass ‘B’ bricks, straight or curved on plan to any radius in half brick thick walls built in cement mortar 1:4 with and including demolition of old brick work complete all as specified and directed.
M&L for Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 complete all as specified and directed.
M & L for spreading crushed/hand broken 20/ 40 mm graded sand stone aggregate around and under 4 pole/ 2 pole structure/11 KV Yard uniformally complete, all as specified and directed. Note :- (i) Excavation of earth work will be measured & paid separately under relevant items. (ii) Spread thickness of aggregates shall be measured and cubical content shall be worked out with deduction of 50% for voids for arriving at net qty.
M&L in replacement of UNSV danger notice board and Supply and fixing new danger notice board size 250mmx200 mm made out of 1.6 mm thick mild steel sheet, suitable for 11KV HT line and applying two coats of synthetic enameled paint (red colour) over a coat of red oxide primer including writing letters,figures and conventional skull and bones of suitable size on board in standard pattern as per IS fixed with and including MS clamps made out of mild steel flat iron,bolts ,nuts and washers etc complete, all as specified and directed.
Dismantling and taking out old PVC flooring of any description and removing old unserviceable floowing of any type and M&L for supplying and fixing nominal 2.5 mm (+ 10% tolerance) thick electric insulated P.V.C. synthetic sheet viz “insulatica 2000” conforming to IS-15652 of 2006 alongwith suitable adhesive/chemibound, having leakage current tested to meet requirement of IS-8437, IS-3043, break-down strength 40 KV having no adverse impact of mineral oil, high insulation resistance including material for water proofing of floor and sealing of all joints as required, suitable for floor covering around electrical apparatus for voltage not exceeding 11 KV (AC) to ground complete all as specified and directed .
M&L for glossy finish rubber moulded chequered cement concrete tile 20 cm x 20 cm x 25 mm thick set jointed and pointed in neat cement slurry in floor with grey cement and pigment to match including screed bed or bedding layer of cement mortar 1:6, 15mm thick for laying floor finished including dismantling floor , hearth or wall tiling including cement mortar bedding (but not backing), removing debris and rubbish off the premises .complete all as specified and directed.
M&L prepration of new plaster surfaces of wall and applying three coat of wash on walll complete all as specified and directed.
M&L for prepration of old steel surfaces of any description over 10 CM width and girth applying one coat of synthetic enamle paint complete all as specified and directed.
Disconnecting and taking out existing HT 11KV VCB/OCB from housing and cleaning, rubbing and overhauling the mechanical parts incl Greasing oiling replacement of UNSV trip coil, breaker charging motor, gear panion, roller switch, Big gear etc and re-assembling the same after replacement as required and made the VCB serviceable including making all electrical connection and testing & calibration (IR Test, Continuity test, Tripping test of earth fault and Over current of panel )alongwith control panel and control wiring, protection system and relays by primary & secondary injection system bank/battery chargers/DC system complete complete all as specified and directed. Note :- (i): Any parts required for replacement to make the breaker serviceable will be measured and paid separately under appropriate item of Sch ‘A’ as supply only but fixing charges of the parts replaced/repaired is deemed to be included in these item (ii) All other accessories excluding sch item No: to be supplied and fixed by the contractor at his own arrangement. (iii) calibration & testing will be carried out by machine which will be arranged by the contractor under his own arrangement.
Supply only the following items / spare parts suitable for 11 KV VCB, 200/800 Amps capacity of any make, dismantled/fixed under Sch ‘A’ item No. 03 here in above complete all as specified and directed .
Vacuum Interrupter
Bushing (Female)
flexible connectors
Closing coil assembly 30/24 volts DC.
Tripping coil assembly 30/24 volts DC.
Heating element with thermostat switch 150 Watt compact type
Motor cut off limit switch.
Spring charge motor, single phase suitable for spring charge motorised mechanism
Auxilary switch (6 NO + 6 NC ).
11 KV bus insulator of suitable for 11 KV VCB/OCB Panel complete
Supply, install, testing and commissioning in replacemen of UNSV tripping coil DC 30 V for 11 KV VCB complete all as specified and directed.
Supply, install, testing and commissioning in replacemen of UNSV closing coil, DC 30V for 11 KV VCB complete all as specified and directed.
Supply, install, testing and commissioning in replacemen of UNSV Trip push button for 11 KV 400 Amps OCB complete, all as specified and directed
Supply, install, testing and commissioning in replacemen of UNSV Voltmeter square type Digital of size 144Sqmm of capacity 0 to 15 KV PT Ratio 11KV/110Volt for panel complete all as specified and directed.
Supply, install, testing and commissioning in replacemen of UNSV 11 KV panel indicating lamp fitting LED type suitable for 24 volt/30volt DC complete with base complete all as specified.
Supply, install, testing and commissioning in replacemen of unserviceable numerical over current & Earth falt relay type aux voltage 20 to 110 volts AC/DC, CT rating 1A or 5A , with inbuilt master trip & TCS feature. Relay should have minimum 4 digital Binary Inputs and 6 Digital output contacts suitable for AC/DC operation universel type including wiring of the relay with 1.5 Sqmm PVC insulated unsheted copper wire with numbering tags, thimble, insulation material, nut bolts etc complete all as specified and directed. Cat part No.MC61A of make L&T or equivalent model in specified makes ie siemens/Alstom/ABB/JVS as approved by GE
Disconnecting & taking down old existing unserviceable MCCB of any description and in any position complete all as specified and directed.
Supplying and fixing MCCB, 630 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity Icu100% = 35/36 KA with adjustable thermal & magnetic setting, complete all as specified and directed. Make : Legrand/Indo Asian/Schnieder/Havells Cat No-IHLLSECF0630
Supplying and fixing MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Ics = 100% of Icu 35/36 kA with adjustable thermal & magnetic setting, complete all as specified and directed. Make : Legrand/Indo Asian/Schnieder/Havells Cat No-IHLLSECF0400
Supplying and fixing MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, complete all as specified and directed. Make : Legrand/Indo Asian/Schnieder / L&T / Havells Cat No-IHLLSECF0250
Supplying and fixing MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, complete all as specified and directed. Make : Legrand/Indo Asian/Schnieder / L&T / Havells Cat No-IHLLSECF0200
Supplying and fixing MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder / L&T
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete all as specified and directed.
Supplying, fixing, testing and commissioning in replacement of front operated ON Load type changeover switch 4 pole, 415 volts, 125 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHCNFO0125 of make Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T
Supplying, fixing, testing and commissioning in replacement of front operated ON Load type changeover switch 4 pole, 415 volts, 200 Amps without sheet enclosure complete all as specified and directed. Cat part No: IHCNFO0200 of make Havells or Make Indo Asian equivalent in Legrand/Indo Asian/Schnieder / L&T
Supplying, fixing, testing and commissioning in replacement of of side operated OFF Load type changeover switch 4 pole, 415 volts, 400 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0400 of make Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T
Supplying, fixing, testing and commissioning in replacement of of side operated OFF Load type changeover switch 4 pole, 415 volts, 630 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0630 of make Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T
Dismantling, taking down and removing the old existing un serviceable non-functional / broken hinges of any description and in any position of existing feeder pillar boxes/panel boards/feeder pillar boxes etc and supplying and fixing new cold rolled 50 mm long medium weight mild steel butt hinges in position with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed. (Note :- Each hinge point shall be measured as one unit. )
ditto item No. 72 above but supplying and fixing new cold rolled 100 mm long medium weight mild steel butt hinges in position complete all as specified and directed.
Material, labour, testing and commissioning in replacement of UNSV indication lamp (LED type) with showing red, yellow and green in colour of 22.5 mm dia monitor on LT panel board suitable for 240 V AC supply all as specified and directed. Make : L&T /Binay.or equivalent approved.
Material, labour, testing and commissioning in replacement of UNSV of digital electronic volt meter 0-500 V range suitable for LT 415 Volts panel flush pattern square type 96mmX96mm with adopter complete with button all as specified and directed. Make : ENERCON/AE Note :- The rate quoted shall be deemed to including the following:- (i) Control wiring for auxiliary supply 230 Volts AC if required. (ii) Cutting the sheet of the panel to suit with existing panel if required. (iii) Calibration and testing the meter.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead 32X 6 mm GI strip, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate No .3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh incl necessary excavation and earth work in any type of soil, and PCC (1: 3 : 6) type C-1 (using 20 mm graded black trap/ granite/ Basalt stone aggregate) for earth pit with 40x40x6 mm mild steel angle iron frame for cover and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1(using 20 mm graded black trap/granite/ basalt stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle, complete all as specified & directed .
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead 4 Sqmm GI wire, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate No . 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh incl necessary excavation and earth work in any type of soil, and PCC (1: 3 : 6) type C-1 (using 20 mm graded black trap/ granite/ Basalt stone aggregate) for earth pit with 40x40x6 mm mild steel angle iron frame for cover and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1(using 20 mm graded black trap/granite/ basalt stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle, complete all as specified & directed .
Material and labour in replacement of UNSV GI strip of size 32mm x 6mm for laying along the wall/roof on batten or burried in ground or drawn in conduit pipe or fixed to poles or any other situation as directed or as required GI strip of size 32mm x 6mm earth continuity conductor complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor all as specified and directed.
All as per item No. 79 here in above but using 4 mm dia galvanised iron or steel wire complete all as specified and directed.
Disconnecting defective transformer indoor/outdoor of any capacity up to 400 KVA both from HT/LT sides, and then drainage of complete transformer oil. Opening of top cover with due care and removal of all HT/LT winding connections from bushing and then lifting of core by means of tripod and chain pulley with due care for inspection and ascertain it’s serviceability state after keeping it aside. Removal of all sludge and unwanted material from tank and core, lowering of core assembly after carrying out required repairs to the winding and core. In case the repairs which are not possible at site then the transformer has to be taken to the work shop for repairs complete, all as specified and directed. Note :- (i) The cost of transportation shall be paid separately. (ii) The cost of rewinding shall be paid separately.
Taking down of transformers of capacity 63 to 400KVA from transformer plate form/2/4 pole structure with due care after disconnecting all HT/LT connections on pole and then lowering it by means of tripod and chainpully and remounting on transformer plate form /2/4 pole structure after repairs all as directed and specified.
Lifting of Indoor/Outdoor transformer from PCC plateform/2/4 pole structure of concerned substation with the help of mobile crane , loading on truck for transporting to civil workshop at Dehradun city & unloading at workshop, transporting back from workshop after repairs to its existing location complete all as specified and directed .
Material and labour for replacement of worn out HT copper coils made out of super enamelled insulated copper wire all as per existing size and shape including all insulating, binding, varnishing and baking if required complete all as specified and directed.
Material and labour for replacement of worn out LT copper coils made out of super enamelled insulated copper strip all as per existing size and shape including all insulating, binding, varnishing and baking if required complete all as specified and directed.
Re-conditioning of existing HT/ LT copper coils made out of super enamelled insulated copper strip/ wire by providing insulating, binding, varnishing and baking if required complete all as specified and directed by Engineer-in-Charge.
Material and labour for replacement of worn out bushing rod made out of copper with heavy duty double nuts and one washer at both ends suitable for HT side all as exiting size, shape and length complete, all as specified and directed by Engineer-in-Charge suitable for following capacity transformers ;-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of worn out bushing rod made out of copper with heavy duty double nuts and one washer at both ends suitable for LT side all as exiting size, shape and length complete, all as specified and directed by Engineer-in-Charge suitable for following capacity transformers ;-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of worn out porcelain bushing for 11KV HT side indoor /outdoor transformers with rubberised cork sheet washers all as required at site complete, all as directed and specified by Engineer-in-Charge suitable for following capacity transformers:-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of worn out porcelain bushing for 0.433 KV LT side indoor /outdoor transformers with rubberised cork sheet washers all as required at site and as directed suitable for following capacity transformers:-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of worn out off load tap changer all as per existing sample complete, all as specified and directed by Engineer-in-Charge suitable for following capacity of transformers of any make.:-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of UNSV oil temperature gauge /thermometer suitable for transformers all as per existing shape and size for any make and model transformers complete, all as specified and directed.
Material and labour for replacement of worn out neoprene rubberised cork sheet 4 mm thick for transformer top cover all as required at site and as directed by Engineer-in-Charge suitable for following capacity transformers:-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material and labour for replacement of worn out neoprene rubberised cork washer mm thick suitable for HT/LT side bushing of off sizes all as required at site and directed.
Material and labour for replacement of UNSV silica gel breather assembly of any description/capacity and supply & fixing new breather assembly transparent body suitable for 11/0.433 KV transformers of capacity upto 100 KVA complete, all as specified and directed.
All as per item No 95 above but transformer of capacity above 100 KVA but upto 315 KVA complete all as specified and directed.
All as per item No 95 above but transformer of capacity above 315 KVA but upto 400 KVA complete all as specified and directed.
Dehydration/centrifuging of transformer oil by means centrifuging machine electrically operated at site of installation of transformer in running condition of transformer including testing of transformer oil before and after centrifuging from top and bottom of transformer at 4mm gap the BDV should be 40KV complete, all as specified and directed
Supply and topping up of transformer oil of dielectric strength of 60 BDV complete, all as specified and directed.
Preparation of old surface of transformer for painting externally including fins/radiators removal of all rust/oil/grease and unwanted material and then two coats of synthetic enamel metallic paint by means of spray gun at site of installation of transformer complete, all as specified and directed suitable for following capacity of transformers:-
100-200 KVA Transformers.
250-400 KVA Transformers.
Material, labour,testinf and commisssioning Chemical Earthing with copper pipe electrode 3.0 M long having outer pipe dia 50mm & inner pipe dia 44mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical compostion Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% buried in ground by digging a bore of 150mm dia surrounded by soil friendly backfill compound non soluble in water including connection with Copper earth strip 20x3mm upto 7 meter length, making PCC pit of size 0.3mx0.3mx0.3m (inner size) in mix 1:3:6 type CI with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting hook made out of 8mm dia bar and testing on completion to acheive value not more than 0.5 ohm complete all as specified and directed.
Material and labour eathing continuity conductor to wall on batten or buried in ground or drawn in conduit or fixed to pole or any other indicated situation for loop earthing etc, as required 20x3 mm dia copper strip complete, all as specified and directed.
Material and labour for replacement of unserviceable Silica gel crystel for transformer of best quality complete all as specified and directed.
JS CONSTRUCTION COMPANY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .