| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-AOC 6 KRIPANATH DUTTA ROAD KOLKATA 700 002 | KOLKATA | KOLKATA | WEST BENGAL | 700002 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹3.6 L+₹7,311.69 (2.08%)Rejected-Finance 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L2 | Rejected-Finance higher than L1 | |
| 3 | L3₹3.7 L+₹14,563.79 (4.14%)Rejected-Finance 17 1 ABHOY HALDER LANE KOLKATA | KOLKATA | L3 | Rejected-Finance higher than L1 |
Tender Value
Refer Docs
EMD Value
₹7,500
Closing Date
19 Mar 2025, 12:00 pmClosed
EXECUTIVE ENGINEER
Utility_Bldg__Beside_Delhi_Public_School_AA_ID_New_Town_Kol_700156
Overhauling of 33KV Breaker and LT panel with allied works at DPS-IC, AA-I under NTK Project.
2025_PHED_824766_23
PHE/NTKMD/e-20 of 2024-25
Open Tender
Project Work
Item Wise
30 days
WORK
Please refer Tender documents.
7 documents required · 7 mandatory
₹7,500
16 May 2025
8 Mar 2025
21 Mar 2025
8 Mar 2025
19 Mar 2025
8 Mar 2025
Amount
Overhauling, servicing, testing complete within de-moistening, desulphating of 33KV HT breaker panel after dismantling of all equipment part by part cleaning by WD40 and remove all carbon particle and sulphation, internal busbar and breaker housing, cleaned by carbon cleaner, checking of tightness of all busbar insulation resistance measurement taken by 5KV magger, all CT removed from the base side of the panel and cleaned thoroughly and hot blowing all supporting insulator and also testing and calibration of the relays for 33KV breaker with high set relay M pact, SCB release, shut trip, circuit alarm trip, annunciator circuit calibration of all meters, transformer test, earth test all complete as per direction and upto entire satisfaction of EIC including servicing & overhauling of 415V PDB with allied all LT panels, battery charger at substation of DPS-IC including servicing of all air circuit breaker. For LT MCC panel : A) Thorough cleaning of entire MCC panel & lighting. B) Motor Protection Relay Setting Checking C) Testing of all MCCB, MCB, Contactor, SFU, CT etc. D) Water Level Sensor And Interlocking With Motor Checking E) All tightness checking. For Battery Charger : Thorough Overhauling of battery charger, De-sulpheriztion & maintenance of battery (Report should be submitted as per Annexure I, II , III & IV)
De-hydration & filtration of 3 nos. 1250KVA transformer oil of the existing transformer. (1545 ltr. x 3 nos.) = 4635 ltrs.
Dielectric strength test as per specification of the I.E. rules (3 Nos. 1250KVA transformer)
Supply & reflling of Silica gel.
Transportation charges of filtration machine (up and down).
N.B. : Within one year after the overhauling if any breakdown will occur, the agency should attend the site within two hours and complete the work within six hours in emergency basis.
GST @18% of Total Value in Amount
CESS @1% of Total Value in Amount
WEST BENGAL ENGINEERING CO. (BID ID -6234170)
ORIENTAL ENGINEERING CO. (BID ID -6235190)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .