Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹6.2 LAccepted-AOC | L-1 | Accepted-AOC AOC |
Tender Value
₹4.9 L
EMD Value
₹9,800
Closing Date
1 Jul 2019, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Division PWD B and R Br., Ambala Cantt
Const. of New Building of 100 Bed Hospital in LNJP Hospital in Phase 1 at Kurukshetra (Providing E.I internal services) (Balance Electrical Work) (Recall).
2019_HRY_80008_2
PWD/Elect-KNL/Elect-AMB/10505
Open Tender
Construction Works
Works
180 days
Ambala
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Executive Engineer, Elect. Division PWD BandR Br.
₹9,800
8 Oct 2021
20 Jun 2019
3 Jul 2019
21 Jun 2019
1 Jul 2019
21 Jun 2019
Amount
1 Moulded case Circuit breakers. (( c ))
Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. (31.12 (c))
1.1 15 amp.to 60 amp. 415 V ,10 KA 3-phase. (31.12 c (i))
2 (Q) Earthing (31.22)
2.1 Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as equired. (31.22(iv))
2.2 Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. (31.22(v))
2.3 Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required . (31.22(x))
2.4 Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material. (31.22(xiv))
3 (R) Lightning conductor (a) Copper. (31.23)
3.1 Supply and erection of copper tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with suitable copper stapples of same size. (31.23 (vii))
4 (b) Lightning conductor Galvanised iron. (31.24)
4.1 Supply and erection of 60 cm. X 60 cm. X 6 mm thick galvanised Iron plate including nacessary bolts and nuts to G.I. tape . (31.24 (iv))
4.2 Pdg. Standard watering tank including down pipe and C.I. cover with locking arrangement etc. (31.24 (v))
4.3 Supply and erection of 20 mm x 3 mm thick lightning conductor G.I. tape fixed with suitable G.I. stapples of same size. (31.24 (vi))
4.4 Supply and erection of G.I. tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with G.I. stapples of same size. (31.24 (vii))
4.5 Supply and erection of 25 mm dia meter 1.5 metre long lightning G.I. tube rod tapered in to a point at the top with 16 cm. X 16 cm x 3 mm thick G.I. base plate and necessary nuts and bolts with washer. (31.24 (viii))
4.6 Prioviding and fixing , testing joint made of 20mm x 3mm thick G.I. strips 125mm long with 4 Nos. G.I. bolts and nuits, check nuts with washer complete. (31.24 (ix))
5 Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . (31.26)
5.1 16 Sq. mm 4 Core Cable . (31.26 (xI) Ard.)
5.2 25 Sq. mm 4 Core Cable . (31.26 (xIi) Ard.)
5.3 35 Sq. mm 4 Core Cable . (31.26 (xIii) Ard.)
5.4 50 Sq. mm 4 Core Cable . (31.26 (xIiii) Ard.)
5.5 70 Sq. mm 3.5 Core Cable . (31.26 (xxviii) Ard.)
5.6 95 Sq. mm 3.5 Core Cable . (31.26 (xxix) Ard.)
6 Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. (31. 40)
6.1 Size 25 sqmm ( 7 / 2.14mm). ( 31.40(vii))
7 Supply and erection of double door sheet steel enclosures distribution boards suitable for MCBs and ELCBs etc. recessed in wall including bonding to earth with all labour and material requared complete the job in all respect upto the entire satisfaction of the Engineer-in Charge of the work. (31.41)
7.1 4-way, TP & N (Vertical) (8+12) (31.41 (ix))
8 Supply, Installation, Testing and Commissioning of Wall/ free standing flooor mounting dust & vermin proof compartmentalized cubical panel made out of 2 mm thick CRCA sheet, required hardware 3 mm thick bakelite sheet provided all along the bus bar and cable alley separating switches compartment and supporting suitable channel duly painted by 2 coat of Zinc/Red oxide primer followed by 2 coats of powder coating in grey or required shade after rinsing. The panel having PU/Neoprene rubber gasket of not less than 3 mm thicness seperate detacable gland plate MS base channel hinged door with inter locking arrangement for equipment/switch wear. (31.63)
Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3 mm thick for separately cable alley to BBC from switch chamber Extended solid copper bars up to cable cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors withdetachable extension type structure. The panel will be complete with control wirring (copper) and fuse protection.(only outer area on all sides shall be measured) ()
9 Supply and Fixing of copper bus bar duly tinned by means of SMC / DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending, cutting in required shape and size and insulation with color coding heat shrinkable PVC insulation complete in all respect. (31.64)
10 Supply and Fixing of rotary handle for ON / OFF operation of existing MCCB in the LT panel including fixing the same in position with all labour and material to required to complete the job in all respect. (31.66)
10.1 Rotary Handle up to 125 Amp., MCCB (( i ))
10.2 Rotary Handle above 125 Amp., MCCB (( ii ))
11 Supply and erection of module case circuit breaker single pole/ 4 pole on wall /on existing pedestal including bounding to earth and making necessary connection required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. (31.69)
11.1 4 pole MCCB 100 amp (v)
12 Supply & erection of cable tray made out of 2 mm thick galavanised perforated sheet steel including erection of the same on wall or ceiling with necessary fixture and other material required to complete the Job in all respect upto the Entire statisfaction of Engineer-in-Charge of the work. (31.81)
12.2 50 x 150 mm (ii)
12.3 50 x 300 mm (iii)
13 Supply & erection of factory manufactureed cable tray cover made of 16g GI Sheet complete with Fastoner Nuts bots and in position including all petty material required to complete the Job in all respect upto the Entire statisfaction of Engineer in Charge of the work (31.82)
13.1 Suitable for 40 x 100 mm (i)
13.2 Suitable for 50 x 150 mm (ii)
13.3 Suitable for 50 x 300 mm (iii)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .